TITAN HUNG YEN PHASE 1 - YM1A
LEED CORE & SHELL
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
ARDOR GROUP (WWW.ARDORARCH.COM)
Vietnam Green Building Council Board Member
EDGE Green Design Certification Advisory Board
HCMC Green Architecture Club Vice President
© All Rights Reserved By Ardor Green @ 09/2023
Agenda / Nội dung Trình bày
LEED CORE & SHELL, DETAIL ASSESSMENT
1. LEED Schedule
Tiến Độ LEED
2. LEED Assessment For Titan Hung Yen - Phase 1
Đánh Giá LEED Cho Dự Án Titan Hung Yen - Phase 1
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Certification Process / Quy trình LEED
Basic Design
Design
Development
Technical Specification &
Construction Drawings
Tendering
❖ Integrative process
❖ LEED Detail Assessment
❖ LEED Preliminary
❖ Detailed Building Energy Simulation
Guidance for
❖ Daylighting Simulation
Tender
Assessment
❖ LEED Registration
❖ Water Uses Assessment
❖ LEED
Construction Stage
❖ LEED Guidance for Sustainable
Construction
❖ LEED Testing & Commissioning
❖ LEED Final Submission
❖ LEED Design Submission
GBCI Registration Fee
GBCI Design Review Fee
LEED Design Review
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
GBCI Final Review Fee
LEED Final Review
Agenda / Nội dung Trình bày
LEED CORE & SHELL, PRELIMINARY ASSESSMENT
1. LEED Schedule
Tiến Độ LEED
2. LEED Assessment For Titan Hung Yen - Phase 1
Đánh Giá LEED Cho Dự Án Titan Hưng Yên - Phase 1
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
9 LEED Categories / 9 Hạng mục LEED
Integrative Process / Quy trình tích hợp
Energy and Atmosphere / Năng lượng và Khí quyển
Promote reaching across disciplines to incorporate diverse team
Promote better building energy performance through innovative
members during the pre-design period.
strategies.
Khuyến khích tương tác giữa các bộ môn để có một nhóm dự án tích
Nâng cao hiệu quả năng lượng công trình cao hơn thông qua các
hợp và đa dạng trong giai đoạn tiền thiết kế.
chiến lược sáng tạo.
Materials and Resources / Vật liệu và Tài nguyên
Location and Transportation / Địa điểm và Vận chuyển
Projects within relatively dense areas, near diverse uses, with access to
a variety of transportation options.
Các dự án trong khu vực mật độ lớn, gần các tiện ích đa dạng, tiếp cận
Encourage using sustainable building materials and reducing waste.
Khuyến khích việc sử dụng các vật liệu công trình bền vững và giảm
rác thải.
Indoor Environmental Quality / Chất lượng Môi trường
đến các hệ thống giao thông công cộng.
Promote better indoor air quality and access to daylight and views.
Nâng cao chất lượng không khí trong nhà tốt hơn và cải thiện chiếu sáng
Sustainable Sites / Khu đất Bền vững
tự nhiên và tầm nhìn chất lượng
Encourage strategies that minimize the impact on ecosystems and
Innovation / Sáng tạo
water resources.
Khuyến khích các chiến lược giảm tác động lên hệ sinh thái và nguồn
nước.
Address sustainable building expertise as well as design measures not
covered in LEED.
Các biện pháp thiết kế bền vững chưa được đề cập trong LEED hoặc
các giải pháp vượt trội
Water Efficiency / Hiệu quả Nước
Regional Priority / Ưu tiên Địa phương
Promote smarter use of water, inside and out, to reduce potable water
Address regional environmental priorities for buildings in different
consumption.
geographic regions.
Đề cao sử dụng nguồn nước thông minh hơn, bên trong và bên ngoài,
Đề cập đến các ưu tiên địa phương cho các công trình tại các vùng địa
để giảm lượng nước thủy cục của khu vực
lý khác nhau.
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Scorecard – Titan Hung Yen Phase 1
Y
1
?
4
2
14
2
LTc1 LEED for Neighborhood Development Location
LTc2 Sensitive Land Protection
1 LTc3 High Priority Site
20
20
2
3
7
Y
Y
3
6 LTc4 Surrounding Density and Diverse Uses
6
1
1 MRc2
6 LTc5 Access to Quality Transit
6
1
1 MRc3
1 LTc6 Bicycle Facilities
LTc7 Reduced Parking Footprint
LTc8 Green Vehicles
1
1
1
2
2 MRc4
MRc5
IPc1
2
1
1
6
Y
1
1
N
0
1
Location and Transportation
Sustainable Sites
5
SSp1
SSc1
1 SSc2
1 SSc3
3 SSc4
SSc5
1
Integrative Process
Construction Activity Pollution Prevention
Site Assessment
Site Development - Protect or Restore Habitat
Open Space
Rainwater Management
Heat Island Reduction
11
Required
1
2
1
3
2
1
SSc6 Light Pollution Reduction
1
1
SSc7 Tenant Design and Construction Guidelines
1
8
Y
Y
Y
1
6
0
1
13 0
Y
Y
Y
Y
3
WEp1
WEp2
WEp3
1 WEc1
WEc2
2 WEc3
WEc4
20
Water Efficiency
Outdoor Water Use Reduction
Indoor Water Use Reduction
Building-Level Water Metering
Outdoor Water Use Reduction
Indoor Water Use Reduction
Cooling Tower Water Use
Water Metering
Energy and Atmosphere
EAp1 Fundamental Commissioning and Verification
EAp2 Minimum Energy Performance
EAp3 Building-Level Energy Metering
EAp4 Fundamental Refrigerant Management
6 EAc1 Enhanced Commissioning
11
7 EAc2 Optimize Energy Performance
1
EAc3 Advanced Energy Metering
2 EAc4 Demand Response
3 EAc5 Renewable Energy Production
1
EAc6 Enhanced Refrigerant Management
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
2 EAc7 Green Power and Carbon Offsets
11
Required
Required
Required
2
6
2
1
33
Required
Required
Required
Required
6
18
1
2
3
1
2
0
Materials and Resources
7
MRp1
MRp2
3 MRc1
7
Y
Y
2
3
1
1
1
5
0
1
1
1
1
1
Indoor Environmental Quality
2
EQp1
EQp2
EQc1
EQc2
EQc3
EQc7
1 EQc8
4
1
1
1
1
0
55
3
Minimum Indoor Air Quality Performance
Environmental Tobacco Smoke Control
Enhanced Indoor Air Quality Strategies
Low-Emitting Materials
Construction Indoor Air Quality Management Plan
Daylight
Quality Views
Innovation
1
LTc7
MRc5
INc1
INc2
1 Credit
Credit
1
Storage and Collection of Recyclables
Construction and Demolition Waste Management Planning
Building Life-Cycle Impact Reduction
Building Product Disclosure and Optimization
Environmental Product Declarations
Building Product Disclosure and Optimization
Sourcing of Raw Materials
Building Product Disclosure and Optimization - Material Ingredients
Construction and Demolition Waste Management
Regional Priority
EAc2
SSc2
WEc2
WEc1
52
Optimize Energy Performance
Site Development - Protect or Restore Habitat
Indoor Water Use Reduction
Outdoor Water Use Reduction
TOTALS
58
2
2
2
2
10
Required
Required
2
3
1
3
1
6
Reduced Parking Footprint
Construction and Demolition Waste Management
Green Awareness
Daylight for Toilet
Innovation
LEED Accredited Professional
0
14
Required
Required
6
Possible Points:
1
1
1
1
1
1
4
1
1
1
1
110
LEED Prerequisite - YM1A / LEED Tiêu chí Bắt ḅc
SSp1
EAp3
EAp4
YP2C
Design Pending
WEp2
WEp1
MRp1
EAp1
EAp2 - EQp1
MRp2
YEN MY
No
Design Pending
No
PREREQUISITE
REQUIREMENTS / TASKS
Construction Activity Pollution Prevention
Sustainable construction methods
ARDOR's FEEDBACKS (27/09/2023)
X
X
SSp1
X
X
WEp1 Outdoor Water Use Reduction
Native/Adaptive Plants - Drip or Sprinkler Irrigation
Compliant (YM1A-MEP-MP-PL-205)
X
X
WEp2 Indoor Water Use Reduction
Water fixtures meet the requirements of flowrate
Compliant (YM1A Sanitary Catalogue)
X
X
WEp3 Building-Level Water Metering
Water meter for whole project water uses
Compliant (YM1A-MEP-MP-LSCH-101)
X
X
EAp1
Fundamental Commissioning and Verification
3rd-party Fundamental Commissioning
X
X
EAp2
Minimum Energy Performance
X
X
EAp3
Building-Level Energy Metering
Compliant
ASHRAE 90.1-2010, Mandatory Provision for Envelop, HVAC, Lighting, Plumbing,
ARCH:
etc.
01-YM1A-MA-List-V1.3(ARC)
MEP: 05-YM1A-MEP-TECHNICAL SHEET
Energy meter/monitor for whole building energy uses
Compliant (YM1A-MEP-MP-EE-101,102&103)
X
X
EAp4
Fundamental Refrigerant Management
No CFC-based refrigerant
X
X
MRp1 Storage and Collection of Recyclables
X
X
MRp2 Construction and Demolition Waste Management Planning Sustainable construction methods
X
X
EQp1
Minimum Indoor Air Quality Performance
ASHRAE 62.1 - 2010, Ventilation system
- Outdoor air intake monitoring
- CO2 monitoring
Compliant
(01. YM1A_MEP-ACMV-CAL-001-V1.0)
(YM1A-MEP-NX1,NX7,NX8-ACMV-101)
X
X
EQp2
Environmental Tobacco Smoke Control
Outdoor smoking area
Compliant (YM1A-ARC-UL-PL-01)
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
Collection areas for recyclable materials
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
Compliant (YM1A-ARC-UL-PL-01)
EQp2
LEED Integrative Process - YM1A / LEED Quy trình Tích hợp
1. IP - INTEGRATIVE PROCESS
•
To support high performance, cost effective project
outcomes through an early analysis of the
interrelationships among systems
•
Perform a preliminary simple box energy modeling
analysis (site consitions, building envelope, lighting
levels,…)
•
Perform a preliminary water budget analysis (indoor,
outdoor water demand, process water demand, supply
sources)
•
Document how the above analysis in the owner’s
project requirements and basic of design.
YP2C
1
1
0
YEN MY
0
1
1
0
0
IPc1
INTEGRATIVE PROCESS
REQUIREMENTS / TASKS
ARDOR's FEEDBACKS (27/09/2023)
Integrative Process
ARD to do the documents
Compliant
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Location and Transportation - YM1A / LEED Địa điểm và Vận chuyển
2. LT - LOCATION AND TRANSPORTATION
LTc2: Project location in areas of no sensitive land - không phải đất nông nghiệp (2
points)
LTc3: Project location in high priority site (2 points): landmine removal report
+ Vùng kinh tế kém phát triển, tỷ lệ hộ nghèo cao: không đáp ứng yêu cầu, sẽ trình
nộp báo cáo rà phá bom mìn
LTc4: Additional public services (1 point): Not compliant, need to have 4 public
services
+ Mật độ xây dựng xung quanh thấp (<0.5): không đáp ứng yêu cầu, phải có 4 tiện ích
YP2C
6
2
YEN MY
12
2
2
14
2
2
2
4
LOCATION AND TRANSPORTATION
REQUIREMENTS / TASKS
ARDOR's FEEDBACKS (11/12/2023)
LTc1 LEED for Neighborhood Developm ent Location
Locate the project on LEED neighborhood area
Not compliant
PARTY
LTc2 Sensitive Land Protection
No sensitive land (farmland, floodplain, habitat, w etland)
Compliant
FPV
1
LTc3 High Priority Site
Locate the project on an infill location in a historic district
ARDOR w ill submit for GBCI construction review
FPV
4
6
LTc4 Surrounding Density and Diverse Uses
Site survey for surrounding density
Site Visit after construction finish
6
6
LTc5 Access to Quality Transit
Not compliant
1
1
LTc6 Bicycle Facilities
Within a 400-meter w alking distance of existing or planned bus
Bicycle spaces for 5% of project occupancy and 2.5% of peak
visitors
1 show er facility for the first 100 project occupants and additional
show er facility for every 150 occupants thereafter
1
2
1
1
LTc7 Reduced Parking Footprint
60% reduction of base ratio
1
1
LTc8 Green Vehicles
5% of total car parking spaces for electrical cars, 2% for chargers
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
ARD, FPV, Design
Consultant
FPV
Not compliant. No bicycle netw ork
4 car-parking spaces. Compliant
(YM1A-ARC-MP-01)
Compliant (YM1A-ARC-MP-01)
ARD
Design Consultant
LEED Location and Transportation - YM1A / LEED Địa điểm và Vận chuyển
2. LT - LOCATION AND TRANSPORTATION
Project location in areas of no sensitive land (2 points - no incremental cost)
Project location in high priority site (2 points - no incremental cost)
Additional public services (1 point)
LTc7: Reduced carparking (1 point)
4 chỗ đậu xe hơi: compliant
Car parking: 60% reduction from the
base ratios:
1.99 spaces/100sqmGFA - Institute of
Transportation Engineers’ Transportation
Planning Handbook, 3rd edition
Green vehicles
- Electrical parking: 5% of all car parking
spaces
- EV charger: 2% of all car parking spaces
LTc8: EV chargers for Electric cars (1 point)
1 chỗ cho xe điện và trụ sạc điện
YP2C
6
2
YEN MY
12
2
2
14
2
2
2
4
LOCATION AND TRANSPORTATION
REQUIREMENTS / TASKS
ARDOR's FEEDBACKS (11/12/2023)
LTc1 LEED for Neighborhood Developm ent Location
Locate the project on LEED neighborhood area
Not compliant
PARTY
LTc2 Sensitive Land Protection
No sensitive land (farmland, floodplain, habitat, w etland)
Compliant
FPV
1
LTc3 High Priority Site
Locate the project on an infill location in a historic district
ARDOR w ill submit for GBCI construction review
FPV
4
6
LTc4 Surrounding Density and Diverse Uses
Site survey for surrounding density
Site Visit after construction finish
6
6
LTc5 Access to Quality Transit
Not compliant
1
1
LTc6 Bicycle Facilities
Within a 400-meter w alking distance of existing or planned bus
Bicycle spaces for 5% of project occupancy and 2.5% of peak
visitors
1 show er facility for the first 100 project occupants and additional
show er facility for every 150 occupants thereafter
1
2
1
1
LTc7 Reduced Parking Footprint
60% reduction of base ratio
1
1
LTc8 Green Vehicles
5% of total car parking spaces for electrical cars, 2% for chargers
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
ARD, FPV, Design
Consultant
FPV
Not compliant. No bicycle netw ork
4 car-parking spaces. Compliant
(YM1A-ARC-MP-01)
Compliant (YM1A-ARC-MP-01)
ARD
Design Consultant
LEED Sustainable Sites - YM1A / LEED Khu đất Bền vững
3. SS - SUSTAINABLE SITES
SSc1: Site assessment - Environmental Impact Assessment is required (1
point)
Phê duyệt Đánh giá tác động Môi trường đã được cung cấp
Restore 15% of site area by native/adaptive plants (1 point)
Heat island reduction by Reflective material for Roof
and pavement (2 points)
External lighting fixtures meet the requirements of BUG rating (1 point)
Tenant Design and Construction Guideline published (1 point)
YP2C
6
0
YEN MY
5
1
1
6
0
SUSTAINABLE SITES
REQUIREMENTS / TASKS
SSc1
Site Assessment
To do the site asessment following to LEED forms
1
SSc2
Site Development - Protect or Restore Habitat
1
SSc3
Open Space
5
1
1
1
1
3
3
Restore 15% of site area by native/adaptive plants (Green Area) - 1 point
Restore 25% for 2 points
30% of site area is open spaces
SSc4
Rainwater Management
Rainwater tank or bioretention to capture total runoff volume of percentile
raDesign Consultantall event:
- 80th: 1 point;
- 85th: 2 points;
- 90th: 3 points.
ARDOR's FEEDBACKS (27/09/2023)
Compliant (YM1A-ARC-MP-01)
Compliant
ARCH: 01-YM1A-MA-List-V1.3(ARC)
2
2
SSc5
Heat Island Reduction
Reflective material for Roof (SRI > 82) and pavement (SRI > 33)
Light color concrete asphalt for internal roads.
1
1
SSc6
Light Pollution Reduction
External lighting fixtures meet the requirements of BUG rating
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
1
1
SSc7
Tenant Design and Construction Guidelines
Publish for tenants an illustrated document, to educate tenants in
implementing sustainable design and construction features in their tenant
improvement buildouts.
Compliant
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Sustainable Sites - YM1A / LEED Khu đất Bền vững
3. SS - SUSTAINABLE SITES
Site assessment - Environmental Impact Assessment is required (1 point)
SSc2: Restore 15% of site area by native/adaptive plants (1 point)
Mật độ cây xanh 21%
Heat island reduction by Reflective material for Roof
and pavement (2 points)
External lighting fixtures meet the requirements of BUG rating (1 point)
Tenant Design and Construction Guideline published (1 point)
YP2C
6
0
YEN MY
5
1
1
6
0
SUSTAINABLE SITES
REQUIREMENTS / TASKS
SSc1
Site Assessment
To do the site asessment following to LEED forms
1
SSc2
Site Development - Protect or Restore Habitat
1
SSc3
Open Space
5
1
1
1
1
3
3
Restore 15% of site area by native/adaptive plants (Green Area) - 1 point
Restore 25% for 2 points
30% of site area is open spaces
SSc4
Rainwater Management
Rainwater tank or bioretention to capture total runoff volume of percentile
raDesign Consultantall event:
- 80th: 1 point;
- 85th: 2 points;
- 90th: 3 points.
ARDOR's FEEDBACKS (27/09/2023)
Compliant (YM1A-ARC-MP-01)
Compliant
ARCH: 01-YM1A-MA-List-V1.3(ARC)
2
2
SSc5
Heat Island Reduction
Reflective material for Roof (SRI > 82) and pavement (SRI > 33)
Light color concrete asphalt for internal roads.
1
1
SSc6
Light Pollution Reduction
External lighting fixtures meet the requirements of BUG rating
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
1
1
SSc7
Tenant Design and Construction Guidelines
Publish for tenants an illustrated document, to educate tenants in
implementing sustainable design and construction features in their tenant
improvement buildouts.
Compliant
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Sustainable Sites - YM1A / LEED Khu đất Bền vững
3. SS - SUSTAINABLE SITES
Site assessment - Environmental Impact Assessment is required (1 point)
Restore 15% of site area by native/adaptive plants (1 point)
SSc5: Heat island reduction by Reflective material for Roof
and pavement (2 points)
Mái có hệ số SRI > 82 (Đông Á, Bluescope,…)
External lighting fixtures meet the requirements of BUG rating (1 point - no
incremental cost)
High reflective roof: SRI > 82
Tenant Design and Construction Guideline published (1 point)
YP2C
6
0
YEN MY
5
1
1
6
0
SUSTAINABLE SITES
REQUIREMENTS / TASKS
SSc1
Site Assessment
To do the site asessment following to LEED forms
1
SSc2
Site Development - Protect or Restore Habitat
1
SSc3
Open Space
5
1
1
1
1
3
3
Restore 15% of site area by native/adaptive plants (Green Area) - 1 point
Restore 25% for 2 points
30% of site area is open spaces
SSc4
Rainwater Management
Rainwater tank or bioretention to capture total runoff volume of percentile
raDesign Consultantall event:
- 80th: 1 point;
- 85th: 2 points;
- 90th: 3 points.
ARDOR's FEEDBACKS (27/09/2023)
Compliant (YM1A-ARC-MP-01)
Compliant
ARCH: 01-YM1A-MA-List-V1.3(ARC)
2
2
SSc5
Heat Island Reduction
Reflective material for Roof (SRI > 82) and pavement (SRI > 33)
Light color concrete asphalt for internal roads.
1
1
SSc6
Light Pollution Reduction
External lighting fixtures meet the requirements of BUG rating
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
1
1
SSc7
Tenant Design and Construction Guidelines
Publish for tenants an illustrated document, to educate tenants in
implementing sustainable design and construction features in their tenant
improvement buildouts.
Compliant
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Sustainable Sites - YM1A / LEED Khu đất Bền vững
3. SS - SUSTAINABLE SITES
Site assessment - Environmental Impact Assessment is required (1 point)
Restore 15% of site area by native/adaptive plants (1 point)
Heat island reduction by Reflective material for Roof
and pavement (2 points - no incremental cost)
SSc6: External lighting fixtures meet the requirements of BUG rating (1
point)
Spec đèn đường đáp ứng yêu cầu thang đo B (backlight), U (uplight)
và G (Glare)
SSc7: Tenant Design and Construction Guideline published (1 point)
Tài liệu hướng dẫn cho thuê có thể hiện các đặc điểm bền vững
YP2C
6
0
YEN MY
5
1
1
6
0
SUSTAINABLE SITES
REQUIREMENTS / TASKS
SSc1
Site Assessment
To do the site asessment following to LEED forms
1
SSc2
Site Development - Protect or Restore Habitat
1
SSc3
Open Space
5
1
1
1
1
3
3
Restore 15% of site area by native/adaptive plants (Green Area) - 1 point
Restore 25% for 2 points
30% of site area is open spaces
SSc4
Rainwater Management
Rainwater tank or bioretention to capture total runoff volume of percentile
raDesign Consultantall event:
- 80th: 1 point;
- 85th: 2 points;
- 90th: 3 points.
ARDOR's FEEDBACKS (27/09/2023)
Compliant (YM1A-ARC-MP-01)
Compliant
ARCH: 01-YM1A-MA-List-V1.3(ARC)
2
2
SSc5
Heat Island Reduction
Reflective material for Roof (SRI > 82) and pavement (SRI > 33)
Light color concrete asphalt for internal roads.
1
1
SSc6
Light Pollution Reduction
External lighting fixtures meet the requirements of BUG rating
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
1
1
SSc7
Tenant Design and Construction Guidelines
Publish for tenants an illustrated document, to educate tenants in
implementing sustainable design and construction features in their tenant
improvement buildouts.
Compliant
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Sustainable Sites - YM1A / LEED Khu đất Bền vững
3. SS - SUSTAINABLE SITES
Site assessment - Environmental Impact Assessment is required (1 point)
Restore 15% of site area by native/adaptive plants (1 point)
Heat island reduction by Reflective material for Roof
and pavement (2 points - no incremental cost)
SSc6: External lighting fixtures meet the requirements of BUG rating (1
point)
Spec đèn đường đáp ứng yêu cầu thang đo B (backlight), U (uplight)
và G (Glare)
SSc7: Tenant Design and Construction Guideline published (1 point)
Tài liệu hướng dẫn cho thuê có thể hiện các đặc điểm bền vững - Ap dụng
template của Frasers
YP2C
6
0
YEN MY
5
1
1
6
0
SUSTAINABLE SITES
REQUIREMENTS / TASKS
SSc1
Site Assessment
To do the site asessment following to LEED forms
1
SSc2
Site Development - Protect or Restore Habitat
1
SSc3
Open Space
5
1
1
1
1
3
3
Restore 15% of site area by native/adaptive plants (Green Area) - 1 point
Restore 25% for 2 points
30% of site area is open spaces
SSc4
Rainwater Management
Rainwater tank or bioretention to capture total runoff volume of percentile
raDesign Consultantall event:
- 80th: 1 point;
- 85th: 2 points;
- 90th: 3 points.
ARDOR's FEEDBACKS (27/09/2023)
Compliant (YM1A-ARC-MP-01)
Compliant
ARCH: 01-YM1A-MA-List-V1.3(ARC)
2
2
SSc5
Heat Island Reduction
Reflective material for Roof (SRI > 82) and pavement (SRI > 33)
Light color concrete asphalt for internal roads.
1
1
SSc6
Light Pollution Reduction
External lighting fixtures meet the requirements of BUG rating
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
1
1
SSc7
Tenant Design and Construction Guidelines
Publish for tenants an illustrated document, to educate tenants in
implementing sustainable design and construction features in their tenant
improvement buildouts.
Compliant
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
LEED Water Efficiency - YM1A / LEED Hiệu quả Nước
4. SS - WATER EFFICIENCY
WEc1: Outdoor water use
Native/Adaptive Plants - Drip / Sprinkler irrigation or Hand watering with flow
control (1 point)
Danh sách cây bản địa/thích nghi
Áp dụng hệ tưới drip hoặc sprinkler hoặc tưới tay có đầu hạn chế lưu lượng
Indoor water use
Low-flow toilets, urinal, faucet and showerheads (6 points)
Water meters for irrigation, indoor fixtures (1 point)
YP2C
8
1
0
YEN MY
3
1
6
8
1
3
1
6
2
1
0
2
1
WATER EFFICIENCY
REQUIREMENTS / TASKS
ARDOR's FEEDBACKS (27/09/2023)
WEc1 Outdoor Water Use Reduction
Native/Adaptive Plants - Drip or Sprinkler irrigation - Turfgrass < 40% (1
point)
Alternative sources (Rainwater, waste water…) tank for Irrigation (1 point)
Compliant (YM1A-MEP-MP-LSCH-101)
WEc2 Indoor Water Use Reduction
Water fixtures meet the requirements of flowrate (6 points);
Rainwater tank for Indoor flushing (1 Innovation point)
Compliant (YM1A Sanitary Catalogue)
WEc3 Cooling Tower Water Use
WEc4 Water Metering
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
Condensate water test for concentration level (1 point)
Chemical treatment for makeup water to increase the cooling tower cycles
(1 point)
Water meters for irrigation, indoor fixtures, cooling tower water, re-used
rainwater
Compliant (YM1A-MEP-MP-LSCH-101)
LEED Water Efficiency - YM1A / LEED Hiệu quả Nước
4. SS - WATER EFFICIENCY
Outdoor water use
Native/Adaptive Plants - Sprinkler irrigation (1 point - costing for sprinkler
system)
WEc2: Indoor water use
Low-flow toilets, urinal, faucet and showerheads (6 points)
Thiết bị vệ sinh đáp ứng yêu cầu về lưu lượng
WEc4: Water meters for irrigation, indoor fixtures (1 point)
Đồng hồ nước cho tưới tiêu và nước dùng cho TBVS
WEc4
YP2C
8
1
0
YEN MY
3
1
6
8
1
0
3
1
6
2
1
WEc2
2
1
WATER EFFICIENCY
REQUIREMENTS / TASKS
ARDOR's FEEDBACKS (27/09/2023)
WEc1 Outdoor Water Use Reduction
Native/Adaptive Plants - Drip or Sprinkler irrigation - Turfgrass < 40% (1
point)
Alternative sources (Rainwater, waste water…) tank for Irrigation (1 point)
Compliant (YM1A-MEP-MP-LSCH-101)
WEc2 Indoor Water Use Reduction
Water fixtures meet the requirements of flowrate (6 points);
Rainwater tank for Indoor flushing (1 Innovation point)
Compliant (YM1A Sanitary Catalogue)
WEc3 Cooling Tower Water Use
WEc4 Water Metering
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
Condensate water test for concentration level (1 point)
Chemical treatment for makeup water to increase the cooling tower cycles
(1 point)
Water meters for irrigation, indoor fixtures, cooling tower water, re-used
rainwater
Compliant (YM1A-MEP-MP-LSCH-101)
LEED Energy and Atmosphere - YM1A / LEED Năng lượng và Khí quyển
5. EA - ENERGY AND ATMOSPHERE
Building Energy Simulation - Meet the requirements of
ASHRAE90.1-2010, AppG for Building Envelop, HVAC,
Lighting, Powers, Process Load, etc
Targeting to achieve 21% energy saving (11 points):
- Laminated LowE glass (U-value 3.6 W/m2K; SHGC 0.4): kính lowE cho văn phòng
- Insulation for roof: Cách nhiệt cho mái
- Energy saving light bulbs (efficacy > 100 lm/W): Đèn tiết kiệm năng lượng
- Lighting control (timers / occupancy sensors): Điều khiển chiếu sáng
Mô phỏng năng lượng công trình đáp ứng yêu cầu tiết kiệm 21% năng lượng tiêu thụ
YP2C
13
0
YEN MY
20
13
0
6
11
0
7
1
11
0
20
ENERGY AND ATMOSPHERE
EAc1 Enhanced Com m issioning
3rd-party Enhanced Commissioning
7
EAc2 Optim ize Energy Perform ance
Meet the requirements of ASHRAE90.1-2010, AppG for Building
Envelop, HVAC, Lighting, Pow ers, Process Load, etc
Building Energy Simulation
1
EAc3 Advanced Energy Metering
2
2
EAc4 Dem and Response
3
3
EAc5 Renew able Energy Production
1
1
2
REQUIREMENTS / TASKS
6
2
+ Base building: Advanced metering for any individual energy end
uses: w ater supply pump, exterior lighting.
+ Tenant spaces: At least 1 meter per space
Participate in an existing demand response (DR) program
135 MWh/year - 840 sqm: 1 point
404 MWh/year - 2521 m2: 2 points + 1 point in EAc2
673 MWh/year - 4201 m2: 3 points + 2 points in EAc2
EAc6 Enhanced Refrigerant Managem ent
Select refrigerants that meet requirements of emission
EAc7 Green Pow er and Carbon Offsets
Engage in a contract for qualified resources of Carbon Offset
program
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
ARDOR's FEEDBACKS (11/12/2023)
PARTY
Design Consultant
21 % energy saving
Compliant (YM1A-MEP-MP-EE-101,102&103)
No need advanced meter for “solar-only”
streetlighting.
Design Consultant / ARD
Design Consultant
Design Consultant
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
Design Consultant
LEED Energy and Atmosphere - YM1A / LEED Năng lượng và Khí quyển
5. EA - ENERGY AND ATMOSPHERE
EAc3: Advanced Energy Metering (1 point)
Metering for:
+ Lesser systems: External lighting and water supply pumps: Advanced
metering (1-hour recording and remotely access): 02 meters
+ Tenant factory/warehouse: 1 meter unit: EVN meters
Đồng hồ điện cho:
+ Hệ thống chủ đầu tư lắp đặt: chiếu sáng bên ngoài / bơm: Đồng hồ nâng
cao (lấy dữ liệu 1 giờ và truy cập dữ liệu từ xa)
+ Khu vực nhà kho/nhà xưởng cho khách thuê: 1 Đồng hồ EVN / unit
YP2C
13
0
0
Advanced Meter: Water pumps
YEN MY
20
13
0
6
11
Advanced Meter: External lighting
No need advanced meter for “solar-only”
streetlighting
7
1
11
0
20
ENERGY AND ATMOSPHERE
EAc1 Enhanced Com m issioning
3rd-party Enhanced Commissioning
7
EAc2 Optim ize Energy Perform ance
Meet the requirements of ASHRAE90.1-2010, AppG for Building
Envelop, HVAC, Lighting, Pow ers, Process Load, etc
Building Energy Simulation
1
EAc3 Advanced Energy Metering
2
2
EAc4 Dem and Response
3
3
EAc5 Renew able Energy Production
1
1
2
REQUIREMENTS / TASKS
6
2
+ Base building: Advanced metering for any individual energy end
uses: w ater supply pump, exterior lighting.
+ Tenant spaces: At least 1 meter per space
Participate in an existing demand response (DR) program
135 MWh/year - 840 sqm: 1 point
404 MWh/year - 2521 m2: 2 points + 1 point in EAc2
673 MWh/year - 4201 m2: 3 points + 2 points in EAc2
EAc6 Enhanced Refrigerant Managem ent
Select refrigerants that meet requirements of emission
EAc7 Green Pow er and Carbon Offsets
Engage in a contract for qualified resources of Carbon Offset
program
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
ARDOR's FEEDBACKS (11/12/2023)
PARTY
Design Consultant
21 % energy saving
Compliant (YM1A-MEP-MP-EE-101,102&103)
No need advanced meter for “solar-only”
streetlighting.
Design Consultant / ARD
Design Consultant
Design Consultant
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET
Design Consultant
LEED Energy and Atmosphere - YM1A / LEED Năng lượng và Khí quyển
5. EA - ENERGY AND ATMOSPHERE
EAc6: Enhanced Refrigerant Management (1 point)
Select refrigerants that meet requirements of emission
(R-410a or R-32 has been used)
Sử dụng môi chất lạnh R-410a hoặc R-32
YP2C
13
0
YEN MY
20
13
0
6
11
0
7
1
11
0
20
ENERGY AND ATMOSPHERE
EAc1 Enhanced Com m issioning
3rd-party Enhanced Commissioning
7
EAc2 Optim ize Energy Perform ance
Meet the requirements of ASHRAE90.1-2010, AppG for Building
Envelop, HVAC, Lighting, Pow ers, Process Load, etc
Building Energy Simulation
1
EAc3 Advanced Energy Metering
2
2
EAc4 Dem and Response
3
3
EAc5 Renew able Energy Production
1
1
2
REQUIREMENTS / TASKS
6
2
+ Base building: Advanced metering for any individual energy end
uses: w ater supply pump, exterior lighting.
+ Tenant spaces: At least 1 meter per space
Participate in an existing demand response (DR) program
135 MWh/year - 840 sqm: 1 point
404 MWh/year - 2521 m2: 2 points + 1 point in EAc2
673 MWh/year - 4201 m2: 3 points + 2 points in EAc2
EAc6 Enhanced Refrigerant Managem ent
Select refrigerants that meet requirements of emission
EAc7 Green Pow er and Carbon Offsets
Engage in a contract for qualified resources of Carbon Offset
program
ARDOR GREEN, LEED CORE & SHELL - TITAN HUNG YEN PHASE 1, 12/2023
ARDOR's FEEDBACKS (11/12/2023)
PARTY
Design Consultant
21 % energy saving
Compliant (YM1A-MEP-MP-EE-101,102&103)
No need advanced meter for “solar-only”
streetlighting.
Design Consultant / ARD
Design Consultant
Design Consultant
Compliant
MEP: 05-YM1A-MEP-TECHNICAL SHEET