Tải bản đầy đủ (.pdf) (96 trang)

TỔNG HỢP CÁC BÁO CÁO KHOA HỌC VỀ BẢO VỆ VÀ TỰ ĐỘNG HÓA TRONG HỆ THỐNG ĐIỆN CỦA BỘ MÔN HỆ THỐNG ĐIỆN (ĐẠI HỌC BÁCH KHOA HÀ NỘI)

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (5.73 MB, 96 trang )

ĐẠI HỌC BÁCH KHOA HÀ NỘI
BỘ MÔN HỆ THỐNG ĐIỆN
eBook for You

PHҪNIII


BҦO Vӊ VÀ TӴ ĈӜNG HÓA
TRONG Hӊ THӔNG ĈIӊN




Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
201
eBook for You
Paper
An Improved Control Strategy for Hybrid Series Active Filter
dealing with Unbalanced Load
Nguyen Xuan Tung

Non-member
Goro Fujita

Member
Kazuhiro Horikoshi
∗∗
Member
This paper presents an improved control strategy for hybrid series active power filter (HSAF) working
with nonlinear and unbalance three-phase three-wire loads. An algorithm based on the Instantaneous Power


Theory is introduced to precisely extract only harmonic component from supply current, even this current is
contaminated with negative sequence component due to the imbalance of load. An improved control strategy
based on that sequence extraction algorithm is proposed and investigated in detail by numerical simulation.
The proposed control method has shown a better performance in mitigating harmonics, especially for the
nonlinear and unbalanced loads.
Keywords: Series active filter, Instantaneous power theory, Unbalanced load, Harmonic isolation.
1. Introduction
The increasing use of power electronics-based loads
(adjustable speed drives, switch mode power supplies,
etc.) is responsible for the rise in harmonic distortion
levels. These nonlinear loads appear to be prime sources
of harmonic distortion in a power distribution system.
Harmonics have a number of undesirable effects on the
distribution system such as the excessive voltage distor-
tion, increasing resistive losses or voltage stresses. In
addition, the harmonic currents can interact adversely
with a wide range of power system equipment such as
capacitors, transformers, and motors, causing additional
losses, overheating, and overloading. Because of the ad-
verse effects that harmonics have on equipments, many
solutions have been developed to deal with harmonic
control
(1)∼(3)
.
Besides conventional solutions such as passive filters,
the hybrid series active power filters have proven to be
an interesting alternative to compensate harmonics in
power distribution systems. Compared to passive fil-
ters, active filters provide superior filtering performance,
more flexible operation and more compact. There are

various series hybrid active power filter topologies re-
ported in literature
(4)∼(6)
, but the most common one is
shown in Fig. 1
Figure 1 shows the system configuration of series hy-
brid active power filter (APF), in which the shunt pas-
sive filter consists of one or more single-tuned LC fil-
ters and/or a high pass filter (HPF). The hybrid se-
ries APF is controlled to act as a harmonic isolator be-
tween the source and nonlinear load by injection of a

Shibaura Institute of Technology
3-7-5, Toyosu, Koto-ku, Tokyo 135-8548
∗∗
Tohoku Electric Power Co.,Inc.
7-2-1, Nakayama, Aoba-ku, Sendai, Miyagi 981-0952
Fig. 1. Typical system configuration of hybrid se-
ries active power filter
controlled harmonic voltage source. It is controlled to
offer zero impedance at the fundamental frequency and
high impedance (ideally open circuit) at all undesired
harmonic frequencies. This forces all harmonic load cur-
rents to flow into the passive filter and decoupling the
source and nonlinear load at all frequencies, except at
the fundamental.
Control algorithm of the series active power filter
is mostly based on the Instantaneous Power Theory
(7)∼(10)
or the Synchronous Reference Frame (so-called

dq transform)
(11)∼(15)
. Basically, all those existing con-
trol schemes calculate the harmonic current reference
signal based on the separation of fundamental positive
sequence component and other “harmonic” components.
In detail, the harmonic contents (i
h
) are determined by
excluding the fundamental component from measured
supply current as presented in Eq. 1:
[i
h
]=[i
s
] −[i
fp
] ····························(1)
here
•i
s
: measured supply current.
•i
fp
: fundamental positive sequence component of
corresponding supply current.
The high impedance imposed by the series active power
filter is achieved by generating an appropriate voltage of
IEEJ Trans. TEEE, Vol.125, No.1, 2005 1
Tổng hợp các bài báo khoa học giai đoạn 2007-2012

Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
202
eBook for You
the same frequency with that of the harmonic current
component as shown below:
[v
F
]=K ×[i
h
] ····························· (2)
with K is the amplification factor.
The performance of the active power filter depends
mainly on the selected reference generation scheme. The
reference current must reflex the desired compensation
current, however, since the Eq. 1 is used, certainly the
“harmonic” component here comprises all other current
components those differ from fundamental positive se-
quence current. Therefore this extraction method gives
the true harmonic component if the load is assumed to
be perfectly balanced.
In a quite common situation, the load current is usually
unbalanced with the existence of fundamental negative
sequence current. Consequently, that negative sequence
current will present in the extracted harmonic compo-
nent i
h
if Eq. 1 is still utilized although it is not a real
“harmonic” component. In this case, the series active
filter would have to handle not only the real harmonic
current but also the undesirable fundamental negative

sequence current. As a result, the controller would force
the series active filter to generate the compensating volt-
age at fundamental frequency and this could increase
significantly the power rating of the PWM converter and
also induce high voltage oscillations at double the sys-
tem frequency in dc link
(16)
.
Literature on series active filter shows that so far no
attempt has been made to deal with unbalanced load
and that is a disadvantageous point of the existing con-
trol strategies. In this paper, an improved control strat-
egy based on Instantaneous Power Theory is proposed
which will ensure that the series active power filter work
with only the harmonic components even the load is un-
balanced.
This paper firstly introduces the Instantaneous Power
Theory, and then discusses the basic principle and
scheme used to extract positive and negative sequence
components. Next, control strategy is presented in de-
tails. Finally, the numerical simulations are carried out
to validate the feasibility and effectiveness of this pro-
posal.
2.
Instantaneous power theory and its ap-
plication
2.1 Brief review of Instantaneous Power The-
ory The Instantaneous Power Theory
(16)
is well uti-

lized for control system of active filter. Control strategy
based on this method provides fast response to changes
in power system, good compensating performance and
imposes a little computational burden
(17) (18)
.
Figure 2 shows the calculation block of this theory:
Firstly, three-phase voltages and load currents are trans-
formed into the stationary α-β reference frame (Clarke
transformation):

v
α
v
β

=

2
3
×

1 −1/2 −1/2
0

3

2 −

3


2

×


v
a
v
b
v
c


(3)
Fig. 2. Calculation block of Instantaneous Power
Theory

i
α
i
β

=

2
3
×

1 −1/2 −1/2

0

3

2 −

3

2

×


i
a
i
b
i
c


(4)
Next, the instantaneous real power p and instantaneous
reactive power q are calculated by:

p
q

=


v
α
v
β
−v
β
v
α

×

i
α
i
β

·············(5)
According to Instantaneous Power Theory, p and q can
be decomposed into average parts ¯p,¯q (dc parts) and
oscillating parts ˜p,˜q asshowninEq.6:

p =¯p +˜p
q =¯q +˜q
····························(6)
Where the ¯p,¯q are the dc components corresponding to
the product of fundamental positive sequence quantities,
and ˜p,˜q are the ac components corresponding to prod-
uct of other components those differ from fundamental
positive sequence components.
By using a high-pass filter, the oscillating components

˜p,˜q can be extracted from p, q and then the reference
harmonic current can be obtained as follow:

i

i


=
1
v
2
α
+ v
2
β
×

v
α
v
β
v
β
−v
α

×

˜p

˜q

· (7)
Next, those reference currents go through an inverse α-β
transform to generate the reference current in conven-
tional three-phase abc frame.
2.2 Consideration in case voltage and current
are distorted and unbalanced If voltage and cur-
rent are distorted (due to the presence of high order
frequency harmonic components) and unbalanced (with
the existence of the fundamental negative sequence com-
ponent) then the resulted oscillating power components
˜p,˜q will be the cross products of not only the harmonic
components but also the fundamental negative sequence
components
(16)
. In other words, the oscillating power
components ˜p,˜q contain the fundamental negative se-
quence components.
Consequently, if the reference current signals are gener-
ated based on those power components then they would
contain both negative sequence and harmonic compo-
nents rather than only harmonic components as ex-
pected. This fact raises a need to develop a method
which can precisely extract only harmonic currents de-
spite of the presence of the fundamental negative se-
quence component.
2 IEEJ Trans. TEEE, Vol.125, No.1, 2005
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội

203
eBook for You
An Improved Control Strategy for Hybrid Series Active Filter dealing with Unbalanced Load
3. Approach for determining reference
current
3.1 Problem formulation and proposal All
the existing control strategies for the series active power
filter determine the reference currents i
h
by simply sub-
tracting the fundamental positive sequence current from
the supply current as below:
[i
h
]=[i
s
] −[i
fp
] ····························(8)
This approach has shown many disadvantages as already
mentioned in Sec. 1 since the reference current i
h
will
contain the fundamental negative sequence current com-
ponent if load is unbalanced. In order to overcome
this drawback, the improved reference current extrac-
tion method is proposed as follow:
[i
h
]=[i

s
] −[i
fp
] −[i
fn
] ·····················(9)
where i
s
,i
fp
,i
fn
are the measured supply current, fun-
damental positive and negative sequence current com-
ponents of corresponding supply current respectively.
The improved reference current extraction method dif-
fers from previous proposals since it eliminates not only
the fundamental positive sequence current but also the
fundamental negative sequence current from the supply
current to form the harmonic reference current.
Because i
s
is already measured, the remaining task of
determining the harmonic reference current based on
new proposal is to extract the positive and negative se-
quence components (two last components at right side
of Eq. 9). In this paper, the sequence current compo-
nent extraction implementation is completely based on
the Instantaneous Power Theory. Basically, it includes
following steps:

•Generate an auxiliary voltage which contains only
a pure fundamental positive or negative sequence
voltage.
•This auxiliary voltage will be used together with ori-
gin supply current to create the instantaneous power
components.
•Implement filtering processes to achieve the desired
power portions from those power components then
applying inverse transformation to generate the cor-
responding current.
The role of the auxiliary voltage will be fully described
in next section.
3.2 Positive sequence current extraction Con-
sidering an auxiliary voltage that contains only funda-
mental positive sequence component
V
+1
with phase an-
gle φ
+1
assumed to be zero then the α-β transform of
this voltage results in:

v
+1α
=

3V
+1
sin (ω

1
t)
v
+1β
= −

3V
+1
cos (ω
1
t)
···········(10)
Next step, this pure fundamental positive sequence volt-
age is used together with the supply current to calculate
the instantaneous power quantities p, q following Eq. 5.
The supply current may contain fundamental negative
sequence and high order harmonic components, however,
the resulted dc components ¯p

, ¯q

of those power quanti-
ties in this case are the cross product of only fundamen-
tal positive components as shown below:

¯p

=3V
+1
I

+1
cos (−δ
+1
)
¯q

=3V
+1
I
+1
sin (−δ
+1
)
············(11)
here
•I
+1
: the fundamental positive sequence current
component of the measured supply current.
•δ
+1
: phase angle between the auxiliary positive se-
quence voltage V
+1
and the fundamental positive
sequence current component I
+1
.
It is clear to see that only fundamental positive sequence
voltage V

+1
and current I
+1
components contribute to
average value ¯p

and ¯q

, the negative sequence compo-
nents does not appear in those power quantities. Next,
the low-pass filter is utilized to extract only those dc
power components ¯p

, ¯q

. Once those power components
in Eq. 11 is extracted then it is easy to obtain the posi-
tive sequence current using the same definition as shown
in Eq. 7.
For extracting fundamental positive sequence compo-
nent, the amplitude of v
+1α
and v
+1β
are not important
and can be chosen arbitrarily due to the fact that they
appear in both “direct” and “inverse”calculations
(16)
.
For simplicity, they are set to unity hence Eq. 10 be-

comes:

v
+1α
=+sin(ω
1
t)
v
+1β
= −cos (ω
1
t)
··················(12)
3.3 Negative sequence current extraction
Similar procedure is employed to extract negative se-
quence current, however, an auxiliary negative sequence
voltage is considered instead of the auxiliary positive se-
quence voltage.
Theresultsofα-β transform of this auxiliary pure fun-
damental negative sequence voltage is shown in Eq. 13.

v
−1α
=+sin(ω
1
t)
v
−1β
=+cos(ω
1

t)
··················(13)
Here the amplitude of negative sequence voltage v
−1α
and v
−1β
are again selected to be unity and correspond-
ing phase angles are assumed to be zero for simplifica-
tion.
The dc power components ¯p

, ¯q

resulted from the
product of those auxiliary negative sequence voltages
{v
−1α
,v
−1β
} and the supply current are shown in Eq. 14

¯p

=3V
−1
I
−1
cos (−δ
−1
)

¯q

=3V
−1
I
−1
sin (−δ
−1
)
············(14)
here
•I
−1
: the fundamental negative sequence current
component of the measured supply current.
•δ
−1
: phase angle between the auxiliary negative se-
quence voltage V
−1
and the fundamental negative
sequence current component I

1
.
Again, only fundamental negative sequence voltage V
−1
and current I
−1
components show up in the average

value ¯p

,¯q

even the supply current is distorted and un-
balanced. Therefore, if those dc power components are
IEEJ Trans. TEEE, Vol.125, No.1, 2005 3
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
204
eBook for You
Fig. 3. Positive sequence current detection circuit
extracted through a filtering process then the negative
sequence current can be calculated using same definition
as shown in Eq. 7.
3.4 Generation of auxiliary voltages and se-
quence detection circuit The generation of the
fundamental positive and negative sequence components
is necessary for determining the harmonic reference cur-
rent. An important part of generating auxiliary ref-
erence voltage is the phase locked loop (PLL) circuit.
The PLL circuit tracks continuously the fundamental
frequency ω
1
of the measured system voltage.
The PLL is designed to operate properly under distorted
and unbalanced voltage wave forms. The frequency ω
1
is used in a sine wave generator to produce two quan-
tities sin(ω

1
t)and−cos(ω
1
t) those correspond to the
auxiliary fundamental positive sequence voltages v
+1α
& v
+1β
(mentioned in Eq. 12). The PLL circuit is al-
ready well introduced in literature and it has good per-
formance in handling this task
(19) (20)
(see Appendix for
operation principle).
Figure 3 shows the positive sequence detection circuit
based on principle stated in Sec. 3.2. Similar circuit can
be implemented for the negative sequence extraction if
the output of PLL circuit are −sin(ω
1
t) and cos(ω
1
t)
following the Eq. 13.
4.
Control strategy
4.1 Operation principle of series active filter
as harmonic current isolator It is well known
that series active filters correct current system distor-
tion caused by non-linear load by synthesizing an active
impedance presenting a zero impedance at fundamen-

tal frequency and a high resistance K between load and
source at all harmonics frequencies. By inserting a high
resistance K, the series active filter forces the high fre-
quency current flow mainly through LC passive filter
connected in parallel to load
(2) (21)
.
The equivalent single phase circuit for harmonic com-
pensation is shown in Fig. 4. In this figure, non-linear
load is represented by a harmonic current source I
h
and
source voltage is represented by harmonic voltage source
V
sh
. The series active filter is equivalent to a controlled
voltage source V
c
and shunt passive filter becomes an
equivalent impedance Z
F
. If the series active filter is
controlled as V
c
= K ×I
sh
(equivalent to a resistor of K
ohm) then the I
sh
can be calculated as:

I
sh
=
V
sh
Z
S
+ Z
F
+ K
+
Z
F
Z
S
+ Z
F
+ K
× I
h
··(15)
Fig. 4. Equivalent circuit for harmonic compensation
Fig. 5. Proposed control circuit for series active
filter
If the gain factor K is set sufficiently large as
K  (Z
S
+ Z
F
) then neither harmonic current flow

from load to ac source nor from ac source to load side.
4.2 Control Scheme The proposed control cir-
cuit is shown in Fig. 5, where the three-phase load cur-
rent is measured and transformed into stationary α-β
frame. The PLL circuit generates the auxiliary posi-
tive and negative sequence voltages (corresponding to
Eq. 12 & 13). Those currents and auxiliary voltages in
stationary α-β frame are supplied to positive and neg-
ative sequence extraction blocks (extraction principle is
detailed in Sec. 3.2 & 3.3). The output positive and neg-
ative sequence currents in α-β frame are passed through
the inverse α-β transform to give the positive and neg-
ative sequence currents in conventional three-phase abc
frame.
Harmonic current is extracted from measured supply
current after subtracting the fundamental positive and
negative sequence components as stated in Eq. 9. Next,
each extracted harmonic current is passed through a
gain block with the amplification factor of K to form
reference voltage v
F
(Eq. 2). Finally, this reference
voltage v
F
is applied to the gate control circuit for each
PWM converter.
5.
Simulation setup
Simulation is setup as following:
•The investigated system is three-phase, three-wire

system then zero sequence component does not ex-
ist.
•Source’s line to line voltage is 200V (50Hz). Source
impedance is Z
s
=0.02∠80 pu (with the system
base of U
base
= 200V and S
base
=20kV A).
•Active filter rating capacity is 700VA and it is ac-
tivated at 0.5 [s] during simulation.
•PWM converter’s switching frequency is set at
4 IEEJ Trans. TEEE, Vol.125, No.1, 2005
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
205
eBook for You
An Improved Control Strategy for Hybrid Series Active Filter dealing with Unbalanced Load
Fig. 6. Representative diagram for simulation
Table 1. Parameter of shunt passive filter
Inductance [mH] Capacitance [μF]
5
th
filter 1.2 340 Q=14
7
th
filter 1.2 170 Q=14
High-pass 0.26 300 R=3Ω

15 kHz. The dc source’s voltage is V
dc
= 200V .
•Coupling transformer’s turn ratio n = 1 : 20. The
ripple filter connected at the output of PWM con-
verter consists of a series inductor L
r
=1mH and
a shunt capacitor C
r
=0.33μF .
•Passive filters are tuned to the most dominant 5
th
,
7
th
harmonics and a high pass filter with total ca-
pacity of 10kVA (parameters are given in Table 1).
•The unbalanced and nonlinear load is represented
by a combination of a 20 kVA three-phase thyristor
rectifier and a linear single phase load (17.5Ω) as
shown in Fig. 6. This setup gives a total load cur-
rent of about 60 [A] RMS with the unbalance factor
I
2
/I
1
∼ 10%.
•Current is measured in ampere [A].
6.

Result and discussion
6.1 Effectiveness of series active filter equipped
with improved control algorithm Figure 7 gen-
erally shows the effect of active power filter equipped
with improved control strategy on the nonlinear and un-
balanced load. For detail:
•Figure 7a shows that: Once active filter is acti-
vated at 0.5 [s] then it almost immediately takes ef-
fect to reduce the harmonic contents injecting into
the source, the source current almost becomes si-
nusoidal. Moreover, the active filter not only suc-
cessfully mitigates the harmonic contents but also
preserves perfectly the imbalance characteristic of
load as expected.
•Figure 7b & 7c present the spectra of source current
before and after active filter is activated. Evidently,
the harmonic contents significantly drops at all har-
monic frequencies. Thus, this is again to numer-
ically confirm the effectiveness of the series active
filter.
The fundamental positive and negative sequence cur-
rents extracted from measured source current are also
shown in Fig. 8 & Fig. 9. Noticeably, the positive and
negative sequence current remain constant, even while
active filter is operating. These results confirm the ad-
vantage of improved control strategy: the active filter
does not alter the load imbalance characteristic. In other
words, the active filter does work with only harmonic
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560
-150

-100
-50
0
50
100
150
Isa Isb Isc
(a) Harmonic mitigation effect with improved control strategy for
unbalanced load
Current S
p
ectrum
5.0
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2
2
23 24 25 26 27 28 29 30 31
(b) Current spectra: Before activation of active filter
Current S
p
ectrum
5.0
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2
2
23 24 25 26 27 28 29 30 31
(c) Current spectra: After activation of active filter
Fig. 7. Waveshapes and sp ectra of source current
before and after active filter is activated
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560

-150
-100
-50
0
50
100
150
Iap Ibp Icp
Fig. 8. Extracted positive sequence current
0.460 0.480 0.500 0.520 0.540 0.560
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
Ian Ibn Icn
Fig. 9. Extracted negative sequence current
current components as designed.
For nonlinear and balanced load, the active filter
equipped with new control strategy still works very well
as it can be seen in Fig. 10, the harmonic contents are
mostly eliminated and the inherent load characteristic
remains untouched.
6.2 Effectiveness comparison over series active
filters equipped with improved and previous con-
IEEJ Trans. TEEE, Vol.125, No.1, 2005 5
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội

206
eBook for You
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560
-150
-100
-50
0
50
100
150
Isa Isb Isc
Fig. 10. Harmonic mitigation with improved con-
trol strategy for balanced load
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560
-150
-100
-50
0
50
100
150
Isa Isb Isc
(a) Result with improved control strategy
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560
-150
-100
-50
0
50
100

150
Isa Isb Isc
(b) Result with previous control strategy
Fig. 11. Waveshape comparison in cases with im-
proved and previous control strategies
trol algorithms For comparison purpose, the active
filter which is equipped with the previous control strat-
egy is also simulated. Simulation studies for comparison
are setup based on follow assumptions:
•In previous control strategy, the negative sequence
component is not excluded from the reference har-
monic current.
•On the contrary, for the improved control strategy,
the negative sequence component is excluded from
the reference harmonic current.
•Comparisons are carried out with unbalanced loads
since the improved control strategy is proposed to
help the series active filter performs better under
unbalanced loading conditions.
•All other conditions remains the same for both
cases.
Figure 11 & 12 compare the current waveshapes and
spectra in cases the active filters utilize the improved
and previous control strategies. Under the same test-
ing conditions, the active filter with improved control
strategy shows a better performance. This conclusion
can be clarified in below discussion:
•The active filter equipped with previous control
strategy will have to handle both harmonic and the
fundamental negative sequence current components,

consequently the load will be forced to be balanced
as shown in Fig. 11b and the PWM converter might
be easily overloaded. Besides exposing the active
Current S
p
ectrum
5.0
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2
2
23 24 25 26 27 28 29 30 31
(a) With improved control strategy
Current S
p
ectrum
5.0
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2
2
23 24 25 26 27 28 29 30 31
(b) With previous control strategy
Fig. 12. Current spectrum comparison in cases
with improved and previous control strategies
filter to overload condition, degrading the harmonic
mitigation effect, that balancing the inherent unbal-
anced load does not bring any benefit for customer
who invested money for that active filter.
•In contrast, the active filter employing the improved
control method does not need to handle the negative
sequence current then it can devote all of it capacity

for harmonic mitigation function. As a result, the
harmonic mitigation efficiency in this case is higher.
This higher efficiency is illustrated in Fig.12a as the
harmonic contents shown there are much more lower
than those in Fig.12b. In other words, the active fil-
ter with the improve control algorithm has a better
performance.
Figure 13 shows the compensating voltages generated
by the series active filters (the blue and red lines show
instantaneous and RMS values respectively), those fig-
ures are for the output volt-ampere comparison purpose.
Figure 13b presents the output voltage of series active
filter which is equipped with previous control algorithm.
Apparently, looking at voltage waveform, one may see
the presence of the 50Hz component. That is reason
why the output voltage in RMS value is almost double
of that in Fig. 13a. This phenomenon is due to all the
previous control algorithms do not exclude the negative
sequence component which may occur if load is unbal-
anced.
For numerical detail comparison:
•In case the active filter employs improved control al-
gorithm, the compensating voltage presents a RMS
value of only about 3.4V . This means that the
volt-ampere rating of the series active filter is only
3.4V ×60A×3 = 612VA. Assuming that the active
filter rating capacity is chosen as 700VA, then this
figure presents only a small portion as about 3.5%
of the load rating 20kV A.
•On the contrary, if the previous control algorithm

is utilized, then the output compensating voltage in
6 IEEJ Trans. TEEE, Vol.125, No.1, 2005
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
207
eBook for You
An Improved Control Strategy for Hybrid Series Active Filter dealing with Unbalanced Load
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560
-20.0
-16.0
-12.0
-8.0
-4.0
0.0
4.0
8.0
12.0
16.0
20.0
V_active_filter VfilterRMS
(a) With improved control strategy
0.460 0.470 0.480 0.490 0.500 0.510 0.520 0.530 0.540 0.550 0.560
-20.0
-16.0
-12.0
-8.0
-4.0
0.0
4.0
8.0

12.0
16.0
20.0
V_active_filter VfilterRMS
(b) With previous control strategy
Fig. 13. Voltage generated by series active filters
Zs = 0.02
p
u
THDv (%)
1.06281
02
(a) Z
s
=0.02pu
Zs = 0.1
p
u
THDv (%)
2.01309
02
(b) Z
s
=0.1pu
Zs = 0.2
p
u
THDv (%)
2.30476
02

(c) Z
s
=0.2pu
Fig. 14. Total harmonic distortion (THD) of
source voltages
this case is about 8V as shown in Fig. 13b. Numer-
ically, the required volt-ampere output of the active
filter now is up to 8V ×60A ×3 = 1440VA.Inthis
case, the active filter is about 1440VA/700VA =
2.05 times overloaded. As a result, this will seriously
damage the converter. Apparently, the percentage
of overload depends on the load unbalance factor.
6.3 Influence of source side impedance on har-
monic mitigation effect From Fig. 4, it is easy to
see that the harmonics generated by nonlinear load are
injecting into source. As consequence, the source volt-
age will be distorted depending on the value of source
impedance. If the source impedance is low, then the
voltage distortion is low and vice versa. Since this con-
trol algorithm utilizes the quantities calculated from
both voltage and current, then it is necessary to examine
the influence of voltage distortion (or source impedance)
on the compensation effect.
All above simulations run with source impedance set at
0.02pu, then now two more worse scenarios are exam-
ined: source impedances are set higher at 0.1pu and
0.2pu. Consequently, the results in Fig. 14 show that
total harmonic distortion (THD) factors of source volt-
ages are 1.06%, 2.01% and 2.3% respectively. Thus, the
higher the source impedance, the worse the voltage dis-

tortion.
Figure 15 show the corresponding THDs of source cur-
rents after compensation. Noticeably, after series active
filter was started, the remain amounts of harmonic con-
Zs = 0.02
p
u
THDi (%)
0.869893
02
(a) Z
s
=0.02pu
Zs = 0.1
p
u
THDi (%)
0.631617
02
(b) Z
s
=0.1pu
Zs = 0.2
p
u
THDi (%)
0.497768
02
(c) Z
s

=0.2pu
Fig. 15. Total harmonic distortion (THD) of
source currents
tents tend to go down for three cases. This fact may be
discussed as below:
•Since the source impedance are set increasingly from
0.01pu to 0.2pu , the source becomes weaker and its
voltage actually get distorted. However, on the con-
trary, the higher the source impedance, the smaller
amount of harmonic currents injected into source.
That is reason why the harmonic contents after com-
pensation is reduced correspondingly for three cases.
•Despite the distortion of voltage, the series active fil-
ter still work effectively. This point proves that the
Instantaneous Power Theory used in the sequence
extraction algorithm can work well under the volt-
age distortion conditions.
7.
Conclusions
The improved control strategy for hybrid series active
filter is already proposed and investigated in detail. This
control method bases on sequence component elimina-
tion algorithm to obtain only the harmonic content from
a distorted and unbalanced current set. Consequently,
this control strategy does help the series active filter to
improve its performance, especially when load is unbal-
anced. Main conclusions can be recognized as follow:
•Only harmonic component is precisely extracted to
form the reference current for the series active filter,
therefore, the active filter work with only harmonic

component as expected, even when load is unbal-
anced.
•The proposed control strategy enhances the stabil-
ity of control process since the imbalance of load will
not have any affect on the reference signal.
•Especially, the active filter is protected away from
severer overload conditions because it does not have
to deal with the fundamental negative sequence
component which may occur if load is unbalanced.
•The proposed control strategy is well tailored to suit
with all operating conditions such as serving bal-
anced or unbalanced loads. In other words, it can
apply for the series active filter working with any
generic loads.
Finally, all the simulation results have successfully vali-
dated the effectiveness and feasibility of this proposal.
References
( 1 ) Z. Salam, and T. P. Cheng, and A. Jusoh, “Harmonics Miti-
gation Using Active Power Filter: A Technological Review”,
IEEJ Trans. TEEE, Vol.125, No.1, 2005 7
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
208
eBook for You
Elektrika Journal of Electrical Engineering, (2006)
( 2 ) F. Z. Peng, and H. Akagi, and A. Nabae, “A New Approach to
Harmonic Compensation in Power Systems”, IEEE Industry
Applications Society Annual Meeting, (1988)
( 3 ) M. El. Habrouk, and M. K. Darwish, and P. Mehta, “Active
Power Filters: A Review”, IEE Proceedings Electric Power

Applications, (2000)
( 4 ) F. Z. Peng, and H. Akagi, and A. Nabae, “Compensation
Characteristics of The Combined System of Shunt Passive and
Series Active Filters”, IEEE Transactions on Industry Ap-
plications, (1993)
( 5 ) F. B. Libano, and D. S. L. Simonetti, and J. Uceda, “Fre-
quency Characteristics of Hybrid Filter Systems”, Power
Electronics Specialists Conference, (1996)
( 6 ) J. Turunen, and M. Salo, and H. Tuusa, “Comparison of Three
Series Hybrid Active Power Filter Topologies”, International
Conference on Harmonics and Quality of Power, (2004)
( 7 ) B. Han, and B. Bae, and H. Kim, and S. Baek, “Combined
Operation of Unified Power Quality Conditioner With Dis-
tributed Generation”, IEEE Transactions on Power Deliv-
ery, (2006)
( 8 ) S. P. Litran, and P. Salmeron, and R. S. Herrera, and J. R.
Vazquez, “New Control Strategy to Improve Power Quality
Using A Hybrid Power Filter”, International Conference on
Renewable Energies and Power Quality, (2008)
( 9 ) H. Akagi, and Y. Kanazawa, and A. Nabae, “Instantaneous
Reactive Power Compensators Comprising Switching Devices
without Energy Storage Components”, IEEE Transactions
on Industry Applications, (1984)
(10) Q. Wang, and W. Yao, and J. Liu, and Z. Wang, “Voltage
Type Harmonic Source and Series Active Power Filter Adopt-
ing New Control Approach”, Industrial Electronics Society
Conference IECON, (1999)
(11) S. Bhattacharya, and D. Divan, “Synchronous Frame Based
Controller Implementation for A Hybrid Series Active Filter
System”, Industry Applications Conference, (1995)

(12) G. D. Marques, and V. F. Pires, and M. Malinowski, and M.
Kazmierkowski, “An Improved Synchronous Reference Frame
Method for Active Filters”, The International Conference on
Computer as a Tool, (2007)
(13) S. Bhattacharya, and D. Divan, “Design and Implementation
of A Hybrid Series Active Filter System”, Power Electronics
Specialists Conference, (1995)
(14) K. Karthik, and J. E. Quaicoe, “Voltage Compensation and
Harmonic Suppression Using Series Active And Shunt Passive
Filters”, Canadian Conference on Electrical and Computer
Engineering, (2000)
(15) B. R. Lin, and B. R. Yang, and T. L. Hung, “Implementa-
tion of A Hybrid Series Active Filter for Harmonic Current
and Voltage Compensations”, International Conference on
Power Electronics, Machines and Drives, (2002)
(16) H. Akagi, and E. H. Watanabe, and M. Aredes: Instantaneous
Power Theory and Applications to Power Conditioning, John
Wiley & Sons, Inc. (2007)
(17) D. Chen, and S. Xie, “Review of The Control Strategies
Applied to Active Power Filters”, IEEE International Con-
ference on Electric Utility Deregulation, Restructuring and
Power Technologies, (2004)
(18) G. W. .Chang, and T. C. Shee, “A Comparative Study of
Active Power Filter Reference Compensation Approaches”,
Power Engineering Society Summer Meeting, (2002)
(19) S. A. O. Silvia, and P. F. Donoso-Garcia, and P. F. Seixas,
“A Three Phase Line Interactive UPS System Implementation
with Series-Parallel Active Power Line Conditioning Capaci-
ties”, IEEE Transactions on Industry Applications, (2002)
(20) F. F. Ewald, and M. A. S. Masoum: Power Quality in Power

Systems and Electrical Machines, Academic Press (2008)
(21) L. Xu, and E. Acha, and V. G. Agelidis, “A New Synchronous
Frame-Based Control Strategy for A Series Voltage and Har-
monic Compensator”, Applied Power Electronics Conference
and Exposition, (2001)
Appendix
Phase locked loop (PLL) circuit
The PLL is one of components of the sequence cur-
rent detection circuit. It detects fundamental angular
frequency (ω
1
) and generates synchronous sinusoidal sig-
nals those correspond to auxiliary positive sequence volt-
ages under sinusoidal as well as highly distorted and un-
balanced source voltages. The PLL circuit introduced
app. Fig. 1. Phase locked loop circuit
here is based on the instantaneous active power expres-
sion:
p


= v
a
i

a
+ v
b
i


b
+ v
c
i

c
= v
ab
i

a
+ v
cb
i

c
=¯p


+˜p


(A1)
The current feedback signals i
a
(ωt)=sin(ωt)and
i
c
(ωt)=sin(ωt + 120
0

) are generated by sine genera-
tor circuits through the time integral of the output ω
of the PI controller. The PLL can reach stable point
of operation only if the input p


of PI controller has,
in steady state, a zero average value, that is, ¯p


=0.
Moreover, the low frequency oscillations ˜p


should be
minimized.
Because i
a
(ωt)andi
c
(ωt) contain only positive-sequence
components and have unity magnitudes, therefore, the
average three phase power p


=¯p


is given by:
¯p



=3V
+1
I

+1
cos(φ
+
+ δ
+
) ··············· (A2)
where φ
+
and δ
+
are the initial phase angles of the fun-
damental positive sequence voltage and current i
a
(ωt)
respectively. Now the PLL can reach stable point of op-
eration only if the input p


of PI controller has a zero
average value, that is equivalent to:
¯p


=3V

+1
I

+1
cos(φ
+
+ δ
+
)=0··········· (A3)
The above condition is satisfied since φ
+
+ δ
+
=90
0
.
This means that the auxiliary currents i
a
(ωt)andi
c
(ωt)
become orthogonal to the fundamental positive sequence
component V
+1
of the measured voltages v
a
and v
c
re-
spectively. Therefore, the generated auxiliary voltage

v
+1a
= sin(ωt −90
0
) is in phase with fundamental pos-
itive sequence voltage V
+1
. Similar relations hold for
v
+1b
and v
+1c
.
Nguyen Xuan Tung (Non-member) received the B.E. de-
gree in electrical engineering from Hanoi Uni-
versity of Technology, VietNam in 1999 and
the M.E degree from Curtin University of
Technology, Australia in 2005. He has been
pursuing PhD degree in Shibaura Institute of
Technology, Japan since 2007. His interests
are about protective relay system and power
quality issue in power distribution system.
8 IEEJ Trans. TEEE, Vol.125, No.1, 2005
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
209
eBook for You
An Improved Control Strategy for Hybrid Series Active Filter dealing with Unbalanced Load
Goro Fujita (Member) received the B.E., M.E. and Ph.D
degrees in electrical engineering from Hosei

University, Tokyo, Japan in 1992, 1994 and
1997 respectively. In 1997, he was a research
student of Tokyo Metropolitan University. He
is an Associate Professor of Shibaura Insti-
tute of Technology, Tokyo, Japan. His inter-
est is in power system control including AGC
and FACTS. He is a member of the Society of
Instrument and Control Engineers (SICE) of
Japan, the IEE of Japan, and IEEE.
Kazuhiro Horikoshi (Member) was born in Miyagi, Japan,
on August 30, 1967. He received the B.E.
degree in electrical engineering from Tohoku
University, Japan, in 1990. In the same year,
he joined Tohoku Electric Power Co., Sendai,
Japan. He is now an assistant research man-
ager in Research & Development Center at To-
hoku Electric Power Co., Inc. His research
area is about distribution system and inter-
connection of distributed generations.
IEEJ Trans. TEEE, Vol.125, No.1, 2005
9
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
210
eBook for You
Paper
Fault Current Limiting Function of Dynamic Voltage Restorer Utilizing
Signals from Existing Protective Relays
Nguyen Xuan Tung


Non-member
Fujita Goro

Member
Dynamic Voltage Restorer (DVR) is a series custom compensator utilized in power distribution network,
however, due to connected in series with distribution line then DVR would suffer from downstream faults.
To limit the flow of large fault currents and protect DVR itself as well, a fault current limiting function is
proposed in the DVR control strategy. Fault current limiting function of DVR will be activated by protection
system and then DVR will start injecting a series voltage to the line in such a way to limit fault current
to an appropriate level (in accordance with required sensitivity of protection systems). The contribution of
this proposal is the utilization of signals from existing feeder protection system to activate DVR. This will
simplify the structure of DVR because the extra build-in fault detection module is not required. Moreover,
it will ensure proper coordination between DVR and protection systems.
Keywords: Dynamic Voltage Restorer, Fault Current Limiter, Protection System.
1. Introduction
Distribution networks are usually expanded by adding
either extra transformers and/or feeders. This fact may
raise the chances of increasing prospective fault currents
that might exceed circuit breaker’s interrupting capac-
ity. Moreover, that adding dispersed power sources may
be convinced as other reason for increasing potential
fault current level. Many solutions have been proposed
to deal with high fault duty level; one of these solutions
is utilizing fault current limiting (FCL) devices. Basi-
cally, FCL can bring many benefits to utilities, such as:
• Avoid or delay upgrading existing CBs.
• Minimize voltage dip on upstream bus when fault
occurs at downstream feeder.
• A larger transformer can be used to meet demand
without upgrading CBs.

• Reduce thermal damage due to fault currents and
hence protecting and extending life time of trans-
formers and other equipments.
In this study, a dynamic voltage restorer (DVR) is
proposed as a fault current limiter. Dynamic voltage
restorer is a series custom power device used to protect
sensitive customers from impacts of all voltage distur-
bances. Dynamic voltage restorer can be implemented
at both low voltage level and medium voltage level. A
topology of typical medium voltage DVR is in Fig. 1.
The basic operation principle of DVR is simple. DVR
will insert a series voltage with appropriate magnitude,
frequency and phase to compensate for any voltage dis-
turbances (especially voltage sags) that may affect the
proper operation of loads. In order to handle that oper-

Shibaura Institute of Technology
3-7-5, Toyosu, Koto-ku, Tokyo 135-8548, Japan
Fig. 1. Typical topology of DVR
ation, DVR is equipped with a Voltage Source Inverter
(VSI) and energy storage. However, when fault occurs
at down stream location, DVR would suffer from a large
fault current and that such large current will damage the
power switching devices within the VSI. In order to pro-
tect DVR, a bypass circuit is added to DVR
(1) (2)
. The
bypass circuit does protect DVR during fault at down-
stream but it still allows the large fault current flowing
through faulty part and circuit breaker. In order to deal

with the above mentioned problems, a fault current lim-
iting function is added to DVR’s control function. When
fault occurs, the DVR reverses its injecting voltage po-
larity in such a way to pull down the current flow to an
appropriate level as desired. The advantages of added
fault current limiting function are:
• Additional protection circuits (such bypass circuit)
are not necessary for DVR.
• Implementation is simple.
• Diminish damage caused by large fault current to
circuit breaker and other equipment.
The fault current limiting function ensures that the de-
vices are protected from excessive high current without
additional circuit complexity. However, another concern
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 1
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
211
eBook for You
Fig. 2. Equivalent diagram of investigated system
Fig. 3. Relationship between fault current and
voltage drop on fault impedance
is that the fault current limiting function of DVR must
not interfere with the existing protection system of the
feeder. Since the proposed function of DVR will force
the fault current to go down during the fault, in order
to avoid the interference it should be well coordinated
with the protection system.
In next section, the implementation of fault current
limiting function with activating signal from existing

protection system is presented and the coordination with
existing protection system is investigated as well.
2.
Operation principle of DVR as fault
current limiter
DVR is known as a multi-function device in distribu-
tion system, it mainly used to against voltage sag that
may occur. To minimize the power losses through DVR
then the DVR is held in a null state in normal condi-
tion. Once an overcurrent occurs then FCL function is
activated and it starts to react as fast as possible and
inject the required ac voltage to the grid.
Figure 2 and 3 illustrate that operation principle:
When fault occurs, the relationship between voltage at
source and fault current can be expressed as (without
DVR):
U
S
= I
f
× R
f
+ jI
f
× X
f
=ΔU
R
f
+ΔU

X
f
=ΔU ················· (1)
where
U
S
: source voltage (behind source’s impedance)
Z
f
: total fault impedance (Z
f
= Z
S
+ Z
Lfault
)
I
f
: fault current
Z
S
: internal impedance of source
Z
Lfault
: impedance of faulty line section
ΔU: voltage drop on total fault impedance
If DVR is activated, it will inject a series voltage into
line in such a way to reduce amplitude of fault current.
At this time, relationship as shown in Eq. 1 has been
Fig. 4. Relationship between compensated fault

current and corresponding injected voltage
changed to Eq. 2:
U
S
+ U
DV R
= I
f(c)
× Z
f
=ΔU
(c)
··········· (2)
here U
DV R
is voltage injected by DVR.
Assuming that fault current will be compensated to ap-
propriate magnitude as represented by dotted circle in
Fig. 3. Depending on the phase angle and magnitude
of injected voltage then inherent phase angle of compen-
sated fault current can vary, for instance it can be either
I
f1(c)
or I
f2(c)
and so on.
Based on vector diagram in Fig. 4, it can be seen that
when compensated fault current (for instance I
f1(c)
)

is kept in phase with pre-compensated fault current
I
f
then the amplitude of injected voltage is minimum
(U
DV R1
<U
DV R2
; U
DV R1
<U
DV R3
), therefore,
this technique minimizes the voltage rating of coupling
transformer (mathematical expression can be found in
ref. (3)), and hence, the voltage rating of DC capacitor
is minimized as well. In this proposal, in-phase current
compensation strategy is utilized.
3.
Activation and termination principles
implemented for DVR
Technical literature is filled with documents and ref-
erences regarding that utilizing the DVR as fault cur-
rent limiter , however, the coordination between DVR
and existing protection system has not been well men-
tioned
(4) (5) (6)
. Apparently, DVR will alter fault current
since it is activated, therefore, sensitivity of protection
system will be influenced. In order to ensure proper op-

eration of existing protection system, the coordination
must therefore be considered. In this section, the above
mentioned issues will be analyzed and appropriate solu-
tion will be proposed. This section is divided into three
sub-sections: setting threshold for compensated current,
activation and termination mechanism of DVR serving
as fault current limiter.
3.1 Setting compensated current level For
setting level of compensated current, S. S. Choi et al.
(5)
,
L. Y. Wei et al.
(6)
proposed setting level based on as-
sumption that voltage at point of common coupling
would remain as that of pre-fault level while DVR is
being activated. In other word, amplitude of compen-
sated current will remain constant as pre-fault normal
load current. This approach had some drawbacks since
the fault current is very high in comparison with normal
load current and DVR will act as a buffer between source
and fault point, hence DVR will absorb energy from up-
2 IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
212
eBook for You
Fault Current Limiting Function of Dynamic Voltage Restorer Utilizing Signals from Existing Protective Relays
stream source in order to reduce fault current level. As
a result, DVR must have a high KVA rating to deal with

large fault currents. Other concern is that some type of
protection system such as an overcurrent relay system
(non-directional type) will operate based on magnitude
of sensed current, hence if the fault current is compen-
sated to pre-fault level then overcurrent relay might no
longer have enough sensitivity to continue tracing the
presence of fault and it will reset to standby status.
Based on that analysis, a new setting level will be pro-
posed to ensure that protection system still functions
properly since DVR operates.
In order to deal with new setting level, the concept of
sensitivity of protection system will be referred
(7) (8) (9)
.
Generally, the protection system must operate reliably
even with the smallest fault current which may occur in
protective zone. However, what could happen in case
the smallest fault current is just about the setting level
(or pickup level) of protection system:
• If protection system still can operate in this case
that means it already senses the faulty condition or
it is sensitive enough.
• If it can not operate, that means the protection does
not sense the faulty condition, in other word, it is
not sensitive enough.
Based on that fact, the relationship between minimum
fault current and pickup level of any protection system
should be considered. In case of overcurrent relay, the
ratio between minimum fault current and setting level
is referred as the sensitivity factor of protection system

as follow:
Sensitivity
min
=
I
fault min
I
pickup level
[pu]
Inherently, the sensitivity factor will vary depending on
fault current level, but the minimum sensitivity referring
to minimum fault current is considered when designing
the protection system. As a rule of thumb, sensitivity to
minimum fault condition for a protection system should
not be less than 2 per unit (pu) in order to ensure the
reliable operation of protection system in any faulty con-
ditions.
From that point of view, setting level for compensated
current should be kept at 2 times of pick up current
(2 × I
pickup
) of existing relay system (pick up current
of existing relay system is already known when design-
ing protection system). This setting level proposes some
advantages:
• Voltage rating of DC link capacitor is lower than
that in case of full compensation.
• Proper operation of existing local protection system
will not be affected by action of DVR.
• The coordination between relays is automatically

ensured.
3.2 Activation mechanism Normally, DVR is
used as multi-function device dealing with improvement
of power quality, for example, DVR may be utilized to
compensate for voltage sags, unbalanced voltage prob-
lems and harmonic compensations. However, when a
fault occurs somewhere downstream then a control sig-
Fig. 5. Activation mechanism applying for DVR
nal will be fed to DVR’s control circuit and DVR starts
working as fault current limiter. This control signal will
override all other control signals referred to above power
quality improvement functions.
I. Axente et al. proposed fault detection method by
adding an extra fault detection block
(4)
, this block took
responsibility for impedance measurement such that im-
plemented in commercial distance relays. However,
that adding extra impedance measurement block is very
costly solution (for reference, distance relay usually is
one of the most expensive relay) and the implementa-
tion of that block is not simple.
Other authors suggested a solution by adding over-
current detection block into DVR configuration
(6)
, but
building an extra block means that more money is
needed.
Besides those costly solutions, a simpler solution can
be implemented by extracting signal from existing pro-

tection system. Generally, protection system is well de-
signed for detecting any fault that may occur at pro-
tected zone, therefore, any signal comes from protection
system can be trusted. Based on that analysis, the sig-
nal used to activate DVR can be extracted from output
circuit of existing protection system. In other word,
when protection system picks up due to detection of
fault, it will concurrently send a signal to activate DVR
(Fig. 5). This proposal will ensure that fault current
limiting function of DVR will only activate when fault
occurs at protected zone, moreover, no extra build-in
fault detection block is needed.
3.3 Termination of DVR after fault cleared
Termination of DVR action must be carefully con-
sidered, otherwise DVR will keep functioning even
when fault has been cleared. In the study done by
L. Y. Wei et al.
(6)
fault clearance was detected by sens-
ing voltage at load bus, but this solution is applied only
when distance between DVR and loads is short enough.
Other authors offered a solution by installing an extra
communication channel between DVR and protection
system, however, both studies did not clarify how fault
is eliminated
(5) (6)
. Another drawback of the above so-
lutions may occur in case of downstream fault and local
CB refuses to trip; in this case the fault will persist
without any elimination.

Alternative solution to terminate DVR’s action pro-
posed in this study is based on the fact that: if com-
pensated fault current level is kept at 2 × I
pickup
(as
stated in Sect. 3.1), consequently when fault occurs, re-
lays will operate as normal even DVR is compensating
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 3
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
213
eBook for You
Fig. 6. Termination mechanism applying for DVR
Fig. 7. Fault at load side and corresponding se-
quence actions
the fault current. Relay will count down setting time
and send tripping signal to open CB whenever setting
time is over. At the moment when relay issues tripping
signal, DVR should be terminated.
Based on that analysis, termination signal feeding to
DVR can be extracted from tripping circuit of relay.
This principle is illustrated in Fig. 6.
In case of fault occur at load side as shown in Fig. 7,
both protection systems of load and feeder pick up, but
only load’s protection system (LPS) trips and open CB
at load side. Whenever fault is cleared by opening CB at
load side, feeder’s protection (FPS) will reset to standby.
In this situation, DVR already is activated due to FPS
picked up, but there is no signal to terminate DVR’s op-
eration since FPS reset without issuing any tripping sig-

nal. In order to deal with this situation, a back up signal
used to terminate DVR’s operation should be deployed.
This paper proposes a solution to obtain the back up ter-
mination signal based on that monitoring DC-link volt-
age. When DVR is operating as fault current limiter, it
can be seen that DVR will absorb energy from upstream
source through the coupling transformer, but the diode
rectifier can not feed the energy back to the source; it
will lead to DC-link voltage pumping-up
(3)
. Since fault
is cleared, the flowing current will drop down below the
setting level of compensated current, at that moment,
DVR will reverse its action and try to increase current
level in order to keep input of its comparator at zero. In
term of energy, now DVR will start injecting energy into
system, as a result, DC-link voltage will decrease. This
principle can be clarified by the block diagram in Fig. 8.
Based on that analysis, the clearance of fault can be de-
tected by tracing the DC-link voltage. Whenever the
DC-link voltage drops down after going up, it can be
assumed that fault has been cleared and DVR as fault
current limiter should stop operating.
Energy absorbed by DVR during compensation pro-
cess can be express approximately by:
Fig. 8. Relationship between DC-link voltage and
operation of DVR
ΔE = P
c
× t

prot
···························· (3)
where:
P
c
: total active power flowing into DVR.
t
prot
: operating time of protection system.
Total active power P
c
flowing into DVR is determined
by:
P
c
=3× V
injected
× I
compensated
× cos(θ) ···· (4)
with θ = angle(V
injected
,I
compensated
)
Maximum voltage can occur across capacitor is:
U
DCmax
=


2ΔE
C
·························· (5)
And voltage across capacitor as function of time can
be represented by:
U
DC
(t)=U
DCmax
×

1 − e
−t/τ

············ (6)
where τ is time constant of circuit.
This principle will be clarified further more by simula-
tion result in Sect. 5.3.
In summary, the current limiting function in DVR can
be terminated by signals from FPS and DC-link voltage
monitoring mechanism, at this point, one may question
whether the termination mechanism can be achieved
only by monitoring DC-link voltage and external trip-
ping signal from FPS is really needed or not. The rea-
son why both terminating signals are still utilized in this
proposal can be convinced as follow:
• To increase the reliability of terminating mecha-
nism: that using both signals (from DC-link voltage
monitoring mechanism and from FPS) will enhance
the reliability of terminating mechanism.

• If only DC-link voltage monitoring mechanism
is utilized: basically, DC-link voltage monitoring
mechanism takes time to process signal and it will
not respond as fast as FPS does in case of fault oc-
curs at feeder. In other word, DC-link voltage mon-
itoring mechanism will give a bit longer fault clear-
ance time in comparison with that done by FPS.
4.
Circuit and control block of DVR serv-
ing as fautl current limiter
Simulation was implemented by PSCAD software.
The proposed DVR model is three phase inverter model
with common DC energy storage as shown in Fig. 9.
Main components of DVR model include:
• Coupling transformer.
4 IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
214
eBook for You
Fault Current Limiting Function of Dynamic Voltage Restorer Utilizing Signals from Existing Protective Relays
g11
g21
g31
g42
g52
g62
1
2
3

2
5
2
4
2
6
2
2
2
4000.0 [uF]
Vic_a
Vic_b
Vic_c
#1 #2
#1 #2
#1 #2
Timed
Fault
Logic
g22
g51
5
2
2
2
g32
g61
3
2
6

2
g12
g41
1
2
4
2
Vsa
Vsb
Vsc
Vasend
Vbsend
Vcsend
Iasend
Ibsend
Icsend
1.0
A
B
C
VFPh
FAUL TS
C
B
A
Fault Type
C
B
A
BK

0.002 [H]
0.002 [H]
0.002 [H]
0.6 [ohm]
0.6 [ohm]
0.6 [ohm]
P+j
Q
Fig. 9. Basic simulation model of DVR
Va
Vb
Vc
PLL
theta
Ia
Ib
Ic
Generate phase angle
for referece signal
Sin
Sin
Sin
D
+
F
-
D
+
F
+

Icref
Ibref
Iaref
120.0
120.0
*
*
*
*
1
D
+
F
-
Delta_
a
Delta_
b
Delta_
c
Ia
Ib
Ic
Ma
g
. of referece current
D
+
F
-

D
+
F
-
I
P
I
P
I
P
Limiter
Fig. 10. Control block of DVR
• Voltage Sourced Inverter (VSI).
• Control system.
The inverter consists of 6-leg inverter (three single phase
full bridge inverters) using a common DC link. The ba-
sic function of the VSI is to convert the DC voltage sup-
plied by the energy storage device into an AC voltage.
The VSI operating in PWM adds voltage harmonics to
the load. To reduce harmonic, filters can be installed at
either low voltage or high voltage side of the coupling
transformer to block high frequency harmonics caused
by DC to AC conversion. In the DVR power circuit,
step up voltage transformer (coupling transformer) is
used, thus a VSI with a low voltage rating is sufficient.
A simple control block diagram of DVR is illustrated
in Fig. 10. Details parameters of simulation model is
shown in appendix. The desired reference current is gen-
erated from a phase locked loop synchronized to the sup-
ply side three-phase AC current. The actual measured

current is compared with the reference currents, and
the difference is fed through PI controller to generate
a modulation index which is applied to the pulse width
modulated (PWM) carrier switching signal to generate
turn-on and turn-off pulses to the IGBTs. The control is
single phase based to achieve best performance, in other
word; the DVR has independent phase control.
For fast response and to maximize dynamic perfor-
mance, direct feed-forward type control architecture is
Fig. 11. Control principle used to keep DVR in
null state
applied in the control strategy of the DVR. With this
control, a fast response time (approximately half cycle)
can be achieved to compensate fault currents.
During normal condition, DVR is kept in null state.
This state is implemented by removing the PWM firing
from the IGBTs in the phases and instead, continuously
fires the IGBTs in half of each single phase portion of
the VSI as shown in Fig. 11, so that the series wind-
ings are short circuited. When DVR is activated, PWM
firing is fed to all IGBTs in phases as normal.
5.
Simulation and discussion
5.1 Simulation setting In this study, simula-
tions were run with following parameters:
• Maximum load current: I
Loadmax
 75 [A]
• Maximum fault current: I
F aultmax

 700 [A]
In power distribution system, overcurrent relay is com-
monly used due to its low cost, hence in this simulation,
that type of relay will be simulated as protection system.
• Pick up threshold of relay: I
pickup
= 115 [A] (RMS)
• Time setting of relay:
◦ t
setting
= 0.2 [s] for FPS relays.
◦ t
setting
= 0.1 [s] for LPS relays.
These settings are intentionally used because the author
would like to have the reader’s attention focused on the
transition process from pre-fault to post-fault in which
fault current limiting function of DVR shows its effect
(in practice, time margin between FPS and LPS is nor-
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 5
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
215
eBook for You
CURRENT
(
in Am
p
ere
)

0.000 0.050 0.100 0.150 0.200 0.250 0.300



-1.0k
-0.8k
-0.5k
-0.3k
0.0
0.3k
0.5k
0.8k
1.0k
y
Ia Ib Ic
Fig. 12. Three-phase fault without DVR
CURRENT
(
in Am
p
ere
)
0.000 0.050 0.100 0.150 0.200 0.250 0.300



-1.0k
-0.8k
-0.5k
-0.3k

0.0
0.3k
0.5k
0.8k
1.0k
y
Ia Ib Ic
Fig. 13. Three-phase fault with DVR and DVR is
terminated by FPS
mally higher).
As stated in Sect. 3.1, minimum required sensitivity
of protection system should not be less than 2 pu, there-
fore, setting level of compensated current should be:
I
compensated
=2× I
pickup
=2× 115 = 230 [A].
In other word, when DVR operates as fault current lim-
iter it should reduce fault current magnitude to about
230 [A]. All the faults are assumed to start at 0.03 [s].
5.2 Simulation procedure Simulation is car-
ried out with various scenarios:
• Fault occurs at feeder side: this scenario used
to verify the effectiveness of mechanism to acti-
vate/terminate DVR by FPS.
• Fault occurs at load side: This simulation is to ver-
ify the proposal used to terminate DVR action by
tracing DC link voltage and to verify the proper co-
ordination between FPS and LPS.

5.3 Result and discussion Simulation results
and discussion are shown below.
Figure 12 shows three-phase fault current (fault takes
place at feeder) with DVR is not activated, fault cur-
rent is about 700 [A] (about ten times of normal load
current). In case DVR is activated (Fig. 13), DVR
takes full effect just after one cycle and fault current is
reduced to 230 [A] (rms) as expected. In this case, DVR
is activated and terminated by FPS.
Comparing Fig.12 with Fig. 13, it can be seen that
the operation of FPS is not interfered even while DVR
is operating, FPS cleared fault after 0.2 [s] based on its
own setting. Similarly, Fig. 14 and Fig. 15 show the
case of phase-phase fault.
In Fig. 15, it can be seen that, DVR performed sin-
gle phase control perfectly, only two faulty phases (a
and b) are compensated while healthy phase (c) remain
constant. Moreover, fault clearance time of relay still
CURRENT
(
in Am
p
ere
)
0.000 0.050 0.100 0.150 0.200 0.250 0.300



-1.0k
-0.8k

-0.5k
-0.3k
0.0
0.3k
0.5k
0.8k
1.0k
y
Ia Ib Ic
Fig. 14. Phase-phase fault without DVR
CURRENT
(
in Am
p
ere
)
0.000 0.050 0.100 0.150 0.200 0.250 0.300



-1.0k
-0.8k
-0.5k
-0.3k
0.0
0.3k
0.5k
0.8k
1.0k
y

Ia Ib Ic
Fig. 15. Phase-phase fault with DVR activated
CURRENT
(
in Am
p
ere
)
0.000 0.050 0.100 0.150 0.200 0.250 0.300



-1.0k
-0.8k
-0.5k
-0.3k
0.0
0.3k
0.5k
0.8k
1.0k
y
Ia Ib Ic
Fig. 16. Three-phase fault at load side without
DVR
is 0.2 [s] that means DVR’ operation did not affect the
protection system.
In next section, the cases with three-phase fault at
load side (as shown in Fig. 7) is investigated. Firstly,
DVR is not activated. In this situation, fault current is

570[A] (Fig. 16) and it is smaller than that in case fault
took place at feeder because now fault location is moved
far away the source. LPS cleared the fault after 0.1 [s] as
expected and whenever fault is cleared hence current get
back to normal load current (current did not go down to
zero because only faulty part is eliminated and healthy
part is untouched). Apparently, restored load current is
lower than that of pre-fault condition because the faulty
section is eliminated.
Secondly, DVR is utilized. In this case DVR is ac-
tivated by FPS because when fault occurs hence both
FPS and LPS pick up. Figure 17 shows that DVR again
fully perform its effect just after one cycle as shown in
other cases.
When fault occurs, DC link voltage goes up (Fig. 18)
since DVR is absorbing energy from upper source. Next,
LPS eliminates the fault after 0.1 [s] (at the same time
FPS reset to standby), DVR immediately reverse its ac-
tion this leads to DC link voltage goes down suddenly.
6 IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
216
eBook for You
Fault Current Limiting Function of Dynamic Voltage Restorer Utilizing Signals from Existing Protective Relays
CURRENT
(
in Am
p
ere

)
0.000 0.050 0.100 0.150 0.200 0.250 0.300



-1.0k
-0.8k
-0.5k
-0.3k
0.0
0.3k
0.5k
0.8k
1.0k
y
Ia Ib Ic
Fig. 17. Three-phase fault at load side with DVR
activated by FPS and terminated by DC-link volt-
age tracing mechanism
Main : Gra
p
hs
0.000 0.050 0.100 0.150 0.200 0.250 0.300

-2.0
0.0
2.0
4.0
6.0
8.0

10.0
12.0
y
DC voltage
Fig. 18. DC-link voltage during fault at load side
At the time DC link voltage drops down then conse-
quently DVR is terminated and fault current get back
to normal level. This simulation again validates the the-
oretical analysis shown in Sect. 3.3.
6.
Conclusion
In this paper, the dynamic voltage restorer is proposed
to use as a fault current limiter. A new method to ac-
tivate that fault current limiting function by the signals
from existing protection system is proposed and tested.
Moreover, the coordination between existing protection
system and fault current limiting function of dynamic
voltage restorer is investigated and implemented. This
proposal offers many advantages such as the reduction
in the cost of DVR device; the proper coordination be-
tween protection systems is ensured regardless of the
fault location and even when the fault current has been
altered. Finally, all the simulation results have validated
the effectiveness of proposal.
References
( 1 ) L. Moran, R. Oyarzun, I. Pastorini, J. Dixon, and R. Wallace,
“A fault protection scheme for series active power filters”,
Power Electronics Specialists Conference, Vol. 01, pp.489–
493 (1996)
( 2 ) N. H. Woodley, L. Morgan, and A. Sundaram, “Experi-

ence with an inverter-based dynamic voltage restorer”, IEEE
Transactions on Power Delivery, Vol. 14, No.03, pp.1181–
1186
( 3 ) G. Xiao, Z. Hu, C. Nan, and Z. Wang, “DC-Link voltage
pumping-up analysis and phase shift control for a series active
voltage regulator”, Proceeding of 37th IEEE Power Electron-
ics Specialists Conference, pp.1–5 (2006)
( 4 ) I. Axente, M. Basu, M. F. Conlon,, and K. Gaughan, “Protec-
tion of DVR against short circuit faults at the load side”, Pro-
ceeding of the 3rd IET International Conference on Power
Electronics, Machines and Drives, pp.627–631 (2006)
( 5 ) S. S. Choi, T. X. Wang, and D. M. Vilathgamuwa, “A se-
ries compensator with fault current limiting function”, IEEE
Transactions on Power Delivery, Vol. 20, No.03, pp.2248–
2256
( 6 ) L. Y. Wei, D. M. Vilathgamuwa, C. L. Poh, and F. Blaab-
jerg, “A dual-functional medium voltage level DVR to limit
downstream fault currents”, IEEE Transactions on Power
Electronics, Vol. 22, No.04, pp.1330–1340
(7) GET-6450 Distribution System Feeder Overcurrent Protec-
tion, GE Publication (1997)
(8) IEEE Std. 1596-1992,Guide for Protective Relay Applica-
tions to Transmission Lines, IEEE (1992)
( 9 ) A. C. Enriquez and E. V. Martinez, “Sensitivity improve-
ment of time overcurrent relays”, Electric Power Systems Re-
search, Vol. 77, No.02, pp.119–124 (2007)
Appendix
Parameters in simulation
- Source & Load (Fig. 9)
Source voltage: 7.5 [kV] (L-L, RMS)

Frequency: 50 Hz
Source impedance: 1

80 [Ω]
Total load impedance: 55 [Ω]
- Coupling transformer
Voltage ratings: 7.5 [kV]
Transformer MVA: 0.6 [MVA]
Leakage reactance: 0.05 [pu]
- Fault resistance
The value of fault current can be adjusted by chang-
ing fault resistance.
To simulate the fault at feeder: R
fault
= 5 [Ω]
To simulate the fault at load: R
fault
= 10 [Ω]
- Reference current in control system (Fig. 10)
I
aref
= I
bref
= I
cref
= 325 [A](peak) or 230
[A](rms)
Nguyen Xuan Tung (Non-member) was born in Hai
Duong, VietNam, on April 15, 1975. He re-
ceived the B.E. from Hanoi University of Tech-

nology, VietNam in 1999 and the M.E degree
from Curtin University of Technology, Aus-
tralia in 2005. Currently, he has been pursuing
PhD degree in Shibaura Institute of Technol-
ogy, Japan. His interests are about relay pro-
tection system and power quality issue.
Fujita Goro (Member) was born in January 1970. He re-
ceived the B.E., M.E. and Ph.D degrees in
electrical engineering from Hosei University,
Tokyo, Japan in 1992, 1994 and 1997 respec-
tively. In 1997, he was a research student of
Tokyo Metropolitan University. Since 1998, he
is in Shibaura Institute of Technology, Tokyo,
Japan as an associate professor. His interest
is in power system opeartion and control. He
is a member of the Society of Instrument and
Control Engineers (SICE) of Japan, the IEE of Japan, and IEEE.
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx
7
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
217
eBook for You
Paper
Phase Load Balancing In Distribution Power System
Using Discrete Passive Compensator
Nguyen Xuan Tung

Non-member
Goro Fujita


Member
Kazuhiro Horikoshi
∗∗
Member
This paper describes a new proposal to deal with imbalance phase loading phenomenon in power distribu-
tion system. Discrete switched passive shunt compensators such as reactors or capacitor banks are considered
as the means to compensate for that imbalance phenomenon. Discrete switched passive compensator offers
advantages in term of installation cost and simplifies the maintenance process.
A new algorithm is developed to calculate the size of discrete compensators, this algorithm incorporates
the unbalance power flow calculation module and optimal compensator sizing module. In addition, the algo-
rithm is written in MATLAB language and tested on an actual three phase-three wires distribution feeder.
Extensive tests have validated the effectiveness of the proposal and shown that this proposal can be a useful
tool for any electrical utilities.
Keywords: Phase Loading Imbalance, Discrete Optimization, Passive Compensation, Distribution System.
1. Introduction
In power system, voltages (and currents) are expected
to be sinusoidal and equal in magnitude, with the in-
dividual phases 120
0
apart. However, the utilities usu-
ally experience the imbalance phenomenon in both volt-
age and current. The nature of imbalance phenomenon
includes unequal magnitude and phase angle deviation
among phases. A major cause of voltage and current im-
balances is that loads are not uniformly spread among
the three phases and load peaks are non-coincident due
to diversity of load categories. Additional causes of
power system imbalances can be asymmetrical distribu-
tion feeder impedances possibly caused by incomplete

transposition of feeder lines.
The influence of imbalance voltage and current on
power system has been well investigated in literature.
V. J. Annette et al.
(1)
and L. F. Ochoa et al.
(2)
con-
cluded that unbalanced voltages and currents can result
in adverse effects on equipment and on the power sys-
tem, for example a small unbalance in the phase volt-
ages can cause a disproportionately larger unbalance in
the phase currents. Under unbalanced conditions, the
power system will incur more losses and heating effects.
The effect of voltage unbalance can also be severe on
equipment such as induction motors, power electronic
converters and adjustable speed drives.
Many mitigation techniques have been developed to
deal with imbalance phenomenon in distribution system,
generally those solutions can be divided into two cate-

Shibaura Institute of Technology
3-7-5, Toyosu, Koto-ku, Tokyo 135-8548
∗∗
Tohoku Electric Power Co.,Inc.
7-2-1, Nakayama, Aoba-ku, Sendai, Miyagi 981-0952
gories:
• Rearrange feeders or redistribute the loads in such a
way the system becomes more balanced
(3)∼(5)

.How-
ever, the utilities usually cannot afford too many
load swapping due to the long time interruption of
customers and cost of labors to implement those op-
erations.
• Install compensators (power quality conditioners)
to compensate for any imbalance quantities
(6)∼(9)
.
They seem to be the most possible solutions but an-
other concern raised by utilities is the capital cost
of these solutions.
This paper focuses on the second mitigation technique
and will establish an appropriate solution in term of cap-
ital cost. For imbalance compensation purpose, active
compensator such as Distribution Static Compensator
(DSTATCOM) is widely introduced in literature, the
power electronic solutions are elegant, however, they in-
clude a greater degree of cost. Cost has been the ma-
jor factor in limiting the application of power electronic
solution over power distribution level. Based on that
fact, solutions those involve passive compensators such
as switched capacitor or switched reactor banks would
seem to be the most cost effective solution and these will
be investigated in this paper.
Moreover, a new algorithm is developed to calculate
the size of compensators. This algorithm includes un-
balance power flow calculation module and discrete op-
timal compensator sizing module. The objective of this
algorithm is to find the optimal size of compensators so

that minimize the unbalanced power flow through the
main feeder. The algorithm allows the user to specific
the type and the maximum number of available taps
for each compensator. In addition, detailed model of
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 1
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
218
eBook for You
Fig. 1. Diagram of unbalanced load and compensator
the feeder including mutual coupling effect, the type of
loads and time-varying load patterns are also considered
in the algorithm in order to suggest the compensator’s
switching patterns over time. Finally, the algorithm is
written in MATLAB language and tested on the data
retrieved from an actual three-phase, three-wire distri-
bution feeder to verify its effectiveness.
2.
Compensation principle
Figure 1 shows the general unbalanced three-phase
load fed from a three-phase, three-wire source. Load
and compensator are connected in delta therefore zero
sequence component will equal to zero. The compen-
sator currents (
.
I
ac
,
.
I

bc
,
.
I
cc
) is added to load currents
(
.
I
al
,
.
I
bl
,
.
I
cl
) and then the following equation is satisfied
(written for phase A, similarly for phase B and C):
.
I
a
=
.
I
al
+
.
I

ac
=(
.
I
a1l
+
.
I
a2l
+
.
I
a0l
)+(
.
I
a1c
+
.
I
a2c
+
.
I
a0c
)
=(
.
I
a1l

+
.
I
a1c
)+(
.
I
a2l
+
.
I
a2c
)+(
.
I
a0l
+
.
I
a0c
) · (1)
Here subscripts “c” and “l” represent for the quantities
coming from compensator and load respectively:

.
I
a
: line current supplying to load after compensa-
tion.


.
I
a1
,
.
I
a2
,
.
I
a0
: positive, negative and zero current
sequence components.
The objective of load compensation is to eliminate or
limit any the negative and zero sequence components of
load currents. Since zero components are zero therefore
in this case the line currents will become perfectly bal-
anced if the negative sequence component is eliminated.
Mathematic expression of above statement is shown in
Eq. 2
(
.
I
a2l
+
.
I
a2c
)=0···························· (2)
Because I

a2l
and I
a2c
are complex numbers then Eq. 2
is equivalent to:

real(
.
I
a2l
)+real(
.
I
a2c
)=0
imaginary(
.
I
a2l
)+imaginary(
.
I
a2c
)=0
(3)
The Eq. 3 mathematically depicts the overall conditions
for load balancing.
3.
Possibility of using only either capaci-
tive or inductive element as a compen-

sator
One of the factors which electrical utility consider
Fig. 2. Diagram of three-phase compensator
when installing the compensator is the capital cost,
therefore the lossless compensator is a first top prior-
ity and the simplicity of compensator bank is preferred
as well. For those reasons, capacitive and inductive com-
pensator banks would be the most prominent solutions.
Furthermore, if a compensator consists of both inductive
and capacitive banks then the compensation system will
be obviously more complex than that if only either pure
capacitive or pure inductive bank is used. Moreover,
the higher complexity degree of compensator will result
in more investment money and more time for mainte-
nance. In order to offer cost advantages to utilities, the
possibility of using only either capacitive or inductive
compensation bank as the phase loading compensator
will be proven in this section.
Considering the general case where the compensator
is full thee-phase and delta connection as shown in Fig. 2
(here Y
ab
, Y
bc
, Y
ca
are compensator’s admittances).
Assume that phase voltages are perfectly balanced:
.
V

A
= V ∠0
0
,
.
.
V
B
= V ∠120
0
,
.
V
C
= V ∠240
0
Currents generated by compensator are calculated as
shown in Eq. 4:









.
I
ac

=

.
Y
ab
(1 − a
2
) −
.
Y
ca
(a − 1)

× V
.
I
bc
=

.
Y
bc
(a
2
− a) −
.
Y
ab
(1 − a
2

)

× V
.
I
cc
=

.
Y
ca
(a − 1) −
.
Y
bc
(a
2
− a)

× V
· (4)
where a is a 120
0
phase shift operator: a =1∠120
0
.
Based on Eq. 4, the current sequence components of
compensator are derived as follow:




.
I
a0
=0
.
I
a1
=(
.
Y
ab
+
.
Y
bc
+
.
Y
ca
) × V
.
I
a2
= −(a
2
.
Y
ab
+

.
Y
bc
+ a
.
Y
ca
) × V
······ (5)
Now considering some particular cases where the com-
pensators are single-phase elements only. The possible
configurations are shown in Fig. 3.
• Case (a): Single-phase compensator is connected
across phase A and phase B (Y
bc
=0, Y
ca
=0).
In order to generalize the results, the values used in
this section will be in per unit.
Substitute (Y
ab
, Y
bc
=0,Y
ca
= 0) into Eq. 5, cur-
rent sequence components produced by this single
phase compensator are:
2 IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx

Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
219
eBook for You
Phase Load Balancing In Distribution Power System Using Discrete Passive Compensator
Fig. 3. Diagram of single-phase compensations
Table 1. Negative current components con-
tributed by various single phase compensator
configurations
Negative Current
Compensator
Capacitive Inductive
.
I
a2(AB)
1∠30
0
1∠−150
0
.
I
a2(BC)
1∠−90
0
1∠90
0
.
I
a2(CA)
1∠150

0
1∠−30
0
Fig. 4. Vector diagram of negative current com-
ponents generated by various single phase compen-
sator configurations



.
I
a0(AB)
=0
.
I
a1(AB)
=
.
Y
ab
× V
.
I
a2(AB)
= −a
2
×
.
Y
ab

× V
···········(6)
Here subscript “AB” denotes current quantities re-
sulting from the single phase compensator con-
nected across phases A&B.
◦ If the compensator is capacitive element with
impedance of X
C
.
I
a2(AB)
= −a
2
×
.
Y
ab
× V
=
V
X
C
∠30
0
=1∠30
0
········ (7)
◦ If the compensator is inductive element with
impedance of X
L

.
I
a2(AB)
= −a
2
×
.
Y
ab
× V
=
V
X
L
∠−150
0
=1∠−150
0
·· (8)
• Case (b) & (c): Similar calculations are applied for
case (b) and case (c).
Table 1 and Fig. 4 show the results of sequence compo-
nents contributed by various single phase compensator
configurations. Assume that the compensator must
generate a required negative sequence current as shown
in Fig. 5. This required vector will be decomposed into
two nearest available vectors:
• Case a: If the compensator is capacitive then the re-
quired vector can be decomposed into the two near-
est component vectors on CA and BC axes with

Fig. 5. Decomposition of required negative cur-
rent vector into two nearest component vectors
magnitudes of a (pu) and b (pu) respectively as
shown in (Fig.5-a).
In order to generate the a (pu) vectors on CA axis
then a single phase capacitive compensator con-
nected across phases C&A must be used (accord-
ing to Table. 1). The value of CA capacitive single
phase compensator will be:
X
C(CA)
=
1
a
→ Y
ca
=
1
X
C(CA)
= a (pu)
Similarly, another single phase capacitive compen-
sator connected between phases B&C must be used
to generate b (pu) vector on BC axis.
X
C(BC)
=
1
b
→ Y

bc
=
1
X
C(BC)
= b (pu)
Finally, configuration of capacitive compensator will
be: [Y
ab
; Y
bc
; Y
ca
] = [0; b; a]
• Case b: Similarly, if compensator is inductive then
a pair of two single phase compensators connected
across phases A&B and B&C must be used (Fig.5-
b).
The final inductive compensator configuration will
take follow form: [Y
ab
; Y
bc
; 0].
In summary, the compensator which is formed from ei-
ther pure capacitive or pure inductive banks can gener-
ate any desired negative current regardless of magnitude
and phase angle. In other word, it is possible to use
only either capacitive or inductive elements to balance
the phase load currents.

4.
Phase load balancing in distribution
system
4.1 Problem formulation The implementation
of load balancing or load compensation in distribution
level may involve some of follow aspects:
Technical aspects:
• Compensation algorithm must be able to apply to
calculate for not only individual load but also for
feeder with several connected loads. The problem
of unbalanced phase loading is not new in power
systems, however, the previous proposed solutions
are to deal with single individual unbalanced load
only and they did not figure out how to deal with
the feeder which has several connected loads
(6)∼(9)
.
The contribution of this paper is to propose an al-
gorithm which can apply to solve the unbalanced
phase loading phenomenon for not only single load
but also for the feeder accommodating several loads
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 3
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
220
eBook for You
Fig. 6. Representative feeder
as seen in practice.
• Algorithm must produce as more accurate results
as possible in comparison with other proposed so-

lutions: in literature, all the calculations were
based on assumption that voltages are perfectly bal-
anced
(6) (7)
, but actually voltages at load terminal
may not be always balanced due to many reasons.
In order to overcome this limit and to provide a more
accurate solution, this proposed algorithm will use
the actual node voltages (not assumed voltages) in
all calculations.
Cost advantage aspects: The key contribution of this
paper is that proposing an economically justifiable com-
pensation solution.
• In order to reduce investment cost and make it ap-
plicable to power distribution level then only either
pure capacitor bank or pure reactor bank is consid-
ered to form the compensator as stated in Sec. 3,
mixed capacitive and reactive compensator bank is
not an option.
• As stated in Sec. 1, power electronic compensators
or active compensators are a perfect choice but these
solutions are far more expensive than that if the pas-
sive compensators are selected.
For that consideration, the discrete switched pas-
sive compensator banks (such as discrete capacitor
or discrete reactor bank) will be utilized as the com-
pensator.
4.2 Phase load balancing algorithm The im-
balance phase loading phenomenon does not immedi-
ately show its influence over system and equipments due

to the fact that thermal inertias of equipments are quite
long. Based on that analysis, it is not really imperative
to instantly correct the imbalance phase loading situ-
ation since it occurs and the balancing action can be
carried out on averaged data over a time interval. In
other word, if daily loading curve is known then it can
be stripped into smaller intervals and the compensation
action will be calculated based on the unbalance factor
averaged over each that time interval.
From above view point, load balancing algorithm is pro-
posed as follow: Considering the representative feeder
with m loads as shown in Fig. 6.
Step 1: Determine the first loading level (n =1)toas-
sess for imbalance compensation (here n stand for load-
ing level order).
Step 2 : Run three-phase, unbalance power flow calcu-
lation with the given loading level from step 1.
This unbalance power flow module has ability to handle
for various types of loads such as the load with con-
stant power; load with constant impedance or load with
constant current
(11)
. Furthermore, mutual impedance of
distribution line is also taken into account.
The outputs of this step will be all node voltages
(V
Ai
,V
Bi
,V

Ci
) and all load currents (I
ali
,I
bli
,I
cli
) with
i =1÷ m (here subscript “i” is used for numbering
the loads).
Step 3: Calculate negative current
.
I
a2li
produced by
load.
Start calculating with the last load (corresponding to
i = m) at ending section of the feeder as shown in Fig. 6.
Load currents (I
ali
,I
bli
,I
cli
) resulting from step 2 will be
used in here. Equation 9 shows the calculation:
.
I
a2li
=

1
3
(
.
I
ali
+ a
2
.
I
bli
+ a
.
I
cli
)
= C
i
+ jD
i
·····························(9)
with C
i
and D
i
are real and imaginary parts of negative
current produced by load number i.
Step 4 : Calculate the compensator size. This step
consists of the follow sub-steps:
* Establish load balancing equations to determine the

compensator’s negative current which will cancel load
negative current resulting from step 3. In this step, ac-
tual load voltages (V
Ai
,V
Bi
,V
Ci
) from step 2 will be used
in calculation to improve accuracy.
Referring to Fig. 2, current generated by compensator
is:



.
I
aci
=(
.
V
Ai

.
V
Bi
)
.
Y
abi

− (
.
V
Ci

.
V
Ai
)
.
Y
cai
.
I
bci
=(
.
V
Bi

.
V
Ci
)
.
Y
bci
− (
.
V

Ai

.
V
Bi
)
.
Y
abi
.
I
cci
=(
.
V
Ci

.
V
Ai
)
.
Y
cai
− (
.
V
Bi

.

V
Ci
)
.
Y
bci
(10)
Here Eq. 10 looks different with Eq. 4 due to the fact
that actual voltages
.
V
Ai
,
.
V
Bi
,
.
V
Ci
of node i are used
instead of assumed balanced voltages V . In Eq. 10, node
volatges
.
V
Ai
,
.
V
Bi

,
.
V
Ci
are already known;
.
Y
abi
,
.
Y
bci
,
.
Y
cai
are compensator’s admittances and are all unknown
variables.
Applying symmetrical component theory, negative cur-
rent injecting by compensator will be:
.
I
a2ci
=
1
3
(
.
I
aci

+ a
2
.
I
bci
+ a
.
I
cci
)
= E
i
+ jF
i
··························· (11)
here E
i
and F
i
are real and imaginary parts of negative
current required to generate by compensator number i.
Note that E
i
and F
i
are functions of variables
.
Y
abi
,

.
Y
bci
,
.
Y
cai
:

E
i
= E
i
(
.
Y
abi
,
.
Y
bci
,
.
Y
cai
)
F
i
= F
i

(
.
Y
abi
,
.
Y
bci
,
.
Y
cai
)
Load balancing process is to satisfy the balancing con-
ditions as stated in Eq. 3, in this context, substitute
E
i
,F
i
,C
i
,D
i
into Eq. 3 we come up with following load
balancing equations:

E
i
(
.

Y
abi
,
.
Y
bci
,
.
Y
cai
)+C
i
=0
F
i
(
.
Y
abi
,
.
Y
bci
,
.
Y
cai
)+D
i
=0

··········· (12)
Or in general form

E
i
(Y )+C
i
=0
F
i
(Y )+D
i
=0
4 IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
221
eBook for You
Phase Load Balancing In Distribution Power System Using Discrete Passive Compensator
with Y represents for compensator’s admittance.
* Solve load balancing equations by utilizing discrete
optimization technique.
Since load balancing conditions or equations have been
already established in Eq. 12 then the target of this step
is to find out the values of variables Y
abi
, Y
bci
, Y
cai

to
fulfill those equations.
Because Y
abi
, Y
bci
, Y
cai
can take only discrete values
(as mentioned in Sec. 4.1) then the Eq. 12 can not be
solved directly by conventional methods which apply to
only continuous variables. That is the reason why the
discrete optimization technique needs to take part in.
The objective of discrete optimization is to ultimately
fulfill the Eq. 12 so that minimize the negative current
magnitude of load. Mathematical expression of that ob-
jective function can be expressed as below:
J = min{(E
i
+ C
i
)
2
+(F
i
+ D
i
)
2
} ········· (13)

with E
i
& F
i
are function of compensator’s admit-
tance Y .
subject to



Y : set of n
d
discrete values

[Y ]
n
d
≥ [0] (for capacitor)
[Y ]
n
d
≤ [0] (for reactor)
n
d
: maximum number of taps for each compensator.
Each element of [Y ]
n
d
will be assigned to a value of cor-
responding tap in a discrete manner.

In this proposal, brute-force search algorithm is uti-
lized to solve the discrete optimization. The brute-force
search technique is simple to implement and will always
find a solution
(10)
.
Outputs of this step is optimal values of compensator
“i” (Y
abi
, Y
bci
, Y
cai
) in a discrete manner.
Step 5 : Add up compensator “i” to the correspond-
ing load “i” and go back to step 2. Now run the power
flow again with updated load “i” and roll up to calculate
compensator size for the upstream adjacent load “i−1”.
Repeat the process from step 2 to step 5 until all loads
are processed and final results will be values of all com-
pensators for all loads: {Y
abi
; Y
bci
; Y
cai
} with i =1÷ m.
Step 6 : Check for further compensation if is is neces-
sary.
Since all compensators have been added to all corre-

sponding loads then it is necessary to check for any fur-
ther compensation correction. This can be done by going
back to step 2 to run power flow again with all updated
loads and repeat all the above mentioned procedures.
The iteration will terminate whenever no further com-
pensation correction is required.
The condition to terminate calculation process is as fol-
low:
Whenever the conditions Y
abi
= Y
bci
= Y
cai
with all
i =1÷ m are satisfied then the iteration will stop be-
cause those conditions mention that all compensators
now are three-phase balanced. Since they are balanced
they will not produce any negative current to cancel for
load negative current. In other word, at this stage the
compensator size is already an optimal value and no fur-
ther compensation is needed.
Fig. 7. Phase load balancing algorithm
Outputs of this step 6 will be the final values of all
compensators. Those discrete optimal compensator’s
sizes will be used to determine the corresponding tap
positions. Those tap positions are the first switching
patterns of the compensators corresponding to the first
loading level.
Since compensation strategy to deal with a certain

level of unbalance has been already addressed, it is pos-
sible to run multiple unbalance level configurations in
order to figure out the switching scheme for compen-
sators over a day period. Therefore, next step is to go
back step 1 and begin to works with next loading level
(loading level “n + 1”).
Figure 7 shows the entire flow chart of the algorithm.
5.
Result and discussion
5.1 Simulation setup The load balancing algo-
rithm is written in MATLAB and the effectiveness of
algorithm is tested with the data collecting from an ac-
tual feeder which has 3 main lateral loads as shown in
Fg. 8. Simulations are run with following conditions:
• All loads have leading power factors (this is based
on actual data provided by power utility company).
• The compensators are selected to be all inductive
due to existing leading power factors of loads; if ca-
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 5
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
222
eBook for You
Fig. 8. Case study of feeder with three loads
1 2 3 4 5 6 7 8 9 10 11 12
0
2
4
6
8

10
12
14
16
Time Interval
Percentage (%)
Negative current through Line 1
Before After
Fig. 9. Negative currents before & after compen-
sation through Line 1
pacitive compensators are used then the power fac-
tor will become worse.
• Compensators are switchable with maximum 10
steps and each step is 25kVAR; 15kVAR and 5
kVAR for compensator 1; compensator 2 and com-
pensator 3 respectively.
In this paper, time interval for unbalance assessment is
selected as 2 hours, in other word, each compensator will
have 12 time-switching patterns over every 24 hours or
aday.
The load balancing algorithm is written in MATLAB.
This algorithm consists of two main modules.
• The first is unbalance power flow module. This un-
balance power flow module has ability to handle for
various types of loads such as the load with constant
power; load with constant impedance or load with
constant current. Furthermore, mutual impedance
of distribution line is also taken into account
(11)
.

• The second module is implementation of brute-force
search algorithm. This search algorithm is sim-
ple
(10)
, however, calculation time will grow signifi-
cantly when the size of problem increases. In power
distribution level, the discrete switched capacitor
bank (or reactor bank) has only a few number of
taps so that if even brute-force search is applied then
the calculation time will not be a matter.
5.2 Result and discussion
5.2.1 Effectiveness of compensation algorithm
The effectiveness of compensations are illustrated in
Fig. 9, 10 and 11. Based on results of negative current
before and after compensation, it is clear that the pro-
posed compensation strategy shows a significant load
balancing effect, the magnitudes of negative currents
that represent the imbalance degree may reduce to less
than 1% in some cases. However, the full compensa-
tion effect (resulting in zero negative current) cannot be
expected due to the discrete characteristic of compen-
sators.
In addition, the node voltages become balanced as a
1 2 3 4 5 6 7 8 9 10 11 12
0
2
4
6
8
10

12
14
16
Time Interval
Percentage (%)
Negative current through Line 2
Before After
Fig. 10. Negative currents before & after compen-
sation through Line 2
1 2 3 4 5 6 7 8 9 10 11 12
0
10
20
30
40
50
Time Interval
Percentage (%)
Negative current through Line 3
Before After
Fig. 11. Negative currents before & after compen-
sation through Line 3
1 2 3 4 5 6 7 8 9 10 11 12
0
0.1
0.2
0.3
0.4
0.5
0.6

0.7
0.8
Time Interval
Percentage (%)
Negative voltage at node 1
Before After
Fig. 12. Negative voltage b efore & after compen-
sation at node 1
1 2 3 4 5 6 7 8 9 10 11 12
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Time Interval
Percentage (%)
Negative voltage at node 2
Before After
Fig. 13. Negative voltage b efore & after compen-
sation at node 2
consequence of the phase load balancing actions. This
effect can be seen in Fig. 12, 13 and 14. As shown in
those figures, the imbalance degrees of voltage are small
and within acceptable level due to the fact that the
source is strong and possibly the distribution line sec-
tions are short.

Figure 15, 16 and 17 show the absolute value of node
voltages with respect to the source voltage of 6750 (V).
In this simulation, the downstream node voltages some-
times are higher than the source voltage due to the lead-
6 IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội
223
eBook for You
Phase Load Balancing In Distribution Power System Using Discrete Passive Compensator
1 2 3 4 5 6 7 8 9 10 11 12
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Time Interval
Percentage (%)
Negative voltage at node 3
Before After
Fig. 14. Negative voltage before & after compen-
sation at node 3
1 2 3 4 5 6 7 8 9 10 11 12
5600
5800
6000

6200
6400
6600
6800
7000
Time Interval
Node Voltage (V)
Phase A Phase B Phase C After
Fig. 15. Absolute voltage value before & after
compensation at node 1
1 2 3 4 5 6 7 8 9 10 11 12
5600
5800
6000
6200
6400
6600
6800
7000
Time Interval
Node Voltage (V)
Phase A Phase B Phase C After
Fig. 16. Absolute voltage value before & after
compensation at node 2
ing power factor condition. After compensation, the
leading reactive powers are partially absorbed by in-
ductive compensators and as a consequence, the down-
stream node voltages become not only mostly balanced
but also its magnitudes are reduced to appropriate level.
The maximum voltage deviation from the rated value is

about ± 3 % and all node voltages are within allowable
level.
The switching patterns of compensators are indicated
by their tap positions versus time. The results are pre-
sented in Fig. 18, 19 and 20. Moreover, the compen-
sation shows not only load balancing effect but it also
helps to reduce power losses through the investigated
system. Figure 21 shows power loss improvement after
compensation.
In this context, the power losses improvement (PLI) is
defined as follow:
1 2 3 4 5 6 7 8 9 10 11 12
5600
5800
6000
6200
6400
6600
6800
7000
Time Interval
Node Voltage (V)
Phase A Phase B Phase C After
Fig. 17. Absolute voltage value before & after
compensation at node 3
1 2 3 4 5 6 7 8 9 10 11 12
0
50
100
150

200
250
300
Time Interval
Tap position (kVAR)
Tap position vs Time for Compensator 1
AB BC CA
Fig. 18. Tap position vs Time for Compensator 1
1 2 3 4 5 6 7 8 9 10 11 12
0
20
40
60
80
100
120
140
160
180
Time Interval
Tap position (kVAR)
Tap position vs Time for Compensator 2
AB BC CA
Fig. 19. Tap position vs Time for Compensator 2
1 2 3 4 5 6 7 8 9 10 11 12
0
10
20
30
40

50
60
Time Interval
Tap position (kVAR)
Tap position vs Time for Compensator 3
AB BC CA
Fig. 20. Tap position vs Time for Compensator 3
PLI =
PL
bf
− PL
af
PL
bf
× 100 (%)
where PL
bf
and PL
af
are total power losses before and
after compensation.
According to results of simulation, power losses im-
provement can be more than 70% and in the the least
remarkable situation it is about 16%. The possible rea-
sons for power losses improvement can be convinced as
follow:
• As stated in Ref. (2), under unbalance loading situa-
IEEJ Trans. TEEE, Vol.xxx, No.xx, xxxx 7
Tổng hợp các bài báo khoa học giai đoạn 2007-2012
Bộ môn Hệ thống điện - Đại học Bách Khoa Hà Nội

224
eBook for You

×