PCVVN1418
Warning
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
R ead the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need
the outdoor unit close to the sea shore, contact your local distributor.
to install
Hotline: 0976 173 173
Đại lý phân phối
• HEAD OFFICE
TRUNG TÂM
DICH VU KHÁCH HÀNG
Miễn phí cöôùc cuoäc goïi
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan
CÔNG TY CỔ PHẦN VIỆT KIM
• VĂN PHÒNG CHÍNH
Tầng 14-15, tòa nhà Nam Á, 201-203 Cách Mạng Tháng 8, P.4, Q.3,
TP.HCM
Tel: (08) 62 504 888
Fax: (08) 62 504 999
• CHI NHÁNH HÀ NỘI
Tầng 12, tòa nhà Ocean Park Tower, 1 Đào Duy Anh, Quận Đống Đa,
Hà Nội
Tel: (04) 35 657 677
Fax: (04) 35 657 688
• CHI NHÁNH ĐÀ NẴNG
Tầng 12, Lô A2.1, Đường 30/4, P. Hòa Cường Bắc, Q. Hải Châu, TP. Đà Nẵng
Tel: (0511) 362 4250
Fax: (0511) 362 4251
www.daikin.com.vn
Specifications, designs and other content appearing in this brochure are current as of February 2014 but subject to change without notice.
All rights reserved
Printed in Vietnam
Hotline: 0976 173 173
Cooling Only / Heat Pump 50 Hz
Next Generation VRV IV System
First launched in Japan in 1982, the Daikin VRV system
First launched in Japan in 1982, the Daikin VRV system
has been embraced by world markets for over 30 years.
has been embraced by world markets for over 30 years.
Now, Daikin proudly introduces the next generation
Now, Daikin proudly introduces the next generation
VRV IV system.
VRV IV system.
It now offers an enhanced lineup to meet an ever
It now offers an enhanced lineup to meet an ever
wider variety of needs while improving energy savings,
wider variety of needs while improving energy savings,
comfort, and ease of installation.
comfort, and ease of installation.
INDEX
INDEX
Main Features
Main Features
P03
P03
Outdoor Unit
Lineup Unit
Outdoor
Lineup
P13
P13
Indoor Unit
Lineup
Indoor Unit
Lineup
P15
P15
Specifications
Specifications
P37
P37
Outdoor Unit
Combinations
Outdoor Unit
Combinations
P67
P67
Option List
Option List
P69
P69
Control Systems
Control Systems
P75
P75
Air Treatment
Equipment
Lineup
Air
Treatment
Equipment Lineup
Enhanced
Enhanced lineup
lineup
Energy
Energy saving
saving
3 types up to 60 HP
3 types up to 60 HP
Higher COP and VRT technology
Higher COP and VRT technology
Ease
Ease of
of installation
installation
Comfort
Comfort
Compact & lightweight design
Compact & lightweight design
P89
P89
Air Handling
Unit
Air Handling
Unit
P103
P103
Lower operation sound
Lower operation sound
* VRV is a trademark of Daikin Industries, Ltd.
* VRV is a trademark of Daikin Industries, Ltd.
01
01
Hotline: 0976 173 173
02
02
Excellent
Excellent Operation
Operation Performance
Performance
Energy
Energysaving
saving
Enhanced
EnhancedLineup
Lineuptoto33types
types
Higher
HigherCoefficient
CoefficientofofPerformance
Performance(COP)
(COP)
Enables
Enablesfurther
furtherenergy
energysaving
saving
1212HP-50
HP-50HP
HPwith
with4 4new
newmodels
modelslineup
lineup
Installation
Installation
Space
Space
Product
Product
Weight
Weight
1010
%%
Increase
Increase
Ease
Easeofofinstallation
installation
Compact
Compact&&lightweight
lightweightdesign
design
Offers
Offershigher
highercapacity
capacityofofup
uptoto6060HP
HP
6 6HP-60
HP-60HP
HPwith
with3 3new
newmodels
modelslineup
lineup
VRV
VRV
1,240
1,240
mmmm
COP
COP
during
during
cooling
cooling
operation
operation 3.94
3.94
20
20HP
HP
Highly-integrated
Highly-integrated
VRV
VRV
ⅣⅣ
system
system
offers
offers
compact
compact
outdoor
outdoor
units
units
to to
achieve
achieve
maximum
maximum
utilisation
utilisation
of of
thethe
installation
installation
space.
space.
3.94
3.94
Installation
Installation
Space
Space
1.66
1.66
m2m2
1.42
1.42
m2m2
Product
Product
Weight
Weight
490
490
kgkg
380
380
kgkg
VRV
VRV 12 12
HPHP
765765
mmmm
VRV
VRV 12 12
HPHP
1414
%%
Decrease
Decrease
2222
%%
Decrease
Decrease
New
Newseries
serieswith
withcompact
compact&&lightweight
lightweightdesign
design
1818HP-50
HP-50HP
HPwith
with1717new
newmodels
modelslineup
lineup
VRV
VRV
3.11
3.11
COP
COP
during
during
cooling
cooling
operation
operation 3.94
3.94
20
20HP
HP
Installation
Installation
Space
Space
1.66
1.66
mm
2
0.95
0.95
m2m2
Product
Product
Weight
Weight
490
490
kgkg
320
320
kgkg
2
Lineup
Lineup
Mo/C
Mo/C
4343
%%
Decrease
Decrease
3535
%%
2525
%%
Decrease
Decrease
Product
Product
Weight
Weight
285
285
kgkg
Product
Product
Weight
Weight
195
195
kgkg
3232
%%
Decrease
Decrease
8 HP
8 HP
1010
HPHP
1212
HPHP
5757
5757
5858
6060
5555
5656
5757
5959
Without
Without
increasing
increasing
operation
operation
sound,
sound,
advanced
advanced
analytic
analytic
technologies
technologies
are
are
utilised
utilised
to to
optimise
optimise
fanfan
design
design
and
and
increase
increase
airflow
airflow
rate
rate
and
and
high
high
external
external
static
static
pressure.
pressure.
Decrease
Decrease
New
New
Lineup
Lineup
High-COP
High-COP
Type
Type
Streamlined
Streamlined
airair
grille
grille
It promotes
It promotes
thethe
discharge
discharge
of of
swirling
swirling
airflow,
airflow,
further
further
reducing
reducing
thethe
pressure
pressure
loss.
loss.
Streamlined
Streamlined
scroll
scroll
fanfan
The
The
sharp
sharp
edge
edge
of each
of each
fanfan
blade
blade
hashas
a certain
a certain
curvature,
curvature,
reducing
reducing
both
both
thethe
vibration
vibration
andand
thethe
pressure
pressure
loss.
loss.
Streamlined
Streamlined
scroll
scroll
fanfan
Standard
Standard
Type
Type
Illustrated
Illustrated
fanfan
Space
Space
Saving
Saving
Type
Type
Installation
Installation
Space
Space
0.71
0.71
m2m2
6 HP
6 HP
Large
Large
airflow,
airflow,
high
high
static
static
pressure
pressure
and
and
quiet
quiet
technology
technology
HPHP
0303
Installation
Installation
Space
Space
0.95
0.95
m2m2
Sound
Sound
level(dB(A))
level(dB(A))
Improve
Improve
heat
heat
exchanger
exchanger
efficency,
efficency,
helps
helps
to to
reduced
reduced
operation
operation
sound.
sound.
Space
SpaceSaving
SavingType
Type
1212
HPHP
1212
HPHP
Comfort
Comfort
Lower
Loweroperation
operationsound
sound
Compact
Compact
Design
Design
930930
mmmm
765765
mmmm
1˜ 21dB(A)
reduction
reduction
than
than
˜ 2 dB(A)
conventional
conventional
model
model
Nighttime
Nighttime
quiet
quiet
operation
operation
function
function
Outdoor
Outdoor
PCB
PCB
automatically
automatically
memorises
memorises
thethe
time
time
when
when
thethe
peak
peak
outdoor
outdoor
temperature
temperature
appears.
appears.
It will
It will
enable
enable
, and
return
return
to to
normal
normal
quiet
quiet
operation
operation
mode
mode
after
after
8 h8*1h, *1and
mode
mode
after
after
it keeps
it keeps
forfor
9 h9*2h. *2.
*1 *1
8 h8ish the
is the
initial
initial
setting
setting
with
with
6 h6or
h 10
or 10
h also
h also
available.
available.
*2 *2
9 h9ish the
is the
initial
initial
setting
setting
with
with
8 h8or
h 10
or 10
h also
h also
available.
available.
Capacity
(%)
Capacity
(%)
Standard
StandardType
Type
Up
Uptoto
6060HPHP
*Cooling
*Cooling
operation
operation
conditions:
conditions:
Indoor
Indoor
temp.
temp.
of of
27ºCDB,
27ºCDB,
19ºCWB,
19ºCWB,
andand
outdoor
outdoor
temp.
temp.
of 35ºCDB.
of 35ºCDB.
*12*12
HPHP
of VRV
of VRV
IV improves
IV improves
more
more
compact
compact
design
design
andand
more
more
saving
saving
space
space
than
than
VRV
VRV
III III
6 HP
6 HP 8 HP
8 HP 1010
HPHP* 12
HPHP 1414
HPHP 1616
HPHP 1818
HPHP
* 12
Peak
Peak
in outdoor
in outdoor
temperature
temperature
100 100
Night
Night
mode
mode
50 50
Load
(%)
Load
(%)
20
20HP
HP
4.35
4.35
2.13
2.13
m2m2
555
555
kgkg
3.25
3.25
33
00
1.66
1.66
m2m2
490
490
kgkg
3.72 3.67
3.84
3.84 3.72
3.67 3.46
3.46
3.53.5
VRV
VRV
COP
COP
during
during
cooling
cooling
operation
operation 3.94
3.94
4.41
4.41 4.30
4.30
8 hrs
8 hrs
0 0
60 60
Operating
sound
(dB)
Operating
sound (dB)
Energy
Energy
Saving
Saving
Cooling
Cooling 4.5
4.5
Operation
Operation
44
COP
COP
Main Features
Main Features
High-COP
High-COPType
Type
57 57
50 50
40 40
8:008:00
Enable
Enable
night
night
mode
mode
12:00
12:00
16:00
16:00
20:00
20:00
9 hrs
9 hrs
VRV
VRV
IVIV
min.
min.
4040
dB(A)
dB(A)
0:000:00
4:004:00
8:008:00
Notes:
Notes:
· This
· This
function
function
is available
is available
in setting
in setting
at site.
at site.
· The
· The
operating
operating
sound
sound
in quiet
in quiet
operation
operation
mode
mode
is the
is the
actual
actual
value
value
measured
measured
by by
ourour
company.
company.
· The
· The
relationship
relationship
of outdoor
of outdoor
temperature
temperature
(load)
(load)
andand
time
time
shown
shown
above
above
is just
is just
an an
example.
example.
Hotline: 0976 173 173
0404
Excellent
Operation
Performance
Excellent
VRT-Variable
Operation
Refrigerant
Performance
Temperature
Enhanced
Lineup to 3 types
State-of-the-art
saving technology for VRV system
Enhanced
Lineupenergy
to 3 types
Higher
Coefficient
Performance
(COP)
Basic
mode
is selected toof
maintain
optimal comfort.
Higher
Coefficient
of
Performance
(COP)
VRT is selected to save energy and prevent excessive cooling or heating.
Cooling 4.5
4.41 4.30
Cooling
Operation
4.41 4.30
4.5
Capacity
priority
Operation
4
COP
4 Fixed Refrigerant
COP
3.5 Temperature
COP during cooling operation 3.94
COP during
coolingSpace
operation 3.94
Installation
1.66 m2
Refrigerant cycle
2
Installation
Space
1.66
490mkg
Product Weight
(During cooling)
490 kg
Product Weight
Standard Type
Standard Type
Increase
Condensing temperature lowered
Compressor workload reduced
Condenser
Indoor unit
heat exchanger
2.13
555mkg
(During heating)
555 kg
2
10%
Increase
10
%
Compressor
Evaporator
Condenser
Indoor unit
heat exchanger
Compressor
Offers higher capacity of up to 60 HP Evaporator
Offers
higher
capacity
up to 60
HP
6 HP-60
HP with
3 newofmodels
lineup
6 HP-60 HP with 3 new models lineup
Evaporating temperature raised
Compressor workload reduced
Up to
Up
60 to
HP
60 HP
VRV
VRV
Typical changes in evaporating temperature and COP
COP during
depending
on changing
load
cooling
operationindoor
3.94
3.94
14%
COP during cooling operation 3.94 2
3.94
Decrease
14%
1.42 m2
1.66 m
Installation Space
Decrease
1.42 m2
1.66 m2
Installation Space
22%
100%
Product Weight
490 kg
380 kg
Decrease
22%
Product Weight
490 kg
380 kg
Decrease
Required capacity changes
Capacity
as air conditioning load
changes
to match
changes according to
heat load
outdoor temperature.
Cooling load
& capacity
20 HP
20 HP
Space Saving Type
Space Saving Type
25%
New series with Temp.
compactIn&
lightweight
design
case
of fixed evaporating
New
series
with
compact
&
lightweight
design
18 HP-50 HP with 17 newtemperature,
models excessive
lineup cooling,
thermo on-off
loss, and other
18 HP-50 HP with 17 new models
lineup
25℃
30℃
Compact
Compact
Design
Design
High
VRT
20 HP
20 HP
Without VRT
20℃
25℃
Lineup
Lineup
35℃
Outdoor
VRV
VRV
inefficiencies occur.
Low
Refrigerant evaporating
temp. / Te(℃)
20℃
Automatic control to
3.11
COP
during
cooling operation 3.94
43%
adjust
temperature
3.11 2
COP during cooling operation 3.94 2
Decrease
43%
0.95 m
1.66 m
Installation Space
Decrease
35%
0.95 m2
1.66 m2
Installation Space
Automatic320
control
Product Weight
490 kg
kg adjusts
Decrease
35%
Product Weight
490 kgevaporating
320 temperature
kg
Decrease
to heat load change.
30℃
35℃
Outdoor
Temp.
High
Low
03
0305
New Lineup
New Lineup
Energy efficiency is
improved without
sacrificing comfort.
COP
HP
HP
High-COP Type
High-COP Type
Standard Type
Standard Type
Space Saving Type
Space Saving Type
Without VRT
Fixed Te/Tc - Standard control
(default setting on VRV IV)
25℃
30℃
35℃
Outdoor
Temp.
27ºCDB,
19ºCWB,
outdoor more
temp.compact
of 35ºCDB.
*12 HP
of VRV and
IV improves
*12 HP
of VRV
IV more
improves
more
compact
design
and
saving
space
than VRV III
High Sensible Mode
design and more saving space than VRV III
Floating target Te/Tc depending on heat load
Fixed target Te
Ease of installation
Ease of installation
Selecting VRT enables operation to be optimised for
Compact
& lightweight design
either energy
efficiency or rapid
cooling/heating.
Compact
& lightweight
design
Highly-integrated VRV Ⅳ
Highly-integrated
VRV Ⅳ
system offers compact
system
offers
compact
outdoor
units
to achieve
outdoor
unitsutilisation
to achieveof the
maximum
maximum
utilisation
installation space.of the
installation space.
Reaction speed
Comfort
Comfort
Very Fast
Installation
Installation
Space
Space
0.95 m2
0.95 m2
Product
Product
Weight
Weight
1,240 mm
930 mm
765
285
kg
765
mm
1,240 mm
mm
930 mm
285 kg
VRV
12 HPMode
12Mild
HP Mode
Quick
VRV
12 HP
12 HP
Reaction speed
Fast
Improve heat exchanger
30
Improve
heathelps
exchanger
efficency,
to reduced
efficency,
helps
to reduced
operation sound.
operation
Startsound.
of
Reaction speed
12 HP
12 HP
Installation
25%
Installation
Space
25Decrease
%
Space
2
0.71 m
Decrease
0.71Fixed
m2 Te
Product
32%
Product
Weight
32Decrease
%
Weight
195 kg
Decrease
195
kg Mode
Eco
765
mm
765
mm
Lower
sound
VRT offersoperation
quicker cool down
Lower
operation
sound
to shorten
uncomfortable
pull down time.
cooling
VRV
12 HP
VRV
12 HP
Floating Te/ Tc
Powerful Mode
Medium
Unable to change Te
Sound level(dB(A))
Sound level(dB(A))
• Can boost capacity above 100% if needed.
6 HP
8 HP
10 HP
12 HP
The refrigerant temperature can go lower in cooling (higher in heating)
6 HP
8 HP
10
HP (maximum
12 HP
than
the
set
minimum
in 60
heating).
Powerful
57
57
58
•57
Gives priority58
to very fast reaction
57mode
60 speed.
1˜ 2 dB(A) reduction than
The56
refrigerant temperature
goes down
fast to keep
55
57
59 (or up in1heating)
conventional
reductionmodel
than
˜ 2 dB(A)
the
room
setpoint
stable.
55
56
57
59
conventional model
Powerful
Quick
Mild
Large airflow, high static pressure and
Large
high static pressure and
quietairflow,
technology
Set temperature
quiet
technology
25
Quick
mode
• Gives priority to fast reaction speed.
Nighttime
quiet operation
The refrigerant temperature
goes down (orfunction
up in heating) fast to keep
Nighttime
quietstable.
operation function
the room setpoint
Outdoor PCB automatically memorises the time when
Outdoor
PCB
automatically
memorises
the time
peak
outdoor
temperature
appears.
It willwhen
enable
Without increasing operation sound, advanced
•the
Gives
priority
to efficiency.
Mild the peak
Time
*1 in heating)
outdoor
temperature
Itreturn
will
enable
The refrigerant
temperature
goes
downappears.
(orhup
gradually
giving
Without
increasing
operation
sound,toadvanced
Very utilised
Fast
quiet
operation
mode
after
8
,
and
to
normal
analytic
technologies
are
optimise
fan
mode
priority to the efficiency of the system instead
of the reaction speed.
Fast
*1
quiet
operation
analytic
are
utilised
to and
optimise
fan
mode
after itmode
keepsafter
for 98 hh*2., and return to normal
Medium
designtechnologies
and increase
airflow
rate
high
external
mode after it keeps for 9 h*2.
design
increase airflow rate and high external
staticand
pressure.
*1 8 h is the initial setting with 6 h or 10 h also available.
Streamlined air grille
static pressure.
h isinitial
the initial
setting
h or
also available.
*1 8 *2
h is9 the
setting
with 6with
h or8 10
h 10
alsoh available.
It promotes
discharge of
Streamlined
airthe
grille
swirling airflow,
furtherof
promotes
discharge
Recommended forItswirling
use
inthe
these
reducing
the
airflow,
further situations
pressure
reducing
the loss.
40
35
Av. max. temp.
Streamlined scroll fan
a certain
Thehas
sharp
edge ofcurvature,
each fan reducing
blade
the vibration
and
the pressure
hasboth
a certain
curvature,
reducing
bothloss.
the vibration and the pressure
loss.
Streamlined
scroll fan
Streamlined
scroll fan (Typical example)
25
20
15
Av. min. temp.
Mar.
Jun.
Sep.
Illustrated
fan when
VRT is particularly effective Illustrated
at night
fan
temperatures are low.
100
100
Av. daily temp.
difference
The
sharpscroll
edge fan
of each fan blade
Streamlined
30
0
20℃
0
pressure
loss.
Cooling only regions having
differences
in daily temperature.
Mo/C
Mo/C
VRT
3
6 HP
8 HP 10 HP * 12 HP 14 HP Mode
16 HP 18 HP
Basic
6 HP Mode
8 HP 10 HP * 12 HP 14Auto
HP 16 HP 18 HP
0
Outdoor Temp. (ºC)
During
cooling, the refrigerant evaporating
20 HP
20 HP (Te) is raised to minimise the
temperature
difference with the condensing temperature.
During heating, condensing temperature (Tc) is
lowered to minimise the difference to the
evaporating temperature. Compressors work less,
and this reduces power comsumption.
4.35
4.35
2.13 m2
3
Indoor Temp. (ºC)
VRV
VRV
3.5
Energy saving priority
3.84 3.72 3.67
Variable
Refrigerant Temperature
3.84 3.72 3.67
3.46
3.25
3.46
*Cooling operation conditions: Indoor temp. of
3.25
*Cooling
operation
conditions:
Indoor temp. of 35ºCDB.
27ºCDB,
19ºCWB,
and outdoor
Main Features
Main Features
Main Features
High-COP Type
The new VRV IV system now features VRT technology.
VRT automatically adjusts refrigerant
to individual
Enables
further energy saving
Energy temperature
Enables
further
energy
building and climate requirement,
thus further
improving
Energy
12 HP-50 HP with
4 newsaving
models lineup
Saving
annual energy efficiency and
maintaining
comfort.
12
HP-50
HP
with
4
new models lineup
Saving
With this excellent technology, running costs are reduced.
Operating Load Capacity
sound
(dB)
(%)
(%)
Outdoor
Temp. (ºC)
Operating Load Capacity
sound (dB)
(%)
(%)
Customise
your VRV
system for optimal annual efficiency
High-COP
Type
How is energy reduced?
Energy saving
Energy
saving
Fine control
to match user preference available through mode selection
Dec.
*2 9 h is the initial setting with 8 h or 10 h also available.
Peak in outdoor temperature
Night mode
Peak in outdoor temperature
Night mode
Cooling/heating regions having periods
of mild
outdoor temperatures.
50
50
40
35
0
60
30
57
25
50
Heating
period
Intermediate
period
0
60
57
Av.
50 max. temp.
40
20
8:00
40
158:00
Cooling period
9 hrs
8 hrs
9 hrs
8 hrs
Intermediate Heating
period
period
VRV IV
VRV
IVdB(A)
Enable night mode
min. 40
Enable night mode
min. 40 dB(A)
12:00
12:00
16:00
16:00
20:00
20:00
0:00
0:00
4:00
4:00
8:00
8:00
(Typical example)
Notes: · This function
available
Av.ismin.
temp. in setting at site.
· The
operating
soundininsetting
quiet operation
Notes:0 · This
function
is available
at site. mode is the actual value
Mar.
Jun.
Sep.
Dec.
by ourincompany.
· The measured
operating sound
quiet operation mode is the actual value
VRT ismeasured
particularly
during
the intermediate
periods.
· The relationship
of outdoor
temperature
(load) and time
shown
by oureffective
company.
is justofanoutdoor
example.
· The above
relationship
temperature (load) and time shown
above is just an example.
Hotline: 0976 173 173
04
0406
Excellent
Operation
Performance
More Flexible
SystemPerformance
Design
Excellent
Operation
Energy saving
Energy saving
Enhanced
Lineup
to 3 types location
More options
for to
installation
Enhanced
Lineup
3 types
Cooling
4.41
4.5 indoor
and residential
units 4.30
Cooling
Operation
4.41 4.30
4.5
Operation
4
COP
4
COP
Energy
Energy
Saving
Saving
For connection of only VRV
indoor units
Max. actual piping length
165 m
20 HP
20 HP
Max. equivalent piping length
Enables further energy saving
Multiple use
Enables
energy
12 HP-50further
HP with
4 newsaving
models lineup
12 HP-50 HP with 4 new models lineup
q
COP during cooling operation 3.94
COP during
coolingSpace
operation 3.94
Installation
1.66 m2
2
Installation
Space
1.66
490mkg
Product Weight
490 kg
Product Weight
190 m
Max. level difference
between the outdoor units
and the indoor units
Max. level difference
between the indoor units
20 HP
20 HP
Up to
Up
60 to
HP
60 HP
90 m
2
30 m
Max.
90 m
2
First
Increase
2
2.13
555mkg
555 kg
indoor branch
f
a
p
b
*The rest of indoor units are
the same as for single use.
a
e
i
VRV
VRV
COP during cooling operation 3.94
3.94
14% Max.
COP during cooling operation 3.94 2
3.94
Decrease
14% s 30 m
2
1.42
m
1.66
m
Installation
Space
15 m higher
Decrease
1.42 m2
1.66 m2
Installation Space
22%
than VRV
Product Weight
490 kg
380 kg
Decrease
% such as a .
Colours in the diagram above are merely for identifying pipes referenced with22
symbols
Product Weight
490 kg
380 kg
Decrease
Actual
piping length
Example
Equivalent
piping length
Refrigerant piping length
165 m
a+f+g+h+i
190 m
Total piping length
1000 m
a+b+c+d+e+f+g+h+i
—
Between the first indoor branch and the farthest indoor unit
90 m*1
f+g+h+i
Space Saving Type
Space Saving Type
Maximum
allowable
piping length
4.35
4.35
2.13 m2
g to 60h HP
f of up
Offers higher capacity
Offers
higher
capacity
of
up
to 60
HP
6 HP-60 First
HPindoor
with
3 new
lineup
b models
d
c
branch
6 HP-60 HP with 3 new models lineup
r
10%
Increase
10
%
First outdoor branch
Single use
Standard Type
Standard
Max.
total piping length Type
1000 m
k
VRV
VRV
—
New series with compact & lightweight design
New
seriesHP
with
compact
lightweight
design
Compact
Level
18 HP-50
with
17
new&models
lineup
Example
Difference
Compact
18
HP-50
HP
with
17
new
models
lineup
Design
Between the outdoor units (Multiple use)
5m
q
Between the outdoor branch and the last outdoor unit
Maximum
allowable
level difference
Design
10 m
k+p
VRV
VRV
30 m
Between the indoor units
13 m
s
90 m
r
3.11
COP during cooling operation
3.94
43%
r3.11
90 m 3.94
operation
Decrease
43%
2
0.95 m2
1.66 m
Installation Space
Decrease
1. No special requirements up to 40 m. The maximum actual piping length can beInstallation
90 m, dependingSpace
on conditions. Various
conditions
0.95 m2have to be met35%
1.66
m2 and requirements
to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data Book
for details
of these conditions and
requirements.
Product
Weight
490
kg
320 kg
Decrease
35%
2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased and connection ratio must be 80% to 130%. If the outdoor unit
Product Weight
490 kg
320 kg
Decrease
is above the indoor unit, a dedicated setting on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more information.
Between the outdoor units
and the indoor units
If the outdoor unit is above.
2
If the outdoor
is below.cooling
COPunit
during
20 HP
20 HP
Connection ratio
Lineup
Connection capacity at maximum is 200%.
Lineup
Connection ratio
HP
HP
50%–200%
High-COP Type
High-COP Type
Standard
ConnectionType
ratio =
Standard
Type
Total capacity index of the indoor units
Space Saving Type
Capacity
Space Saving
Typeindex of the outdoor units
03
0307
Conditions of VRV indoor unit connection capacity
Applicable
VRV indoor units
Single outdoor units
Double outdoor units
Triple outdoor units
Mo/C
Mo/C
FXDQ, FXMQ-P, FXAQ models
200%
Other VRV indoor
New unit
Lineup
models*1
New Lineup
3.5
3.5
3
3
0
0
3.46
3.46
b
Colours in the diagram below are merely for identifying
pipes referenced with symbols such as a .
3.25
3.25
a
6 HP
8 HP 10 HP * 12 HP 14 HP e 16 HP 18 HPf
branch
6 HP
8 HP 10 HP * 12First
HPindoor14
HP BP
16 HP 18 HP
VRV : VRV indoor unit
RA : Residential indoor unit
BP : BP unit
Max.
50 m
Ease of installation
Ease of installation
h
n
Compact & lightweight design Max.
Compact & lightweight design l 15 m
i
RA
Maximum allowable
piping length
Comfort
Comfort
1,240
mm
Total piping
length
VRV
VRV
Between BP unit
and indoor unit
765
mm
930 mm
*12 HP
of VRV
IVg
improves
more
compact
design
and
more
saving
space
than VRV III
Max.
design and more saving space than VRV
o III
m
Max.
Installation
Installation
Space
Space
0.95 m2
0.95 m2
765
mm
765
mm
Product
Actual
piping
length
Product
Weight
Weight
100 m
285
kg
250 m
285 kg
2 m–12 m
If indoor unit capacity index is 71.
2 m–8 m
Minimum allowable piping length Between outdoor unit and the first indoor branch
Lower
operation sound
Lower operation sound
6 HP
6 HP
57
57
55
55
8 HP
8 HP
57
57
56
56
If the outdoor unit is above.
k
12 HP
VRV
12 HP
Installation
25%
Installation
Space
RA
25Decrease
%
Space
2
0.71 m
Decrease
0.71 m2
h, i, j, k
b+c+g, b+c+d
50 m*1
5m
Sound
level(dB(A))
Sound level(dB(A))
10 HP
12 HP
10 HP
12 HP
Level Difference
58
60
15 m 60
58
5715 m
59
57
59
If the outdoor unit is below.
40
m
Product
Example
32%
Product
Weight
32Decrease
%
Weight
a+b+c+g+k, a+b+c+d
195 kg
Decrease
195a+b+c+d+e+f+g+h+i+j+k
kg
2 m–15 m
If indoor unit capacity index is 60.
15 m
BP
VRV
12 HP
VRV
12 HP RA
Between the first indoor branch and the farthest BP unit or
between the first indoor branch and the farthest VRV indoor unit
and the indoor unit
*Cooling operation conditions: Indoor temp. of
*Cooling
operation
conditions:
Indoor temp. of 35ºCDB.
27ºCDB,
19ºCWB,
and outdoor
d
27ºCDB,
19ºCWB,
outdoor more
temp.compact
of 35ºCDB.
*12 HP
of VRV and
IV improves
VRV
12 HP
12 HP
12 HP If indoor unit capacity index
12 HP
< 60.
Improve heat exchanger
Improve
heathelps
exchanger
Between the indoor units
efficency,
to reduced
efficency,
helps
to
reduced
Between BP units
operation sound.
Maximum allowable
operation
sound.
Between the outdoor unit
level difference
c
j
RA
Highly-integrated VRV Ⅳ
Highly-integrated
VRV Ⅳ
system offers compact
system
offers
compact
outdoor
units
to achieve
outdoor
unitsutilisation
to achieveof the
maximum
When a mixed
combination of VRV and residential indoor units is connected
maximum
utilisation
of the
installation
or when onlyspace.
residential indoor units are connected
765
installation space.
1,240
mm
mm
Refrigerant piping
length
930 mm
50 m
40 m
a
Example
l
1˜ 2 dB(A)
reduction than
conventional
1˜ 2 dB(A)
than
mreductionmodel
conventional
model
n
n
Large airflow, high static
pressure and
Nighttime quiet operation function o
Between the outdoor unit and the BP unit
40 m
Large
high static
pressure and
Nighttime quiet operation
function
quietairflow,
technology
Outdoor
PCB
automatically
memorises
time when
*1.
When
the
piping
length
exceeds
20
m,
the
size
of
the
main
pipes
(the
gas
side
and
the
liquid
side)
must
be increased.
Please refer tothe
Engineering
quiet technology
Outdoor PCB automatically memorises the time when
Data Book
for details. operation sound, advanced
the peak outdoor temperature appears. It will enable
Without
increasing
thequiet
peakoperation
outdoor temperature
appears.
Itreturn
will enable
Without
increasing
operation
sound,toadvanced
mode after connected,
8 h*1, and
to normal
analytic
technologies
are
utilised
optimise
fan
*When a mixed combination of VRV and residential indoor units is connected or when only residential indoor units are *1
connection ratio
*2 , and return to normal
quiet
operation
mode
after
8
h
analytic
technologies
are
utilised
to
optimise
fan
mode Refer
aftertoitpage
keeps
9 h unit
. combination details.
design
increase
airflow
rate
andandhigh
must beand
50% to
130% for cooling
only
models
80% external
to 130% for heat pump models.
68 forfor
outdoor
mode after it keeps for 9 h*2.
design
increase airflow rate and high external
staticand
pressure.
*1 8 h is the initial setting with 6 h or 10 h also available.
Streamlined air grille
static pressure.
h isinitial
the initial
setting
h or
also available.
*1 8 *2
h is9 the
setting
with 6with
h or8 10
h 10
alsoh available.
Itpressure
promotes
discharge of
Streamlined
airthe
grille
High external static
swirling airflow,
furtherof
It promotes
the discharge
reducing
thefurther
swirling
airflow,
VRV IV outdoor unit has been
achieved
high
pressure
reducing
the loss.
external static pressure up pressure
to 78.4 loss.
Pa,
100
*2 9 h is the initial setting with 8 h or 10 h also available.
Peak in outdoor temperature
Night mode
Peak in outdoor temperature
Night mode
78.4 Pa
100
ensuring the efficient heat dissipation and
50
More options
50 in the
stable operation of equipmentStreamlined
in either scroll fan
The sharpscroll
edge fan
of each fan blade opening/angle of louvre
Streamlined
hierarchical or intensive arrangement.
0
200%
160%
130%
*1 For the FXFQ25LU,FXFQ-S and FXVQ models, maximum connection ratio is 130% for the
entire range of outdoor units.
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is
enforced in all the indoor units.
*Refer to page 67-68 for outdoor unit combination details.
3.84 3.72 3.67
3.84 3.72 3.67
Operating Load Capacity
sound (dB)
(%)
(%)
Operating Load Capacity
sound (dB)
(%)
(%)
High-COP Type
The long piping length provides more design flexibility, which can match even large-sized buildings.
Main Features
Main Features
Main Features
Higher Coefficient of Performance (COP)
Higher
Coefficient of Performance (COP)
For mixed combination of VRV
Long
piping length
High-COP
Type
8 hrs
9 hrs
Outstanding heat
dissipation
a certain
Thehas
sharp
edge ofcurvature,
each fan reducing
blade
60
9 hrs
8 hrs
0
57
the vibration
and
the pressure effect in both
hasboth
a certain
curvature,
reducing
60 hierarchical and
VRV IV
57
intensive arrangement
50
bothloss.
the vibration and the pressure
VRV
IVdB(A)
Enable night mode
min. 40
50
loss.
40
Enable night mode
Streamlined
min. 40 dB(A)
8:00
8:00
12:00
16:00
20:00
0:00
4:00
40
scroll fan
Streamlined
8:00
8:00
12:00
16:00
20:00
0:00
4:00
scroll fan
Notes: · This function is available in setting at site.
· The
operating
soundininsetting
quiet operation
Notes: · This
function
is available
at site. mode is the actual value
Illustrated
by ourincompany.
· The measured
operating sound
quiet operation mode is the actual value
fan
Illustrated
· The relationship
of outdoor temperature (load) and time shown
measured
by our company.
fan
is justofanoutdoor
example.
· The above
relationship
temperature (load) and time shown
above is just an example.
Hotline: 0976 173 173
04
0408
Excellent
Operation
Performance
Reliable and
Stable Performance
System
Excellent
Operation
Enhanced
Lineup
to 3 types
Multiple advanced
features
more accurate test operation and stable system
Enhanced
Lineup
toensuring
3 types
High-COP Type
Cooling 4.5
4.41 4.30
Cooling
Operation
4.41
4.5
During
start-up,
Daikin4.30
VRV IV unit sequencing operation will be automatically enabled to
Operation
4
COP
3.72
3.84
ensure balanced
operation of each
outdoor
unit to3.67
improve longevity of equipment and stable
4
COP
Daikin VRV IV system incorporates a simplified and efficient test operation function, not only greatly
Enablesimproving
further energy
saving
accelerating the installationEnergy
process, but effectively
the field setting
quality as well.
Enables
energy
12 HP-50further
HP with
4 newsaving
models lineup
12 HP-50 HP with 4 new models lineup
Automatically checks the wirings between
outdoor units and indoor units to confirm
whether there is a defective wiring.
Confirms
20
HP and corrects the actual piping
length.
20
HP
VRV
VRV
Wiring
check
4.35
4.35
2.13 m2
COP during cooling operation 3.94
COP during
coolingSpace
operation 3.94
Installation
1.66 m2
2
Installation
Space
1.66
490mkg
Product Weight
490 kg
Product Weight
2.13
555mkg
2
Piping
555 kg
check
Automatically check whether the stop
valve in each outdoor unit is in normal
status to ensure the smooth operation of
air conditioning system.
Standard Type
Standard Type
10%
Increase
10
%
Increase
Stop valve
check
VRV
VRV
COP during cooling operation 3.94
COP during cooling operation 3.94 2
1.66 m
Installation Space
1.66 m2
Installation Space
Product Weight
490 kg
Product Weight
490 kg
3.94
3.94
1.42 m2
Simplified commissioning and after-sales service
20 HP
20
HP of information display
Function
by luminous digital tube
1.42 m2
380 kg
380 kg
7-segment digital display
14%
Decrease
14%
Decrease
22%
Decrease
22%
Decrease
Figures out
system
operation
luminous digital tubes to display system
Displays
information by
system
reading light
operation information, enabling the
emitting state
operational state to be visually displayed Newoperation
series
with
compact
&
lightweight
design
information
of different
New
series
with
compact
&
lightweight
design
Compact
whilst facilitating simplified
directly HP with 17 new models
18 HP-50
lineup
diodes, which
Compact
Design service. 18 HP-50 HP with 17 new models
commissioning and after-sales
is both lineup
Design
inefficient and
fallible.
Space Saving Type
Space Saving Type
VRV configurator
20 HP
20 HP
3.11
3.11 2
The VRV configurator is an advanced software solution
that allows for easy system configuration and
commissioning.
Lineup
Lineup
less time is required on the roof configuring the outdoor
unit. HP
HP
High-COP Type
multiple
systems at different sites can be managed in
High-COP Type
exactly the
Standard
Typesame way, thus offering simplified
Standard
Type
commissioning
for key accounts.
Space Saving Type
Space Saving Type
0.95 m
0.95 m2
320 kg
320 kg
Simplified
commissioning
Mo/C
Mo/C
Retrieve initial
system settings
3.25
3.25
6 HP
8 HP 10 HP * 12 HP 14 HP 16 HP 18 HP
6 HP
8 HP 10 HP * 12 HP 14 HP 16 HP 18 HP
Ease of installation
Ease
Priority:of installation
operation.
*Cooling3operation conditions: Indoor temp. of
Stage
*Cooling
operation
conditions:
Indoor temp. of 35ºCDB.
27ºCDB,
19ºCWB,
and outdoor
27ºCDB,
19ºCWB,
outdoor more
temp.compact
of 35ºCDB.
*12 HP
of VRV and
IV improves
*12 HP
of VRV
IV more
improves
more
compact
design
and
saving
space
than VRV III
design and more saving space than VRV III
Automatic
sequencing
Automatic
sequencing
Priority:
Priority:
VRV
12 HP
VRV
12 HP
Installation
Installation
Space
Space
0.95 m2
0.95 m2
43%
Decrease
43%
Decrease
35%
Decrease
35%
Decrease
1,240 mm
1,240 mm
765
mm
765
mm
930 mm
930 mm
VRV
12 HP
VRV
12 HP
Double backup operation functions
12 HP
12 HP
Installation
25%
Installation
Space
25Decrease
%
Space
2
0.71 m
Decrease
0.71 m2
Product
Product
Weight
Weight
285 kg
285 kg
Product
Product
Weight
Weight
195 kg
195 kg
32%
765
mm
12 HP
12 HP
even
if failure
occurs insound
a set of air conditioning equipment.
Sound level(dB(A))
Lower
operation
Sound level(dB(A))
Lower
operation
sound
In the event
of a failure,
emergency operation can6 HP
be conveniently
enabled
the remaining system
8 HP
10 HP to allow
12 HP
to
operate
in aexchanger
limited fashion.
Improve
heat
Improve
heathelps
exchanger
efficency,
to reduced
efficency,
helps
to reduced
operation
sound.
operation sound.
6 HP
57
57
55
55
8 HP
57
57
56
56
10 HP
58
58
57
57
12 HP
60
60
59
59
1˜ 2 dB(A) reduction than
conventional
1˜ 2 dB(A)
reductionmodel
than
conventional model
Unit backup operation function
Large airflow, high static pressure and
Nighttime quiet operation function
If malfunction
in an outdoor
Large
airflow,
high occurs
static pressure
and unit...
Nighttime quiet operation function
quiet
technology
Outdoor PCB automatically memorises the time when
operation can be conveniently set and enabledOutdoor PCB automatically memorises the time when
quietEmergency
technology
the peak outdoor temperature appears. It will enable
Without increasing operation sound, advanced
by
the
remote
controller
for
indooradvanced
unit (for systems
thequiet
peakoperation
outdoor temperature
will enable
Without
increasing
operation
sound,
mode after appears.
8 h*1, andItreturn
to normal
analytic
technologies
are utilised
to optimise fan
composed
of two are
or more
outdoor
units ).fan
quiet operation mode after 8 h*2*1, and return to normal
analytic
technologies
utilised
to optimise
design and increase airflow rate and high external
design
increase airflow rate and high external
staticand
pressure.
Streamlined air grille
static pressure.
It promotes
discharge of
Streamlined
airthe
grille
swirling airflow,
furtherof
It promotes
the discharge
reducing
thefurther
swirling
airflow,
pressure
reducing
the loss.
pressure loss.
Compressor backup operation
function
Streamlined scroll
fan
New Lineup
New Lineup
765
mm
Comfort
Daikin VRV IV system boasts double backup operation functions, which can secure the use of air
Comfort
conditioners in this area to the greatest extent by emergently enabling double backup operation functions
The sharpscroll
edge fan
of each fan blade
Streamlined
If malfunction occurs
in
compressor...
aacertain
Thehas
sharp
edge ofcurvature,
each fan reducing
blade
both
the vibration
and
the
pressure
a certain
curvature,
reducing
Emergency operationhascan
be
easily
set
and
bothloss.
the vibration and the pressure
enabled by the outdoor
loss.unit (for a single
Streamlined
outdoor unit system RX(Y)Q14-20TY1
models).
scroll fan
Streamlined
scroll fan
Illustrated
fan
Illustrated
fan
Initial settings on the outdoor unit can be easily retrieved.
03
0309
3.46
3.46
32Decrease
%
Double backup operation functions responding resiliently to various unexpected situations
Decrease
VRV IV system utilises 7-segment
COP during cooling operation 3.94
COP during cooling operation 3.94 2
1.66 m
Installation Space
1.66 m2
Installation Space
Product Weight
490 kg
Product Weight
490 kg
Stage 2
Highly-integrated VRV Ⅳ
Highly-integrated
VRV Ⅳ
system offers compact
system
offers
compact
outdoor
units
to achieve
outdoor
unitsutilisation
to achieveof the
maximum
maximum
utilisation
installation space.of the
installation space.
Conventional LED display
VRV
VRV
3.67
Compact & lightweight design
Compact & lightweight design
Offers higher capacity of up to 60 HP
Offers
higher
capacity
up to 60
HP
6 HP-60
HP with
3 newofmodels
lineup
6 HP-60 HP with 3 new models lineup
Up to
Up
60 to
HP
60 HP
3.72
3.84
mode after it keeps for 9 h .
mode after it keeps for 9 h*2.
Operating Load Capacity
sound (dB)
(%)
(%)
Operating Load Capacity
sound (dB)
(%)
(%)
Automatic check
3.5
3.5
Stage 1 3
3
0
0
Main Features
Main Features
Main Features
Higher Coefficient of Performance (COP)
Higher
Coefficient
of Performance
Automatic
sequencing
operation (COP)
Efficient
automatic
test operation
High-COP
Type
Energy
Saving
Saving
Energy saving
Energy saving
Outdoor
unit sequencing technology
100
100
*1 8 h is the initial setting with 6 h or 10 h also available.
h isinitial
the initial
setting
h or
also available.
*1 8 *2
h is9 the
setting
with 6with
h or8 10
h 10
alsoh available.
*2 9 h is the initial setting with 8 h or 10 h also available.
Peak in outdoor temperature
Night mode
Peak in outdoor temperature
Night mode
50
50
0
60
57
50
40
8 hrs
8 hrs
0
60
57
50
40
8:00
8:00
9 hrs
9 hrs
VRV IV
VRV
IVdB(A)
Enable night mode
min. 40
Enable night mode
min. 40 dB(A)
12:00
12:00
16:00
16:00
20:00
20:00
0:00
0:00
4:00
4:00
8:00
8:00
Notes: · This function is available in setting at site.
· The
operating
soundininsetting
quiet operation
Notes: · This
function
is available
at site. mode is the actual value
by ourincompany.
· The measured
operating sound
quiet operation mode is the actual value
· The relationship
of outdoor temperature (load) and time shown
measured
by our company.
is justofanoutdoor
example.
· The above
relationship
temperature (load) and time shown
above is just an example.
Hotline: 0976 173 173
04
0410
Enhanced
Lineup
to 3 types compressor in compact casing
Large
capacity
all DC
Enhanced
Lineup
to 3inverter
types
Cooling 4.5
4.41 4.30
Cooling
Operation
4.41technology
SMT4.5
packaging
4.30 adopted by the
Operation
4
COP
whole computer
control panel improves
the
3.84 3.72
4
COP
Enables further energy saving
Enables
energy
12 HP-50further
HP with
4 newsaving
models lineup
12 HP-50 HP with 4 new models
lineup
Small type
high efficiency
concentrated winding motor
VRV
VRV
winding
COP during cooling operation Distributed
% motor
3.94 winding motor
4.35 Concentrated10
(New 12 HP
compressor)
(Current 8 HP compressor)
Increase
COP during
cooling
operation
10
%
3.94
4.35
2
2
Installation Space
1.66 m
2.13 m
Increase
2
2
Installation
Space
1.66
2.13
490mkg
555mkg
Product Weight
490 kg
555 kg
Product Weight
20 HP
20 HP
Coil
end
Standard Type
Standard Type
Offers higher capacity of
up to 60
HP
Small
coilHP
end using concentrated
Offers
higher
capacity
upsizing
to 60
6 HP-60
HP with
3 newofwinding,
models
lineup
reduce copper loss
6 HP-60 HP with 3 new models
lineup
(winding resistance).
Up to
Up
60 to
HP
60 HP
VRV
VRV
Improve motor efficiency in low rpm
COP during cooling operation range
3.94(improve intermediate
3.94
14%
COP during cooling operation 3.94
3.94
Decrease
efficiency).
14%
1.42 m2
1.66 m2
Installation Space
Decrease
1.42 m2
1.66 m2
Installation Space
22%
Product Weight
490 kg
380 kg
Decrease
22%
Product Weight
490 kg
380 kg
Decrease
As a result of having thinned a wall -
20
HP of the scroll, compression
thickness
20
HP volume increase 50%
chamber
Space Saving Type
Space Saving Type
Highly integrated heat New
exchanger
series with compact & lightweight design
New
seriesHP
with
compact
lightweight
design
Compact
18 HP-50
with
17 new&models
lineup
Compact
18 HP-50 HP with 17 new models lineup
Design
Improve performanceDesign
by increasing heat exchanger area while maintaining
VRVthe same installation space.
VRV
Realise
highlyoperation
integrated heat
performance
COP during
cooling
3.94exchanger 3.11
43%
(increase
row,
reduce fin3.94
pitch) by
reducing
of airflow Decrease
3.11
COP during
cooling
operation
43%
0.95 m2
1.66 m2
Installation
Space
resistance which changes cooling
tube to Ø7.2
Decrease
35%
0.95 m
1.66 m2
Installation Space
Product Weight
490 kg
320 kg
Decrease
35%
Product Weight
490 kg
320 kg
Decrease
VRV
20 HP
20 HP
Lineup
Lineup
HP
HP
High-COP Type
High-COP Type
Standard Type
Standard Type
Space SavingFine
TypeLouvre Fin
Space Saving Type
03
0311
Mo/C
Mo/C
New Lineup
New Lineup
20 HP
3 row with small pipe design,
increases heat transfer efficiency
Waffle Fin
Change fin shape from fine louvre to waffle fin.
Fin pitch can be reduced fin pitch from 2.0 mm to 1.4 mm, to realise unit
efficiency which increased heat exchanger area.
10 HP
16 HP
Heat exchanger Contribution of COP
area
(cooling)
13%UP
24%UP
105.5%
111.5%
Computer control board surface
adopting SMT packaging
technology
Ease of installation
Ease of installation
Highly-integrated VRV Ⅳ
Highly-integrated
VRV Ⅳ
system offers compact
system
offers
compact
outdoor
units
to achieve
outdoor
unitsutilisation
to achieve
Refrigerant
cooling
maximum
of the technology,
maximum
utilisation
installation space.of the
installation space.
1,240 mm
*Cooling operation conditions: Indoor temp. of
*Cooling
operation
conditions:
Indoor temp. of 35ºCDB.
27ºCDB,
19ºCWB,
and outdoor
27ºCDB,
19ºCWB,
outdoor more
temp.compact
of 35ºCDB.
*12 HP
of VRV and
IV improves
*12 HP
of VRV
IV more
improves
more
compact
design
and
saving
space
than VRV III
design and more saving space than VRV III
SMT
packaging
material
Computer control board
Compact & lightweight design
Compact & lightweight design
Conventional
computer control
board surface
3.67
3.84 3.72 3.67
3.46
anti-clutter
3.5 performance.
3.25
3.46
3.5
3.25
Protects3your computer boards from the
3
adverse 0effect of sandy and humid weather.
0
6 HP
8 HP 10 HP * 12 HP 14 HP 16 HP 18 HP
6 HP
8 HP 10 HP * 12 HP 14 HP 16 HP 18 HP
VRV
12 HP
*SMT: Surface mounted
technology
VRV
12 HP
Installation
Installation
Space
Space
0.95 m2
0.95 m2
12 HP
12 HP
Installation
25%
Installation
Space
25Decrease
%
Space
2
0.71 m
Decrease
0.71 m2
ensures stability of PCB temperature
765
mm
765
mm
765
765
Improved inner design1,240
tomm
increase
smooth airflow
mm
mm
930 mm
930 mm
VRV
12 HP
VRV
12 HP
12 HP
12 HP
Downsize electric component, re-locate to dead
space of bell mouth side to decrease airflow resistance.
Product
Product
Weight
Weight
285 kg
285 kg
Product
Product
Weight
Weight
195 kg
195 kg
32%
32Decrease
%
Decrease
Bell mouth
Comfort
Comfort
Lower operation sound
Lower operation sound
Improve heat exchanger
Improve
heathelps
exchanger
efficency,
to reduced
efficency,
helps
to reduced
operation sound.
operation sound.
6 HP
6 HP
57
57
55
55
VRV
Large airflow, high static pressure and
Large
high static pressure and
quietairflow,
technology
quiet technology
8 HP
8 HP
57
57
56
56
Sound level(dB(A))
Electric Component Space
Sound level(dB(A))
10 HP
10 HP
58
58
57
57
12 HP
12 HP
60
60
59
59
1˜ 2 dB(A) reduction than
conventional
1˜ 2 dB(A)
reductionmodel
than
conventional model
Nighttime quiet operation function
Nighttime quiet operation function
Without increasing operation sound, advanced
Without
increasing
operation
sound,toadvanced
analytic
technologies
are utilised
optimise fan
analytic
are
utilised
to and
optimise
fan
designtechnologies
and increase
airflow
rate
high external
design
and
increase
airflow
rate
and
high
external
static pressure.
Streamlined air grille
static pressure.
It promotes
discharge of
Streamlined
airthe
grille
swirling airflow,
furtherof
It promotes
the discharge
reducing
thefurther
swirling
airflow,
pressure
reducing
the loss.
pressure loss.
Streamlined scroll fan
Roof terrace temperature Streamlined
in summer
isscroll
over fan
40each
C, seriously
The sharp
edge
of
fan blade
affecting inverter coolingThe
efficiency,
resulting
infan
decline
has
a certain
reducing
sharp
edge
ofcurvature,
each
bladeof
inverter operating speed.
device
parts
response
both
the
vibration
and
the pressure
hasFinally
a certain
curvature,
reducing
both
the vibration and the pressure
speed
isloss.
reduced.
loss.
Streamlined
scroll fan
Streamlined
fan ambient temperature
Improve reliability atscroll
high
Outdoor PCB automatically memorises the time when
Outdoor
PCBoutdoor
automatically
memorises
the time
the peak
temperature
appears.
It willwhen
enable
thequiet
peakoperation
outdoor temperature
will enable
mode after appears.
8 h*1, andItreturn
to normal
*1
quiet
operation
mode
after itmode
keepsafter
for 98 hh*2., and return to normal
mode after it keeps for 9 h*2.
Operating Load Capacity
sound (dB)
(%)
(%)
Operating Load Capacity
sound (dB)
(%)
(%)
Gives 2.4 times tensile strength compare
to conventional material
New Material: 600 MPa
Conventional Material : 250 MPa
Increase compression chamber volume
by using thin spiral design.
Energy saving
Energy
Varioussaving
advanced control main PC board
Higher Coefficient of Performance (COP)
Higher
Coefficient
of Performance (COP)
SMT* packaging
technology
High-COP Type
High-COP Type
Large capacity inverter compressor using high tension strength material,
realise 12 HP compressor using 8 HP casing.
Energy
Energy
Saving
Development of high Saving
strength material
Excellent Performance
Main Features
Main Features
Main Features
Excellent
Operation
Performance
Advanced
Technologies
Achieve
Excellent
Operation
Performance
100
100
*1 8 h is the initial setting with 6 h or 10 h also available.
h isinitial
the initial
setting
h or
also available.
*1 8 *2
h is9 the
setting
with 6with
h or8 10
h 10
alsoh available.
*2 9 h is the initial setting with 8 h or 10 h also available.
Peak in outdoor temperature
Night mode
Peak in outdoor temperature
Night mode
50
50
0
60
57
50
40
9 hrs
8 hrs
Control board failure
ratio at stable
operation
9 hrs
8 hrs
is reduced.
0
60
57
50
40
8:00
8:00
VRV IV
VRV
IVdB(A)
Enable night mode
min. 40
Enable night mode
min. 40 dB(A)
12:00
12:00
16:00
16:00
20:00
20:00
0:00
0:00
4:00
4:00
Notes: · This function is available in setting at site.
8:00
8:00
· The
operating
soundininsetting
quiet operation
Notes: · This
function
is available
at site. mode is the actual value
It is possible to cool theIllustrated
inverter power module stability
even
at
high
ambient
temperature.
by ourincompany.
· The measured
operating sound
quiet operation mode is the actual value
fan
Illustrated
This helps to keep air-conditioning
capacity and also reduces
failure
ratio.
· The
relationship
of outdoor temperature (load) and time shown
measured
by our
company.
fan
is justofanoutdoor
example.
· The above
relationship
temperature (load) and time shown
above is just an example.
Hotline: 0976 173 173
04
0412
Outdoor
Outdoor Unit
Unit Lineup
Lineup
Outdoor
OutdoorUnits
Units
Cooling
CoolingOnly
Only/ Heat
/ HeatPump
Pump
Lineup
Lineup
VRV
VRV
IV IV
outdoor
outdoor
unit
unit
offers
offers
a higher
a higher
capacity
capacity
of of
upup
to to
6060
HP,
HP,
responding
responding
to to
thethe
needs
needs
of of
large-sized
large-sized
building.
building.
The
The
single
single
outdoor
outdoor
unit
unit
has
has
only
only
2 different
2 different
shapes
shapes
and
and
dimensions,
dimensions,
notnot
only
only
simplifying
simplifying
thethe
design
design
process,
process,
butbut
also
also
bringing
bringing
thethe
system
system
flexibility
flexibility
to to
a new
a new
level.
level.
With
With
thethe
outdoor
outdoor
unit
unit
capacity
capacity
increased
increased
in in
increment
increment
of of
2 HP,
2 HP,
customers'
customers'
needs
needs
can
can
bebe
precisely
precisely
met.
met.
Outdoor
Outdoor
units
units
with
with
anti-corrosion
anti-corrosion
specifications
specifications
(-E(-E
type
type
onon
request)
request)
areare
designed
designed
specifically
specifically
forfor
use
use
in in
areas
areas
which
which
areare
subject
subject
to to
salt
salt
damage
damage
and
and
atmospheric
atmospheric
pollution.
pollution.
High-COP
High-COPType
Type
Triple
TripleOutdoor
OutdoorUnits
Units
Double
DoubleOutdoor
OutdoorUnits
Units
12,12,
14,14,
1616
HPHP
RX(Y)Q26THY1(E)
RX(Y)Q18THY1(E)
RX(Y)Q18THY1(E)RX(Y)Q26THY1(E)
RX(Y)Q28THY1(E)
RX(Y)Q20THY1(E)
RX(Y)Q20THY1(E)RX(Y)Q28THY1(E)
RX(Y)Q30THY1(E)
RX(Y)Q22THY1(E)
RX(Y)Q22THY1(E)RX(Y)Q30THY1(E)
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
RX(Y)Q24THY1(E)RX(Y)Q32THY1(E)
RX(Y)Q12THY1(E)
RX(Y)Q12THY1(E)
RX(Y)Q14THY1(E)
RX(Y)Q14THY1(E)
RX(Y)Q16THY1(E)
RX(Y)Q16THY1(E)
Standard
StandardType
Type
6, 6,
8, 8,
10,10,
1212
HPHP
RX(Y)Q6TY1(E)
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
RX(Y)Q12TY1(E)
14,14,
1616
HPHP
RX(Y)Q14TY1(E)
RX(Y)Q14TY1(E)
RX(Y)Q16TY1(E)
RX(Y)Q16TY1(E)
Space
SpaceSaving
SavingType
Type
Single
SingleOutdoor
OutdoorUnits
Units
18,18,
2020
HPHP
RX(Y)Q18TY1(E)
RX(Y)Q18TY1(E)
RX(Y)Q20TY1(E)
RX(Y)Q20TY1(E)
1313
18,18,
2020
HPHP
RX(Y)Q18TNY1(E)
RX(Y)Q18TNY1(E)
RX(Y)Q20TNY1(E)
RX(Y)Q20TNY1(E)
22,22,
24,24,
2626
HPHP
RX(Y)Q22TNY1(E)
RX(Y)Q22TNY1(E)
RX(Y)Q24TNY1(E)
RX(Y)Q24TNY1(E)
RX(Y)Q26TNY1(E)
RX(Y)Q26TNY1(E)
28,28,
30,30,
3232
HPHP
RX(Y)Q22TSY1(E)
RX(Y)Q22TSY1(E)
RX(Y)Q24TSY1(E)
RX(Y)Q24TSY1(E)
Space
Space
Saving
Saving
Type
Type
34,34,
3636
HPHP
RX(Y)Q28TNY1(E)
RX(Y)Q28TNY1(E)
RX(Y)Q30TNY1(E)
RX(Y)Q30TNY1(E)
RX(Y)Q32TNY1(E)
RX(Y)Q32TNY1(E)
Double
DoubleOutdoor
OutdoorUnits
Units
22,22,
2424
HPHP
Standard
Standard
Type
Type
42,42,
44,44,
46,46,
48,48,
5050
HPHP
RX(Y)Q42THY1(E)
RX(Y)Q42THY1(E)RX(Y)Q48THY1(E)
RX(Y)Q48THY1(E)
RX(Y)Q44THY1(E)
RX(Y)Q44THY1(E)RX(Y)Q50THY1(E)
RX(Y)Q50THY1(E)
RX(Y)Q46THY1(E)
RX(Y)Q46THY1(E)
Triple
TripleOutdoor
OutdoorUnits
Units
Double
DoubleOutdoor
OutdoorUnits
Units
Single
SingleOutdoor
OutdoorUnits
Units
High-COP
High-COP
Type
Type
RX(Y)Q36THY1(E)
RX(Y)Q36THY1(E)
RX(Y)Q40THY1(E)
RX(Y)Q40THY1(E)
RX(Y)Q34THY1(E)
RX(Y)Q34THY1(E)
RX(Y)Q38THY1(E)
RX(Y)Q38THY1(E)
New
New
Lineup
Lineup
HPHP
36,36,
4040
HPHP
34,34,
3838
HPHP
18,18,
20,20,
22,22,
24,24,
26,26,
28,28,
30,30,
3232
HPHP
Mo/C
Mo/C
Outdoor Unit Lineup
Outdoor Unit Lineup
The
Theoutdoor
outdoorunit
unitcapacity
capacityisisup
uptoto6060HP
HPininincrement
incrementofof2 2HP.
HP.
RX(Y)Q34TNY1(E)
RX(Y)Q34TNY1(E)
RX(Y)Q36TNY1(E)
RX(Y)Q36TNY1(E)
34,34,
36,36,
38,38,
4040
HPHP
RX(Y)Q26TSY1(E)
RX(Y)Q26TSY1(E)RX(Y)Q30TSY1(E)
RX(Y)Q30TSY1(E)
RX(Y)Q28TSY1(E)
RX(Y)Q28TSY1(E)RX(Y)Q32TSY1(E)
RX(Y)Q32TSY1(E)
RX(Y)Q34TSY1(E)
RX(Y)Q34TSY1(E)RX(Y)Q38TSY1(E)
RX(Y)Q38TSY1(E)
RX(Y)Q36TSY1(E)
RX(Y)Q36TSY1(E)RX(Y)Q40TSY1(E)
RX(Y)Q40TSY1(E)
RX(Y)Q42TNY1(E)
RX(Y)Q42TNY1(E)
RX(Y)Q44TNY1(E)
RX(Y)Q44TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q40TNY1(E)
RX(Y)Q40TNY1(E)
Double
DoubleOutdoor
OutdoorUnits
Units
26,26,
28,28,
30,30,
3232
HPHP
42,42,
4444
HPHP
38,38,
4040
HPHP
46,46,
48,48,
50,50,
52,52,
54,54,
56,56,
58,58,
6060
HPHP
RX(Y)Q54TNY1(E)
RX(Y)Q46TNY1(E)
RX(Y)Q46TNY1(E)RX(Y)Q54TNY1(E)
RX(Y)Q56TNY1(E)
RX(Y)Q48TNY1(E)
RX(Y)Q48TNY1(E)RX(Y)Q56TNY1(E)
RX(Y)Q58TNY1(E)
RX(Y)Q50TNY1(E)
RX(Y)Q50TNY1(E)RX(Y)Q58TNY1(E)
RX(Y)Q60TNY1(E)
RX(Y)Q52TNY1(E)
RX(Y)Q52TNY1(E)RX(Y)Q60TNY1(E)
Triple
TripleOutdoor
OutdoorUnits
Units
42,42,
4444
HPHP
RX(Y)Q42TSY1(E)
RX(Y)Q42TSY1(E)
RX(Y)Q44TSY1(E)
RX(Y)Q44TSY1(E)
46,46,
48,48,
5050
HPHP
RX(Y)Q46TSY1(E)
RX(Y)Q46TSY1(E)
RX(Y)Q48TSY1(E)
RX(Y)Q48TSY1(E)
RX(Y)Q50TSY1(E)
RX(Y)Q50TSY1(E)
Hotline: 0976 173 173
1414
Indoor
Indoor Unit
Unit Lineup
Lineup
VRV Indoor
Units
Enhanced
Enhanced
range
range
ofofchoices
choices
AA
mixed
mixed
combination
combination
ofof
VRV
VRV
indoor
indoor
units
units
and
and
residential
residential
indoor
indoor
units
units
Ceiling
Mounted
Cassette
Corner
Type
is is
enabled
enabled
allall
in in
one
one
system.
system.
Opening
Opening
the
the
door
door
toto
stylish
stylish
and
and
quiet
quiet
indoor
indoor
units.
units.
Slim Ceiling Mounted Duct Type
VRV
VRV
indoor
indoor
units
units
FXKQ25MA / FXKQ32MA
Residential
Residential
indoor
indoor
units
units
with
with
connection
connection
toto
BP
BP
units
units
Slim Model
design,
quietness
and
2.0
2.0
kWkW
Rated
Capacity
Capacity
Model
Name
Name Rated
Capacity
Capacity
Index
Index
2020
static pressure switching
20 20
Type
Type
Model
Model
Name
Name
FXKQ40MA / FXKQ63MA
FXFQ-SVM
FXFQ-SVM
Min.195 mm
Panel spacer
20 mm
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Drain pump is equipped as standard
accessory with 500 mm lift.
2
28˚C
32˚C 30˚C
FFQ-BV1B
FFQ-BV1B
2
3
71 71
2.52.5
kWkW
3.53.5
kWkW
5.05.0
kWkW
6.06.0
kWkW
7.17.1
kWkW
2525
3535
5050
6060
7171
FBQ-BV1
FBQ-BV1
FXDQ40NB / FXDQ50NB / FXDQ63NB
Cooling
Cooling
OnlyOnly
FDKS-EAVMB
FDKS-EAVMB
(900/1,100
(900/1,100
mmmm
width
width
type)type)
HeatHeat
Pump
PumpFDXS-CVMA
FDXS-CVMA
24˚C
Cooling
Cooling
OnlyOnly
FTKS-DVM
FTKS-DVM
Great
for
FTXS-DVMA
FTXS-DVMA
hotel
use!
HeatHeat
Pump
Pump
Wall
Wall
Mounted
Mounted
22˚C
5
Cooling
Cooling
OnlyOnly
FTKS-BVMA
FTKS-BVMA
200 mm
Cooling
Cooling
OnlyOnly
FTKS-FVM
FTKS-FVM
Only
700 mm
* 1,100 mm in width for the FXDQ63NB model.
Note:
Note:
BPBP
units
units
areare
necessary
necessary
for for
residential
residential
indoor
indoor
units.
units.
Only
Only
single
single
outdoor
outdoor
unitunit
(RX(Y)Q6-20TY1)
(RX(Y)Q6-20TY1)
cancan
be be
connected.
connected.
Suspension bolt*
AIR
Downward discharge
6464
* To be obtained locally
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Set for front discharge using a suspended ceiling.
FXDQ-PB and FXDQ-NB models are available in two
types to suit different installation conditions.
Main body
Control of the airflow rate has been improved from 2-step
to 3-step control.
BPBP
unit
unit
Air discharge grille
(Option)
Low operation sound level
FXVQ-MY1
FXVQ-MY1
FXDQ-PB/NB
Downward discharge is shut off and air is blown straight out
(front discharge).
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
Daikin
Daikin
airair
handing
handing
units
units
can
can
bebe
connected
connected
to to
VRV
VRV
IV IV
system.
system.
Please
Please
refer
refer
to to
page
page
103
103
and
and
contact
contact
your
your
local
local
sales
sales
office
office
forfor
details.
* details.
8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Suction grille *
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
flexible
model.
VRV
VRVindoor
indoorunits
unitsonly
only
Max.
Max.
indoor
indoor
units
units
25
1515
240 mm
Discharge grille *
Air discharge grille (Option)
FXVQ-MY16
FXVQ-MY16
Air filter
AIR
Main body
(high(high
staticstatic
pressure
pressure
type)type)
200 mm
900 mm
HeatHeat
Pump
PumpFTXS-FVMA
FTXS-FVMA
6 (m)
Front discharge is possible with an air
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
500 mm
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
FTXS-EVMA
FTXS-EVMA
26˚C
4
60 60
Only
700
mm
in width and
23mm
kg
in type)
weight, this
(700(700
mm
width
width
type)
HeatHeat
Pump
Pump
CDXS-EAVMA
CDXS-EAVMA
Slim
Slim
Ceiling
Ceiling
Mounted
Mounted
Duct
Duct model is suitable to install in limited spaces like
Cooling
Cooling
OnlyOnly
FDKS-C(A)VMB
FDKS-C(A)VMB
drop-ceilings in hotels.
20˚C
1
50 50
FXDQ20PB / FXDQ25PB / FXDQ32PB
1
0
Ceiling
Ceiling
Mounted
Mounted
Cassette
Cassette
(Compact
(Compact
MultiMulti
Flow)
Flow)
Ceiling
Ceiling
Mounted
Mounted
Built-in
Built-in
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
FCQ-BVE
FCQ-BVE
35 35
Suited to use in drop-ceilings!
Slim design for flexible installation
Slim body needs only 220 mm space above the
ceiling. If you use a panel spacer (option), the
unit can be installed in the minimum space of
195 mm.
Ceiling
Ceiling
Mounted
Mounted
Cassette
Cassette
8 types
8 types
2323
models
models
25 25
Indoor Unit Lineup
Indoor Unit Lineup
Type
Type
1818
types
types
8686
models
models
20/25/32
(dB(A))
40
50
63
Sound level
33/31/29
34/32/30
35/33/31
36/34/32
(HH/H/L)
Max.
Max.
indoor
* Theindoor
values
of operation sound level represent those for rear-suction operation.
units
units
Sound
level values for bottom-suction operation can be obtained by adding 5 dB(A).
3232
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXDQ-PB/NBVET: without a drain pump
Residential
Residentialindoor
indoorunits
units
750 mm
VRV
VRVindoor
indoorunits
units
Ceiling
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
of 15 Pa.
*Refer
*Refer
to page
to page
67-68
67-68
for for
thethe
maximum
maximum
number
number
of connectable
of connectable
indoor
indoor
units.
units.
Hotline: 0976 173 173
1626
16
Indoor
Indoor Unit
Unit Lineup
Lineup
VRV Indoor Units
Daikin offers a wide range of indoor units includes both VRV and residential
models responding to variety of needs of our customers that require
Ceiling Mountedsolutions.
Cassette Corner Type
air-conditioning
VRV Indoor
Units
FXKQ25MA / FXKQ32MA
FXHQ-MAVE
FXAQ-PVE
Slim Ceiling Mounted Duct Type
Slim design, quietness and
Stylish flat panel design
harmonised with your interior
static pressure switchingdécor
Slim body with quiet and wide
airflow
Ceiling Mounted Cassette
(Round Flow) Type
(Round Flow with Sensing)
Type
Wall Mounted Type
Floor Standing Type
FXFQ-LUV1
FXLQ-MAVE
FXFQ-SVM
Slim design for flexible installation
Presence of people and floor
temperature
be needs
detected
to 220 mm space above the
Slimcan
body
only
provide ceiling.
comfort and
energy
savings
If you use a panel spacer (option), the
360 airflow improves temperature
distribution
and offers
a comfortable
Providing
3 different
settings of standard, draft
living prevention
environment. and ceiling soiling prevention, the
Ceiling
Mounted
Cassette
195
mm.
(Compact Multi Flow) Type
4-Way
Flow Ceiling
distribution
of airflow and room temperature.
Suspended Type
FXZQ-MVE
FXUQ-AVEB
unit can be installed in the minimum space of
Min.195 mm
auto swing mechanism realises even
Panel spacer
2
20 mm
Single-flow type allows effective air discharge
from corner or from drop-ceiling.
Quiet, compact, and designed for
user comfort
Drain pump is equipped as standard
accessory with 500 mm lift.
Ceiling Mounted Cassette
(Double Flow) Type
FXCQ-MVE
500 mm
(m)
3
28˚C
32˚C 30˚C
26˚C
1
24˚C
Suited to use in drop-ceilings!
Concealed Floor
Standing
FXDQ20PB
/ FXDQ25PB / FXDQ32PB
Type
20˚C
Only 700 mm in width and 23 kg in weight, this
Only 200 mm in height, this model can be installed in
model is suitable to install in limited spaces like Large airfiow type for large spaces.
roomsdesign
with as
240 mm depth between the
Flexible interior
forlittle
eachastenant.
Suitable for perimeterdrop-ceilings
zone air conditioning
in hotels.
drop-ceiling and ceiling slab.
Great for
hotelIndoor
use!
Residential
Units
Only
FCQ-BVE
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Ceiling Mounted Cassette
body
CornerMain
Type
Downward discharge
FXDQ40NB / FXDQ50NB / FXDQ63NB
FXNQ-MAVE
with connection to BP units
Ceiling Mounted Cassette
Type
22˚C
This slim and stylish
indoor
unit3
0
1
2
4
5
6 (m)
achieves optimum air distribution,
and can be installed without the
Front
discharge
need for
ceiling
cavity. is possible with an air
FXKQ-MAVE
Floor Standing Duct Type
FXVQ-MY1
FXVQ-MY16
(high static pressure type)
Ceiling Mounted Cassette
200 mm
200 mm(Compact Multi900
Flow)
mmType
700 mm
FFQ-BV1B
* 1,100 mm in width for the FXDQ63NB model.
Suspension bolt*
Specially designed for false ceilings
—for a smooth, modern interior finish
Quiet, compact, and designed for user
AIR
comfort
Ceiling Mounted Built-in
Type
Slim Ceiling Mounted Duct Type
Air filter
240 mm
Discharge grille *
Cooling Only
AIR
Suction grille *
FDKS-EAVMB
FDKS-C(A)VMB
FBQ-BV1
Indoor Unit Lineup
Indoor Unit Lineup
FXKQ40MA
/ FXKQ63MA
Ceiling Mounted
Cassette
Ceiling Suspended Type
* To be obtained locally
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
CDXS-EAVMA
flexible model.
Air discharge grille (Option)
Heat Pump
FDXS-CVMA
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
Set for front
Slim design
for discharge
flexibleusing a suspended ceiling.
installation Main body
Flexible air discharge unit to fit
various forms of space
Slim Ceiling Mounted Duct
Type
Ceiling Mounted Duct
Type
Wall Mounted
Type
Control
of the airflow rate has been improved from 2-step
FXDQ-PBVE(T)
FXMQ-PVE
FXDQ-NBVE(T)
Downward discharge is shut off and air is blown straight out
FXMQ-MAVE
Slim design, quietness and
static pressure switching
High external
static
pressureas standard accessory.
year*) is
equipped
allows
flexible
installations
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
(front discharge).
A long-life filter (maintenance free up to one
to 3-step control.
Cooling Only
FTKS-DVM
FTKS-BVMA Low operation sound level
FTKS-FVM
FXDQ-PB/NB
20/25/32
Air discharge grille
(Option)
Heat Pump
1725
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Slim and smooth design suits your
shallow ceiling
FXDQ-PB and FXDQ-NB models are available in two
types to suit different installation conditions.
Thin, lightweight, and easy to install
in narrow ceiling spaces
FTXS-DVMA
FTXS-EVMA
FTXS-FVMA
Sound level
(HH/H/L)
33/31/29
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXDQ-PB/NBVET: without a drain pump
(dB(A))
40
50
63
34/32/30
35/33/31
36/34/32
* The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
panel
harmonises with
of 15 Pa.
750 mm
Ceiling
Stylish flat
your interior décor
Hotline: 0976 173 173
1826
Indoor
Indoor Unit
Unit Lineup
Lineup
VRVIndoor
IndoorUnits
Units
VRV
Ceiling
CeilingMounted
MountedCassette
Cassette(Round
CornerFlow
Typewith Sensing) Type
Slim Ceiling Mounted Duct Type
Airflow block function *3
Sensing function
Auto airflow rate mode + Auto airflow direction mode
Slim design, quietness and
Without sensing function
static pressure switching
FXFQ25S
/ FXFQ32S
/ FXFQ40S
FXKQ25MA
/ FXKQ32MA
FXFQ50S
/ FXFQ63S
/ FXFQ80S
FXKQ40MA
/ FXKQ63MA
Floor temperature is detected and over cooling prevented.
FXFQ100S / FXFQ125S
Area around feet gets
too cold because air
conditioner continues
until the temperature
near the ceiling reaches
the set temperature.
20°C near floor to use in drop-ceilings!
Suited
unit can
be installed
in the minimum space of
Infrared
presence
sensor
195 mm.
The sensor detects human presence and adjusts
the airflow direction automatically to prevent drafts.
Energy saving control can be performed
Min.195 mm
when no people are detected.
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
Panel spacer
20 mm
26˚C
22˚C
0
20˚C
1
2
3
4
5
Front discharge is possible with an air
discharge
unit airflow
(option),
which air
allows
Indoor
unit offers 360°
discharges
in all the
directions
with more
temperature distribution.
installation
inuniform
the drop-ceiling
or sagging wall.
The sensor detects the floor temperature and automatically
adjusts operation of the indoor unit to reduce the temperature
difference between the ceiling and the floor.
Individual airflow direction control
Thanks to the individual airflow direction control function, airflow
direction can be individually adjusted for each air discharge
outlet. 5 directions of airflow and auto-swing can be selected
with wired remote controller BRC1E62, which realises the
optimum air distribution.
Individual airflow direction example case
Position 2
Swing
Dead spot of airflow
Air discharge grille (Option)
Energy efficiency has been improved thanks to the
adoption of a new heat exchanger with smaller tubes,
DC fan motor and DC drain pump motor.
Set for front discharge using a suspended ceiling.
Low operation
sound level
Main body
FXFQ-S
Sound
level
(H/M/L)
25/32
40
50
63
80
100
125
30/28.5/27 31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35
Air discharge grille
(Option)
Control of airflow rate can be selected from 3-step
control, which provides comfortable airflow. Auto airflow
rate control can be selected with wired remote controller
BRC1E62.
Downward discharge is shut off and air is blown straight out
(front discharge).
Drain pump is equipped as
A long-life
filter
(maintenance
free up850
tomm
one
standard
accessory
with
850 mm
lift. year*) is equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
Example: • Cooling setpoint: 26°C
• Shift temperature: 1.0°C
28
27
26
26°C
Occupied
Automatically
reverts when
people return.
240 mm
Control of the airflow rate has been improved from 2-step
Low operation
sound
levelfrom 0.5 to 4°C in 0.5°C increments
Shift temperature
and time can
be selected
(dB(A))
and 15, 30, 45, 60, 90 or 120 minutes respectively with remote controller.
40
50
Suction grille *
* To be obtained locally
The airflow block function is
useful
when rearranging
the
FXDQ-PB
and FXDQ-NB
models are available in two
room
layout.
Airflow
types
to suit different installation
conditions.
mm*5
block
Time
After another 30 min
20/25/32
bolt* all-round
Air filterflow
This function only Suspension
works when
is used. It cannot be used when sealing material is
used inAIRthe air discharge outlet (option).
10 Horizontal
Pa-30 Pa/factory
models.block
flow set: 10 Pa for FXDQ-PBAirflow
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
26°C
If people
not return,
the air conditioner will raise the
todo
3-step
control.
temperature 1°C every 30 minutes and then operate at 30°C.
FXDQ-PB/NB
200 mm
New airflow block function prevents
900
mm
uncomfortable
drafts
by reducing air velocity.
It can be set using the BRC1E62 remote controller.
* 1,100 mm in width for the FXDQ63NB model.
There is no need for sealing
material of air discharge
outlet (option).
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
flexible model.
28°C
Unoccupied
After 30 min
Also can support
such this case
AIR
• Shift time: 30 min.
• Limit cooling temperature: 30°C
27°C
Airflow block
for cabinet side
grille *
Easy Discharge
setup with
remote controller
Sensing sensor low mode *1. 2
When there are no people in a room,
the set temperature is shifted automatically.
Downward discharge
Infrared floor sensor
700 mm
Comfortable airflow
Airflow rate automatically increases during hot or cold periods (when there
is a large difference with set temperature), and operation is rapidly
performed for cooling or heating.When the difference with set temperature
becomes small, drafts are prevented by automatically reducing airflow rate,
and raising the flap to a horizontal position during cooling operation.
Sensing sensor mode
Main body
500 mm
1925
Only
6 (m)
Airflow
block function
prevents uncomfortable
FXDQ40NB
/ FXDQ50NB
/ FXDQ63NB
drafts by reducing air velocity to approx. 0.3m/s.*4
Great for
Energy savings
The temperature near the person is automatically calculated by
detecting the temperature of the floor. Energy is saved, because
200 mm
the area around the feet does not get too cold.
24˚C
1
Single-flow type
air discharge
from corner or from drop-ceiling.
average
temperature of
indoor floor
28˚C
32˚C 30˚C
2
Presence of
people effective
in 4
allows
areas
24°C near floor
The floor temperature, which is lower
hotel
than
nearuse!
the ceiling, is detected.
(m)
3
Drain pump is equipped as standard
accessory with 500 mm lift. Detecting the
Automatic
control using
30°C near ceiling
Only 700 mm in width andthe
23temperature
kg in weight, this
Room temperature is
near the person
calculated as 27°C
in the area
which
model
is
suitable
to
install
in
limited
spaces like
is in the vicinity of the person.
as the room
drop-ceilings in hotels. temperature.
Setpoint (°C)
Slim body needs only 220 mm space above the
Dual sensors detect the presence of people and floor temperature
ceiling.
If youair-conditioning
use a paneland
spacer
(option),
to provide
comfortable
energy
savings.the
With sensing
function
FXDQ20PB
/ FXDQ25PB / FXDQ32PB
Indoor Unit Lineup
Indoor Unit Lineup
Presence of people and floor temperature can be
Slim design for flexible installation
detected to provide comfort and energy savings
Position 3
Airflow block
air velocity
approx. 0.3m/s*4
30°C near ceiling
Room
temperature is
detected as
30°C.
Position 0
Total comfort by individual airflow direction control
and newly-equipped “airflow block function”
63
Sensing sensor
Soundstop
level mode33/31/29
34/32/30
35/33/31
36/34/32
(HH/H/L)
When there are no people in a room, the system
The values of operation sound level represent those for rear-suction operation.
stops *automatically.
*1. 2
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXDQ-PB/NBVET: without a drain pump
500
Wall
*3. Works in one direction only.
*4. In case of FXFQ63S type (Data is based on Daikin research.)
*5. A gap of 1500 mm is required if the air block function is not used.
750 mm
Ceiling
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
Absent* stop
can be
selected
1 to 24 hrs in 1 hr
Valuestime
are based
on the
followingfrom
conditions:
increments
with remote
controller.
FXDQ-PB:
external static
pressure of 10 Pa; FXDQ-NB: external static pressure
*1. These of
functions
15 Pa. are not available when using the group control system.
*2. User can set these functions with remote controller.
Hotline: 0976 173 173
2026
Indoor
Indoor Unit
Unit Lineup
Lineup
VRVIndoor
IndoorUnits
Units
VRV
Ceiling
CeilingMounted
MountedCassette
Cassette(Round
CornerFlow)
Type Type
Slim Ceiling
Mounted
Duct
Type Multi Flow) Type
Ceiling
Mounted
Cassette
(Compact
FXZQ20M
/ FXZQ25Mquietness
/ FXZQ32M
Slim
design,
and
FXZQ40M / FXZQ50M
static pressure switching
FXFQ25LU
/ FXFQ32LU
/ FXFQ40LU
FXKQ25MA
/ FXKQ32MA
FXFQ50LU
/ FXFQ63LU
/ FXFQ80LU
FXKQ40MA
/ FXKQ63MA
FXFQ100LU / FXFQ125LU
Suited to use in drop-ceilings!
Quiet, compact, and designed for user comfort
Slim body needs only 220 mm space above the
The industry’s first* Round Flow Ceiling Mounted
ceiling.
you 360°
use aairflow
panelwith
spacer
(option), the
Cassette
type If
offers
improved
unit
can
be
installed
in
the
minimum
space of
temperature distribution.
4-way flow
195 mm.
Round Flow
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
Min.195 mm
Panel spacer
2
20 mm
There are much fewer
areas of uneven temperature.
There are areas of
uneven temperature.
Single-flow type allows effective air discharge
The light
weight
unitoratfrom
19.5drop-ceiling.
kg for FXFQ25-50LU
from
corner
Drain Drain
pump pump
is equipped
as a
is equipped
as standard
standard
accessory
with
a
850
mm
accessory with 500 mm lift.
lift.
850 mm
A modern sophisticated decoration panel has been
applied, with a panel surface that has been
treated with
500 mm
a dirt-repellant coating.
Treated surface
Untreated surface
Dirt and
grime • Condition after
exposure to the
smoke of 600
3
cigarettes in 1 m
enclosed space.
Resists
soiling
Control of the airflow rate can be selected from 3-step
control.
Low operation sound level
FXFQ-LU
25/32
40
50
(dB(A))
63
80
100
125
Sound
level
30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
(HH/H/L)
Example of airflow patterns:
All-round flow
All-round flow is available, as well as 2-way to
4-way flows, so you can choose the most
suitable airflow pattern depending on location or
room layout.
28˚C
32˚C 30˚C
26˚C
24˚C
0
2
3
4
5
20/25
Sound Great
level
(H/L)
for 32/29
30/25
hotel use!
32
40
50
32/26
33/29
36/28
36/30
41/33
41/34
Wide discharge angle: 0° to 60°
Auto swing
6 (m)
Front discharge is possible with an air
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Only
FXDQ40NB / FXDQ50NB / FXDQ63NB
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
200 mm
700 mm
0°
200 mm
900 mm
* 1,100 mm in width for the FXDQ63NB model.
Suspension bolt*
0°
60°
Main body
240 mm
Discharge grille *
AIR
Downward discharge
An antibacterial treatment that uses silver ions has
been applied to the drain pan, preventing the growth
Air discharge
(Option)
of slime, mould and bacteria
thatgrille
cause
blockages
and odours.
The horizontal louvres prevent dew condensation.
for front dischargesurfaces,
using a suspended
ceiling.
TheirSet
non-flocking
which
repel dirt, are
easy to clean.
Main body
The air filter has an anti-mould and antibacterial
treatment that prevents the growth of mould
generated from dust or moisture that may adhere to
Air discharge grille
the filter.
(Option)
4-way flow
3-way flow
L-shaped 2-way flow
Downward discharge is shut off and air is blown straight out
(front discharge).
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
0°
60°
2-, 3-, and 4-way airflow patterns are available,
enabling
in the
of a room.
Control installation
of the airflow
ratecorner
has been
improved from 2-step
to 3-step control.
Low operation sound level
FXDQ-PB and FXDQ-NB models are available in two
750 mm
types to suit different installation
conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXDQ-PB/NBVET: without a drain pump
(dB(A))
FXDQ-PB/NB
20/25/32
40
50
63
Sound level
(HH/H/L)
33/31/29
34/32/30
35/33/31
36/34/32
* The values of operation sound level represent those for rear-suction operation.
L-shaped
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
4-way flow
3-way flow
2-way flow
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
*For 3-way
orPa.
2-way flow installation, the sealing member for air discharge outlet
of 15
(option) must be used to close each unused outlet.
* To be obtained locally
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
*Angles can be also set on site to prevent drafts (0°-35°)
or soiling of the ceiling (25°-60°), other than standard setting (0°-60°).
2
Suction grille *
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
Drainflexible
pump model.
is equipped as standard accessory with
Pa-30
750 10
mm
lift. Pa/factory set: 10 Pa for FXDQ-PB models.
0°
60°
Air filter
AIR
60°
Fixed angles: 5 levels
3
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge
sealing
material (option)
used to close each
unused
outlet.
* 8 outlet
hr/day,
25 day/month.
Formust
dustbe
concentration
of 0.15
mg/m
2125
FXZQ-M
1
20˚C
1
Dimensions correspond with 600 mm X 600 mm
architectural module ceiling design specifications.
Only 700 mm in width and 23 kg in weight, this
modelsound
is suitable
Low operation
levelto install in limited spaces like
(230 V)(dB(A))
drop-ceilings in hotels.
Comfortable airflow
22˚C
1
* As of April 2004, the release date for Japan.
models makes installation easy.
FXDQ20PB / FXDQ25PB / FXDQ32PB
Indoor Unit Lineup
Indoor Unit Lineup
360° airflow
improves
distribution
Slim design
for temperature
flexible installation
and offers a comfortable living environment.
750 mm
Ceiling
Hotline: 0976 173 173
2226
Indoor
Indoor Unit
Unit Lineup
Lineup
VRVIndoor
IndoorUnits
Units
VRV
Slim Ceiling
Mounted
Duct
Type Flow) Type
Ceiling
Mounted
Cassette
(Double
4-Way
Flow
CeilingCassette
Suspended
Type
Ceiling
Mounted
Corner
Type
FXCQ20M / FXCQ25M / FXCQ32M
Slim design, quietness and
static
pressure switching
FXCQ80M
/ FXCQ125M
FXKQ25MA / FXKQ32MA
FXUQ71A / FXUQ100A
FXKQ40MA / FXKQ63MA
FXCQ40M / FXCQ50M / FXCQ63M
ceiling.
If you use
a panel spacer (option), the
Unit body
and suction
panel
adopted
round
and in the minimum space of
unit
can shapes
be installed
realised a slim appearance
195 mm.
design. The unit can be used
for various locations such as
the ceilings with no cavity
and mm
Min.195
bare ceilings.
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
Panel spacer
Flaps close automatically when
20 mm
the unit stops, which gives a
simpleSingle-flow
appearance.type allows effective air discharge
Unifiedfrom
slim corner
height ofor198
mm
from
drop-ceiling.
for all models that gives the
198 mm
unified impression even when
pump iscapacities
equipped as standard
modelsDrain
with different
accessory
mm lift.
are installed
in thewith
same500
area.
Built-in electronic expansion valve eliminates the need
for a BEV unit, which improves flexibility of installation.
Current model
BEV unit is
needed
New
model
500 mm
2
0
305 mm
20˚C
1
2
3
4
5
Only
Front discharge is possible with an air
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Control of the airflow rate has been improved from
Main body
2-step to 3-step control. Auto airflow rate control can
be selected with wired remote controller BRC1E62.
Drain pump is equipped as a standard accessory, and the
lift height has been improved from 500 mm to 600 mm.
Set for front
using a suspended
ceiling.
Depending
ondischarge
installation
site requirements
or room
conditions,Main
2-way,
3-way
and
4-way
discharge
body
patterns are available.
3-way flow
4-way flow
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
200 mm
700 mm
200 mm
900 mm
(When a high-efficiency filter is attached, the unit's height is
400 mm.)
6 (m)
* 1,100 mm in width for the FXDQ63NB model.
Suspension bolt*
Low operation sound level
Air filter
(220 V)(dB(A))
FXCQ-M
20
25/32
40/50
63
80
125
Sound level
(H/L)
32/27
34/28
34/29
37/32
39/34
44/38
240 mm
AIR
Discharge grille *
AIR
Designed with higher airflow suitable for high ceiling
application up to 3 metres.
Providing 2 different settings of standard and ceiling soiling
prevention, the auto swing mechanism realises even
distribution of airflow and room temperature.
Suction grille *
* To be obtained locally
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
flexible model.
Two 10
types
optionalset:
high-efficiency
filter
are available
Pa-30ofPa/factory
10 Pa for FXDQ-PB
models.
Pa-44
Pa/factory
set: 15 Pa for
FXDQ-NB models.
(65%15and
95%,
colourimetric
method).
FXDQ-PB and FXDQ-NB models are available in two
types to suit different installation conditions.
A long-life filter (maintenance free up to one year*) is
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
DrainControl
pump is
standard
accessory
with
of equipped
the airflowasrate
has been
improved
from 2-step equipped as standard
accessory.
as a standard
accessory
600 mm
lift.
to 3-step control.
* 8 hr/day,
25 day/month. For dust concentration
of 0.15 mg/m
FXDQ-PB/NBVET:
without a drain
pump
3
Air discharge grille
(Option)
Position 2
Swing
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings
hotels.
The thin unit
(only 305 in
mm
high) can be installed in a
ceiling space as narrow as 350 mm. All models feature a
compact design
with a depth of only 600 mm.
Great for
hotel use!
22˚C
Energy efficiency has been improved thanks to the
adoption of a new heat exchanger with smaller
Air discharge
grille
(Option)
tubes, DC fan motor and
DC drain
pump
motor.
BEV unit is
not needed
Thin, lightweight, and easy
to install
in / FXDQ63NB
FXDQ40NB
/ FXDQ50NB
narrow ceiling spaces
FXDQ20PB / FXDQ25PB / FXDQ32PB
24˚C
1
Individual airflow direction example case
Position 3
26˚C
Downward discharge
With adoption of the individual flap control, airflow
direction adjustment can be individually set for each air
outlet. 5 directions of airflow and auto-swing can be
selected with wired remote controller BRC1E62, which
realises the optimum air distribution.
Position 0
28˚C
32˚C 30˚C
Suited to use in drop-ceilings!
Indoor Unit Lineup
Indoor Unit Lineup
This slim and stylish indoor unit achieves
optimum
distribution,
and can
be installed
Slimair
design
for flexible
installation
without the need for ceiling
cavity.
Slim body needs only 220 mm space above the
Providing 3 different settings of standard, draft
Downward
is shut off and air is blown straight out
L-shaped
2-waydischarge
flow
(front discharge).
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
Low operation sound level
(dB(A))
FXDQ-PB/NB
20/25/32
40
Sound level
(HH/H/L)
33/31/29
34/32/30
50
63
35/33/31
36/34/32
600 mm
* The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
of 15 Pa.
Major maintenance work can be performed by removing
750 mm
the panel. A flat-type suction grille and a detachable
blade make cleaning easy.
Ceiling
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
2325
Hotline: 0976 173 173
2426
Indoor Unit
Unit Lineup
Lineup
Indoor
VRVIndoor
IndoorUnits
Units
VRV
SlimCeiling
CeilingMounted
MountedDuct
DuctType
Type
Slim
CeilingMounted
MountedCassette
CassetteCorner
CornerType
Type
Ceiling
Slimdesign,
design,quietness
quietnessand
and
Slim
staticpressure
pressureswitching
switching
static
FXKQ25MA/ FXKQ32MA
/ FXKQ32MA
FXKQ25MA
FXKQ40MA/ FXKQ63MA
/ FXKQ63MA
FXKQ40MA
Suitedtotouse
useinindrop-ceilings!
drop-ceilings!
Suited
Slim
body
needs
only
220
mm
space
above
the
Slim
body
needs
only
220
mm
space
above
the
ceiling.If you
If you
use
a panel
spacer
(option),
the
ceiling.
use
a panel
spacer
(option),
the
unit
can
installed
the
minimum
space
unit
can
bebe
installed
in in
the
minimum
space
ofof
195
mm.
195
mm.
Providing
3 different
settings
standard,
draft
Providing
3 different
settings
ofof
standard,
draft
prevention
and
ceiling
soiling
prevention,
the
prevention
and
ceiling
soiling
prevention,
the
auto
swing
mechanism
realises
even
auto
swing
mechanism
realises
even
distribution
airflow
and
room
temperature.
distribution
ofof
airflow
and
room
temperature.
(m)(m)
3 3
Min.195
Min.195
mmmm
Panel
spacer
Panel
spacer
20 20
mmmm
Single-flow
type
allows
effective
discharge
Single-flow
type
allows
effective
airair
discharge
from
corner
from
drop-ceiling.
from
corner
oror
from
drop-ceiling.
Drain
pump
equipped
standard
Drain
pump
is is
equipped
asas
standard
accessory
with
500
mm
accessory
with
500
mm
lift.lift.
FXDQ20PB/ FXDQ25PB
/ FXDQ25PB/ FXDQ32PB
/ FXDQ32PB
FXDQ20PB
2 2
28˚C 26˚C
26˚C
28˚C
24˚C
24˚C
30˚C
30˚C
32˚C
32˚C
22˚C
22˚C
1 1
20˚C
20˚C
0 0
Only
700
mm
width
and
weight,
this
Only
700
mm
in in
width
and
2323
kgkg
in in
weight,
this
model
suitable
install
limited
spaces
like
model
is is
suitable
to to
install
in in
limited
spaces
like
drop-ceilings
hotels.
drop-ceilings
in in
hotels.
200
mm
200
mm
200
mm
200
mm
900mm
mm
900
* 1,100
in width
for the
FXDQ63NB
model.
* 1,100
mmmm
in width
for the
FXDQ63NB
model.
Front
discharge
possible
with
Front
discharge
is is
possible
with
anan
airair
discharge
unit
(option),
which
allows
the
discharge
unit
(option),
which
allows
the
installation
the
drop-ceiling
sagging
wall.
installation
in in
the
drop-ceiling
oror
sagging
wall.
Suspension
bolt*
Suspension
bolt*
Air Air
filterfilter
240mm
mm
240
AIRAIR
Main
body
Main
body
500500
mmmm
Only
200
mm
height,
this
model
can
installed
Only
200
mm
in in
height,
this
model
can
bebe
installed
in in
rooms
with
little
240
mm
depth
between
rooms
with
asas
little
asas
240
mm
depth
between
thethe
drop-ceiling
and
ceiling
slab.
drop-ceiling
and
ceiling
slab.
Great
Great
forfor
hotel
use!
hotel
use!
Only
700mm
mm
Only
700
6 (m)
1 1 2 2 3 3 4 4 5 5 6 (m)
FXDQ40NB/ FXDQ50NB
/ FXDQ50NB/ FXDQ63NB
/ FXDQ63NB
FXDQ40NB
Indoor Unit Lineup
Indoor Unit Lineup
Slimdesign
designfor
forflexible
flexibleinstallation
installation
Slim
Discharge
grille
Discharge
grille
* *
AIRAIR
Downward
discharge
Downward
discharge
Suction
grille
Suction
grille
* *
To obtained
be obtained
locally
* To* be
locally
External
static
pressure
selectable
remote
controller
External
static
pressure
selectable
byby
remote
controller
switching
make
this
indoor
unit
a very
comfortable
and
switching
make
this
indoor
unit
a very
comfortable
and
flexible
model.
flexible
model.
discharge
grille
(Option)
Air Air
discharge
grille
(Option)
Pa-30
Pa/factory
FXDQ-PB
models.
10 10
Pa-30
Pa/factory
set:set:
10 10
Pa Pa
for for
FXDQ-PB
models.
Pa-44
Pa/factory
FXDQ-NB
models.
15 15
Pa-44
Pa/factory
set:set:
15 15
Pa Pa
for for
FXDQ-NB
models.
for front
discharge
using
a suspended
ceiling.
SetSet
for front
discharge
using
a suspended
ceiling.
FXDQ-PB
and
FXDQ-NB
models
available
two
FXDQ-PB
and
FXDQ-NB
models
areare
available
in in
two
types
suit
different
installation
conditions.
types
to to
suit
different
installation
conditions.
Main
body
Main
body
Control
airflow
rate
has
been
improved
from
2-step
Control
of of
thethe
airflow
rate
has
been
improved
from
2-step
3-step
control.
to to
3-step
control.
discharge
grille
Air Air
discharge
grille
(Option)
(Option)
Low
operation
sound
level
Low
operation
sound
level
FXDQ-PB/NB
FXDQ-PB/NB
Sound
level
Sound
level
(HH/H/L)
(HH/H/L)
Downward
discharge
is shut
off and
airblown
is blown
straight
Downward
discharge
is shut
off and
air is
straight
out out
(front
discharge).
(front
discharge).
long-life
filter
(maintenance
free
one
AA
long-life
filter
(maintenance
free
upup
toto
one
year*)
year*)
equipped
standard
accessory.
is is
equipped
asas
standard
accessory.
20/25/32
20/25/32
FXDQ-PB/NBVE:
with
a drain
pump
(750
FXDQ-PB/NBVE:
with
a drain
pump
(750
mmmm
lift)lift)
a standard
accessory
as as
a standard
accessory
FXDQ-PB/NBVET:
without
a drain
pump
FXDQ-PB/NBVET:
without
a drain
pump
(dB(A))
(dB(A))
40 40
50 50
63 63
750
mm
750
mm
33/31/29 34/32/30
34/32/30 35/33/31
35/33/31 36/34/32
36/34/32
33/31/29
* The
values
of operation
sound
level
represent
those
for rear-suction
operation.
* The
values
of operation
sound
level
represent
those
for rear-suction
operation.
Sound
level
values
for bottom-suction
operation
be obtained
by adding
5 dB(A).
Sound
level
values
for bottom-suction
operation
cancan
be obtained
by adding
5 dB(A).
* Values
based
on the
following
conditions:
* Values
are are
based
on the
following
conditions:
FXDQ-PB:
external
static
pressure
of Pa;
10 Pa;
FXDQ-NB:
external
static
pressure
FXDQ-PB:
external
static
pressure
of 10
FXDQ-NB:
external
static
pressure
of Pa.
15 Pa.
of 15
Ceiling
Ceiling
3
3
8 hr/day,
25 day/month.
concentration
of 0.15
mg/m
* 8 *hr/day,
25 day/month.
ForFor
dustdust
concentration
of 0.15
mg/m
2525
Hotline: 0976 173 173
2626
Indoor
Indoor Unit
Unit Lineup
Lineup
VRVIndoor
IndoorUnits
Units
VRV
Ceiling
Type Corner Type
CeilingMounted
MountedDuct
Cassette
Ceiling
Suspended
TypeDuct Type
Slim Ceiling
Mounted
FXMQ20P / FXMQ25P / FXMQ32P
FXKQ25MA
/ FXKQ32MA
FXMQ40P
/ FXMQ50P
/ FXMQ63P
FXMQ80P
/ FXMQ100P
/ FXMQ125P
FXKQ40MA
/ FXKQ63MA
FXMQ140P
FXHQ32MA
/ FXHQ63MA
Slim
design,
quietness and
FXHQ100MA
static
pressure switching
Suited toSlim
use inbody
drop-ceilings!
with quiet
Slim body needs only 220 mm space above the
Aceiling.
DC fan motor
the spacer
external(option),
static the
If you increases
use a panel
pressure capacity range to include middle to high
unit can
be installed
in thedesign
minimum
space of
static
pressures,
increasing
flexibility.
mm.Pa for FXMQ20P-32P
30195
Pa–100
30 Pa–160 Pa for FXMQ40P
50 Pa–200 Pa for FXMQ50P-125P
Min.195 mm
50 Pa–140 Pa for FXMQ140P
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
All models are only 300 mm in height, anPanel spacer
mm of
improvement over the 390 mm 20
height
conventional models. The weight of the
Single-flow
airtodischarge
FXMQ40P
hastype
beenallows
reducedeffective
from 44 kg
28 kg.
frompump
corner
or from drop-ceiling.
Drain
is equipped
as
standard accessory with
700 mm lift.
700 mm
Drain pump is equipped as standard
accessory with 500 mm lift.
Ceiling
Control of the airflow rate has been improved
from 2-step to 3-step control.
Low operation sound level
FXMQ-P 20/25
32
40
50
63
500 mm
80/100
125
(dB(A))
140
Sound
level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
(HH/H/L)
Energy-efficient
The adopted DC fan motor is much more efficient than
the conventional AC motor, yielding an approximate
20% decrease in energy consumption (FXMQ125P).
FXMQ200MA/FXMQ250MA
FXDQ20PB / FXDQ25PB / FXDQ32PB
2
28˚C
32˚C 30˚C
26˚C
22˚C
2
3
4
5
6 (m)
Front discharge is possible with an air
discharge unit (option), which allows the
Improved
ease of installation
installation
in the drop-ceiling or sagging wall.
Airflow rate can be controlled using a remote controller during
Main body
test operation. With the conventional model, the airflow rate
was controlled from the PC board. It is automatically adjusted to
Downward discharge
the range between approximately
±10% of the rated HH tap
airflow for FXMQ20P–125P.
Built-in Drain Pump (Option)
Housing the drain pump inside the unit reduces the
space required for installation.Air discharge grille
(Option)
With drain pump
mm
External static pressure can be easily adjusted using
a change-over switch inside the electrical box to meet
the resistance in the duct system.
2725
Only
Downward
discharge is shut off and air is blown
out
470 straight
mm
470
mm
(front discharge).
222 mm
25 mm
A long-life filter (maintenance free up to one
Indoor unit
year*) is equipped as standard accessory.
Indoor unit
200 mm
700 mm
200 mm
900 mm
* 1,100 mm in width for the FXDQ63NB model.
Low operation sound level
(dB(A))
FXHQ-MA
32
63
100
Sound level
(H/L)
36/31
39/34
45/37
Suspension bolt*
Air filter
240 mm
AIR
Discharge grille *
Installation is easy
Drain pump kit (option) can be easily incorporated.
AIR
Suction grille *
* To be obtained locally
Maintenance is easy
Non-dew Flap with no implanted bristles
Bristle-free
minimises
ExternalFlap
static
pressure selectable by remote controller
contamination
and makes
switching make
this indoor unit a very comfortable and
cleaning simpler.
600 mm
flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Drain pump kit
(built inside main unit)
Main body
0–250
Simplified Static Pressure Control
Quiet stream fan
Straightening vane
Air discharge grille (Option)
Improved ease of maintenance
The drain pan can be detached for easy cleaning. An
antibacterial treatment that uses silver ions has been applied to
the drain
preventing
thea growth
ofceiling.
slime, mould and
Setpan,
for front
discharge using
suspended
bacteria that cause blockages and odours.
Without drain pump
Sound absorption
member
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
Great for
hotel use!
Turbulent flow
is produced
20˚C
1
700 mm
in width
Uses the Only
quiet stream
fan and
many and 23 kg in weight, this
more advanced
modeltechnologies.
is suitable to install in limited spaces like
24˚C
1
0
FXDQ40NB / FXDQ50NB / FXDQ63NB
Adoption of QUIET STREAM FAN
drop-ceilings in hotels.
and wide airflow
Indoor Unit Lineup
Indoor Unit Lineup
Middle and high static pressure
Slim
design
flexible
allows
for for
flexible
ductinstallation
design
Wide air discharge openings produce a spreading 100°
Control of the airflow rate has been improved from 2-step
airflow.
to 3-step control.
Low operation sound level
(dB(A))
FXDQ-PB/NB
20/25/32
40
50
63
Sound level
(HH/H/L)
33/31/29
100°
34/32/30
35/33/31
36/34/32
* The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
of 15 Pa.
FXDQ-PB and FXDQ-NB models are available in two
types to suit different installation conditions.
Non-dew
FXDQ-PB/NBVE:
with aFlap
drain pump (750 mm lift)
as a standard accessory
Easy-to-clean
flat
design
FXDQ-PB/NBVET: without a drain pump
Maintenance is easier because everything can be
performed from below the unit.
750 mm
A long-life filter (maintenance
free up to one year*) is
equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Ceiling
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
Hotline: 0976 173 173
2826
Indoor
Indoor Unit
Unit Lineup
Lineup
VRVIndoor
IndoorUnits
Units
VRV
Wall
Mounted
TypeCassette Corner Type
Ceiling
Mounted
Floor
Type
SlimStanding
Ceiling Mounted
Duct Type
FXLQ20MA / FXLQ25MA
Slim
design, quietness and
FXLQ32MA / FXLQ40MA
static
pressure
switching
FXLQ50MA
/ FXLQ63MA
FXAQ20P / FXAQ25P
FXKQ25MA
/ FXKQ32MA
FXAQ32P
/
FXAQ40P
FXKQ40MA / FXKQ63MA
FXAQ50P / FXAQ63P
Stylish flat panel design harmonised
Slim design
for flexible
installation
with your
interior décor
unit can be installed in the minimum space of
Flat
panel
can be cleaned with only the single pass of a
195
mm.
cloth across their smooth surface.
Flat panel can also be easily removed and washed for
more thorough cleaning.
Min.195 mm
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
Panel spacer
Low operation sound level
FXAQ-P
20
25
20 mm
32
40
28˚C
32˚C 30˚C
2
(dB(A))
50
26˚C
24˚C
63
Single-flow type allows effective air discharge
38/31
39/34
42/37
47/41
drop-ceiling.
0
20˚C
1
2
3
4
5
Only
Main body
5 steps of discharge angle can be set by remote
controller.
Discharge angle is automatically set at the same angle
as the previous operation when restarting. (Initial setting:
10° for cooling and 70° for heating)
Flexible installation
Drain pipe can be fitted to from either left or
right sides.
The adoption of a fibre-less discharge grille featuring an
forto prevent condensation also helps
originalGreat
design
hotel use!
prevent staining and makes cleaning easier.
6 (m)
Front discharge is possible with an air
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Vertical auto-swing realises efficiency of air distribution.
The louvre closes automatically when 500
themm
unit stops.
Floor Standing types can be hung on the wall for easier
cleaning.
Running
the
from23
thekgback
allowsthis
the
Only
700 mm
in piping
width and
in weight,
unit to model
be hung
on
walls.
Cleaning
under
the
unit,
where
is suitable to install in limited spaces like
dust tends
to accumulate,
is considerably easier.
drop-ceilings
in hotels.
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
700 mm
900Wallmm
hanging
3
Floor installation
Suspension bolt*
Concealed Floor Standing Type
Air filter
240 mm
AIR
Discharge grille *
AIR
FXNQ32MA / FXNQ40MA
FXNQ50MA / FXNQ63MA
Suction grille *
* To be obtained locally
External static pressure selectable by remote controller
switching make this indoor unit a very comfortable and
flexible model.
Air discharge grille (Option)
Drain pump kit is available as optional accessory, which
lifts the drain 1,000 mm from the bottom of the unit.
Setoffordrain-up
front discharge using a suspended ceiling.
Height
200 mm
* 1,100 mm in width for the FXDQ63NB model.
FXNQ20MA / FXNQ25MA
Downward discharge
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
FXDQ-PB and FXDQ-NB models are available in two
Designed to be concealed in the
skirting-wall
typesperimeter
to suit different installation
conditions.
Main body
Control
the airflowinrate
has beenof
improved
from
2-step
The
unit isofconcealed
skirting-wall
perimeter,
that
to 3-step
enables
to control.
create high class interior design.
1,000 mm
Drain pump kit
FXDQ40NB / FXDQ50NB / FXDQ63NB
A long-life filter (maintenance free up to one year*) is
equipped as standard accessory.
200 mm
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m
22˚C
1
Sound level
35/31
36/31
from
(H/L) corner or from
Drain
equipped
as standard
Drain
panpump
and airisfilter
can be kept
clean by mould-proof
polystyrene.
accessory with 500 mm lift.
Suitable for perimeter zone air conditioning
FXDQ20PB / FXDQ25PB / FXDQ32PB
Indoor Unit Lineup
Indoor Unit Lineup
Stylish
panel
design
creates
graceful
harmony
Slimflat
body
needs
only
220 amm
space
above that
the
enhances
any
interior
space.
ceiling. If you use a panel spacer (option), the
Suited to use in drop-ceilings!
Air discharge grille
(Option)
Indoor
unit
Low
operation port
sound
level
The
connecting
faces
downward,
greatly
facilitating on-site
FXDQ-PB/NB
20/25/32piping work.
40
Sound level
(HH/H/L)
Downward discharge is shut off and air is blown straight out
(front discharge).
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
33/31/29
34/32/30
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXDQ-PB/NBVET: without a drain pump
(dB(A))
50
35/33/31
63
Connecting
port
36/34/32
A long-life filter (maintenance free up
Refrigerant
The values of operation sound level represent those for rear-suction operation. piping
to* one
year*) is equipped as standard
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
* Values are based on the following conditions:
accessory.
750 mm
Ceiling
* Appliesstatic
also topressure
Floor Standing type (FXLQ-MA).
FXDQ-PB:
external
pressure of of
100.15
Pa;mg/m
FXDQ-NB:
external
3
* 8 hr/day,
25 day/month.
Forstatic
dust concentration
of 15 Pa.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
2925
Hotline: 0976 173 173
3026
Indoor
Indoor Unit
Unit Lineup
Lineup
VRVIndoor
IndoorUnits
Units
VRV
Residential Indoor Units
Floor
Standing
Duct
Type Corner Type
Ceiling
Mounted
Cassette
Slim Ceiling
Mounted
Duct
Type
Ceiling
Mounted
Cassette
Type
FXVQ125M / FXVQ200M
FXKQ25MA
/ FXKQ32MA
FXVQ250M
/ FXVQ400M
/ FCQ50B
SlimFCQ35B
design,
quietness and
FCQ60B / FCQ71B
static pressure switching
FXKQ40MA / FXKQ63MA
FXVQ500M
Large airflow type for large spaces.
Flexible interior design for each tenant.
Slim design for flexible installation
Suited to use in drop-ceilings!
FXDQ20PB / FXDQ25PB / FXDQ32PB
Slim body needs only 220 mm space above the
Various installations
be supported
from full-scale
ceiling.
If you use acan
panel
spacer (option),
the duct
connection airflow to direct airflow that allows for easy
unit
can
be
installed
in
the
minimum
space
of
installation.
195 mm.
Full-scale duct connection airflow
allows for air conditioning evenly in
spacious areas. Min.195 mm
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
distribution of airflow and room temperature.
(m)
3
Panel spacer
Duct connection airflow type
20 mm
26˚C
1
2
3
4
5
6 (m)
Downward discharge
A long-life filter (maintenance free up to one year*) is
equipped as a standard accessory.
Air discharge grille (Option)
950 mm
Main body
A wide range of optional accessories are available such
as high-efficiency filters.
All-fresh (using outdoor air only) system
Outside
*When using the unit as an outdoor-air
processing unit, there are some
restrictions. Strictly follow the restrictions
specified in the Engineering Data Book.
Outdoor air
introduction
Air
conditioning
Outside
Suspension bolt*
Same for
all models
240 mm
Discharge grille
Draft* prevention
AIR
A long-life filter (maintenance free up to one
introduced from the outside and circulated air must be mixed in the
year*) is*airAir
equipped
as standard accessory.
conditioner primary side before introduction into the air conditioner.
Low operation
level
FXDQ-PB/NBsound
20/25/32
Suction grille *
* To be obtained locally
External static pressure selectable by remote controller
switchingSoiling
makeprevention
this indoor unit a very comfortable and
flexible model.
Decoration panel is optional
Low operation sound level
Air
conditioning
Downward discharge is shut off and air is blown straight out
(front discharge).
Outdoor air
introduction
Air filter
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
FXDQ-PB and FXDQ-NB models are available in two
types to suit different installation conditions.
DrainFXDQ-PB/NBVE:
pump is equipped
as
with a drain pump (750 mm lift)
Min. been
245 mm improved from 2-step
Control of the airflow rate has
a standard accessory
standard with 750asmm.
to 3-step control.
FXDQ-PB/NBVET: without a drain pump
Air discharge grille
(Option)
Return + Outdoor air mixed system
Circulated air
Outdoor air intake mode is
useable as an outdoor-air
processing air conditioner.
Standard
The indoor units weigh only 24 kg and require an
installation space with a height of just 245 mm.
Set for front discharge using a suspended ceiling.
mg/m3
* 1,100 mm in width for the FXDQ63NB model.
AIR
Main body
Design with high maintainability that allows major
services and maintenance services to be performed at
the front.
200 mm
Three convenient patterns for auto-swing operation
All models feature a decoration panel with the same
compact size and simple design for easier planning
of lighting systems and harmonising of interior décor.
950 mm
The high static pressure type driven by the belt drive
system allows for use of air discharge outlets in various
shapes as well as long ducts. Highly
installation
500 flexible
mm
is possible.
Note: Wireless remote
controllers and signal
receiver units are sold
as a set.
Specially designed for false ceilings
200 mm
900 mm finish
—for
a
smooth,
modern interior
Only 700 mm
20˚C
0
Only 200 mm in height, this model can be installed in
Signal receiver
unit the
depth
between
Option
rooms with as little as 240 mm
Note: Remote controller
drop-ceiling
cables
not included. and ceiling
Optionslab.
Cables should be
obtained locally.
Great for
hotel use!
22˚C
Front discharge is possible with an air
discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Drain pump is equipped as standard
Direct airflow type
accessory with 500 mm lift.
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings in hotels.
24˚C
1
Adding the plenum
chamber
(option)air discharge
Single-flow
type allows
effective
allows for simple operation with direct
from
corner or from drop-ceiling.
airflow.
* Note that the operation sound increases by
approximately 5 dB(A).
28˚C
32˚C 30˚C
2
FXDQ40NB / FXDQ50NB / FXDQ63NB
Indoor Unit Lineup
Indoor Unit Lineup
Large airflow type that fits for spacious areas such as factories
and large stores.
* 8 hr/day, 26 day/month. For dust concentration of 0.15
with connection to BP units
750 mm
(dB(A))
These models have750
themm
35/33/31
36/34/32 power to provide a
FCQ71B
comfortable airflow
Ceiling
values of operation sound level represent those for rear-suction operation.
33/29 dB (A) 35/30 dB (A) 35/30 dB (A)
33/29* The
dB
(A)
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).even with a ceiling
* Values are based on the following conditions:
height of up to 3.8 m.
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
40
Sound level
34/32/30
FCQ35B(HH/H/L)FCQ50B33/31/29FCQ60B
50
(H/L)
63
Max. 3.8 m
of 15 Pa.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
3125
Hotline: 0976 173 173
3226
Indoor
Indoor Unit
Unit Lineup
VRV IndoorIndoor
Units Units
Residential
with connection to BP units
Ceiling
Mounted
Built-inDuct
TypeType
Slim Ceiling
Mounted
CeilingMounted
MountedCassette
Cassette(Compact
Corner Type
Ceiling
Multi Flow) Type
Slim FBQ60B
design,
quietness and
/ FBQ71B
static pressure switching
FFQ25B / FFQ35B
FXKQ25MA
/ FXKQ32MA
FFQ50B
/
FFQ60B
FXKQ40MA / FXKQ63MA
Option
Suited to use in drop-ceilings!
Providing 3 different settings of standard, draft
prevention and ceiling soiling prevention, the
auto swing mechanism realises even
Option
Signal receiver unit
distribution of airflow
and room
temperature.
Note: Remote controller
Note: Wireless remote
Option
cables not included.
Cables should be
obtained locally. (m)
3
Min.195 mm
FXDQ20PB / FXDQ25PB / FXDQ32PB
Panel spacer
2
controllers and signal
receiver units are sold
as a set.
28˚C
32˚C 30˚C
26˚C
24˚C
Quiet, compact, and designed for user comfort
20 mm
Single-flow type allows effective air discharge
Designed to fit 600 mm wide ceiling grids
from corner or from drop-ceiling.
575 mm
575 mm
Drain pump is equipped as standard
accessory
with 500 mm lift.
286
mm
act
Comp e panel
tiv
decora
Comfortable across all areas
5 direction
T-bar grid does not need to be cut.
Air discharge grille (Option)
0
60
Auto-swing
between 0 and 60
0
60
Draft
Set for front discharge using a suspended ceiling.
prevention
0
0
setting
Auto-swing
Main
35
35 body
(Set on site)
between 0 and 35
Ceiling panel
T-bar
Setting to
prevent
soiling of
ceiling
600 mm
600 mm
Low operation sound level
(Set on site)
25
60
Auto-swing
between 25 and 60
25
60
FFQ25B
FFQ35B
FFQ50B
FFQ60B
29.5/24.5 dB (A)
32/25 dB (A)
36/27 dB (A)
41/32 dB (A)
Settable to 5 different levels
between 25 and 60
Drain pump is equipped as standard
accessory with 750 mm lift.
Downward discharge is shut off and air is blown straight out
(front discharge).
A long-life filter (maintenance free
up mm
to one
750
year*) is equipped as standard accessory.
In crawl space
6
Only
200 mm
700 mm
2 Air conditioner
4
350 mm or more
With canvas bellows and air intake panel (sold separately)
4
6
Air intake
Long-life filter
Long-life filter
5
13
2 Air conditioner
Air intake
Long-life filter
2 Air conditioner
450 mm or more
6
8
Air blow
4
9
540 mm or more
Air intake
Air filter
Air intake
8
5
Air blow
Options 1 Decorative panel
4
Air discharge opening adaptor
Canvas bellows and air intake panel
5
6
Flexible duct
Air discharge grille
Air discharge chamber
7
1
240 mm
With ordinary ducts
Ordinary duct
(procured locally)
11
11
Discharge
grille *
7
540 mm or more
7
3
Suspension
bolt*
5
Ceiling return with high-efficiency filter
AIR
5
2
4
Air blow
Ceiling return
4
* 1,100 mm
in width for the FXDQ63NB model.
2 Air conditioner
6
1
Air intake
Air blow
45 mm
With high-efficiency filter
425 mm or more
3
200 mm
900 mm
2 Air conditioner
1
5
Air blow
3
Settable to 5 different levels
between 0 and 35
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
3325
Flexible air discharge unit to
fit various forms of space
10
High-efficiency filter
460 mm or more
9
AIR
Air blow
10
Ordinary duct
(procured locally)
Air conditioner
Suction grille *
8
intake
* ToAirbe
obtained locally
Air discharge opening flange
11 Rear intake filter chamber
Inspection panel
External
static pressure selectable
by remote controller
12 Branch duct
9 Rear intake blocking pad
switching make this indoor
unit a very comfortable and
13 Low-draft filter chamber
flexible model.
8
Settable to 5 different levels
between 0 and 60
Air discharge grille
(Option)
Note: Angles shown above are provided as a guide. They
may differ depending on the installation site.
(H/L)
Only 200 mm in height, this model can be installed in
rooms with as little as 240 mm depth between the
drop-ceiling and ceiling slab.
The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab.
It also works with both flexible and ordinary ducts.
6
Conditioned air is distributed
Adjustable airflow angle to
evenly by Auto-swing operation.
suitdischarge
all room conditions.
Downward
Standard
setting
Great for
hotel use!
Standard installation examples
Main body
AUTO-SWING
700 mm
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings in hotels.
20˚C
Low draft performance
is2 3 4 5 6 (m)
0
1
0º
designed for your comfort.
0º Horizontal Flow
Front discharge is possible with an air
discharge unit (option), which
allows the
Less draught
installation in the drop-ceiling or sagging wall.
500 mm
700 mm
22˚C
1
FXDQ40NB / FXDQ50NB / FXDQ63NB
Indoor Unit Lineup
Slim design for flexible installation
Slim body needs only 220 mm space above the
ceiling. If you use a panel spacer (option), the
unit can be installed in the minimum space of
195 mm.
Note: Remote controller
cables not included.
Cables should be
obtained locally.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
Pa-44 Pa/factory
set: 15 Pa
FXDQ-NB models.
To cope with the challenges of L-shaped or
Drain15pump
is equipped
asforstandard
accessory with
U-shaped spaces, it is possible to install the air
250 mm lift.
FXDQ-PB and FXDQ-NB models are available in two
discharge unit away from the main unit. This
types to suit different installation conditions.
extends the possibilities for coping with human
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
Control patterns
of the airflow
rate lighting.
has beenAt
improved
from 2-step
gathering
or sun
the same
as a standard accessory
250 mm
to different
3-step control.
FXDQ-PB/NBVET: without a drain pump
time,
types of architectural space can be
keptLow
comfortable.
operation sound level
(dB(A))
FXDQ-PB/NB
20/25/32
40
50
63
Sound level
(HH/H/L)
33/31/29
34/32/30
35/33/31
36/34/32
750 mm
Low operation sound level
Ceiling
* The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
* Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure
of 15 Pa.room
L-shaped
U-shaped room
Long room
(H/L)
FBQ60B
FBQ71B
41/35 dB (A)
41/35 dB (A)
Hotline: 0976 173 173
3426
Indoor Unit
Unit
Lineup
Indoor
Outdoor
UnitLineup
Lineup
Outdoor
Units
withconnection
connectiontotoBPBPunits
units
Residential
IndoorUnits
Unitswith
Residential
Indoor
Cooling Only / Heat Pump
Lineup
WallMounted
MountedType
Type
Wall
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The singleCooling
outdoor
unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
Cooling
Only
Only
FDKS25EA
/ FDKS35EA
FDKS25EA
/ FDKS35EA
system flexibility to a new level.
FDKS25CA
/ FDKS35CA
FDKS25CA
/
FDKS35CA
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
FDKS50C
/
FDKS60C
FDKS50C
/
FDKS60C
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
Heat
Pump CDXS25EA
Heat
Pump
CDXS25EA
/ CDXS35EA
/ CDXS35EA
salt damage and atmospheric
pollution.
FDXS25C
/ FDXS35C
FDXS25C
/ FDXS35C
FDXS50C
/ FDXS60C
FDXS50C
/ FDXS60C
Double Outdoor Units
12, 14, 16 HP
Triple Outdoor Units
18, 20, 22, 24, 26, 28, 30, 32 HP
HP
Cooling
OnlyOnlyFTKS25D
FTKS25D/ FTKS35D
/ FTKS35D
High-COPCooling
Type
HeatHeat
Pump
PumpFTXS20D
FTXS20D
/ FTXS25E/ FTXS35E
/ FTXS35E
/ FTXS25E
Standard Type
Space Saving Type
Standard
accessory*
Standard
accessory*
Cooling
Cooling
OnlyOnlyFTKS50B
FTKS50B
Cooling
Cooling
OnlyOnlyFTKS50F
FTKS50F/ FTKS60F
/ FTKS60F/ FTKS71F
/ FTKS71F
HeatHeat
Pump
PumpFTXS50F
FTXS50F/ FTXS60F
/ FTXS60F/ FTXS71F
/ FTXS71F
34, 38 HP
Standard
accessory
Standard
accessory
New Lineup
36, 40 HP
42, 44, 46, 48, 50 HP
Standard
accessory*
Standard
accessory*
Note:
Remote
controllers
Note:
Remote
controllers
other
standard
other
thanthan
the the
standard
accessory
wireless
remote
accessory
wireless
remote
controller
cannot
be used.
controller
cannot
be used.
Slimand
andsmooth
smoothdesign
design
Slim
RX(Y)Q26THY1(E)
suitsyour
yourshallow
shallow
ceiling
suits
ceiling
RX(Y)Q34THY1(E)
RX(Y)Q28THY1(E)
RX(Y)Q18THY1(E)
RX(Y)Q20THY1(E)
RX(Y)Q38THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
Models
the
FDKS-EA
and
CDXS-EA
series
are
Models
in in
the
FDKS-EA
and
CDXS-EA
series
are
Low
operation
sound
level
Low
operation
sound
level
RX(Y)Q12THY1(E)
RX(Y)Q14THY1(E)
RX(Y)Q16THY1(E)
Standard
Standard
accessory*
accessory*
RX(Y)Q36THY1(E)
RX(Y)Q40THY1(E)
(H/L/SL)
(H/L/SL)
only
700
mm
width
and
weight,
are
only
700
mm
in in
width
and
2121
kgkg
in in
weight,
soso
are
FDKS25 FDKS35
FDKS35 FDKS50
FDKS50 FDKS60
FDKS60
FDKS25
easily
installed
in
limited
spaces.
Just
200
mm
in
easily
installed
in
limited
spaces.
Just
200
mm
in
Standard Type
C(F)DXS25 C(F)DXS35
C(F)DXS35 FDXS50
C(F)DXS25
FDXS60
FDXS50 FDXS60
height,
models
can
installed
in
rooms
with
height,
allall
models
can
bebe
installed
in
rooms
with
Double
Outdoor
Units
Single
Outdoor
Units
35/31/29
35/31/29
dBdB
(A)(A)35/31/29
35/31/29
dBdB
(A)(A)37/33/31
38/34/32
37/33/31
dBdB
(A)(A)
dBdB
(A)(A)38/34/32
as
little
as
240
mm
depth
between
the
drop
as
little
as
240
mm
depth
between
the
drop
6, 8, 10, 12 HP
14, 16 HP
22, 24, 26 HP
18, 20 HP
28, 30, 32 HP
ceiling
and
ceiling
slab,
making
them
ideal
ceiling
and
ceiling
slab,
making
them
ideal
forfor
Home
Leave
Operation
prevents
large
rises
falls
Home
Leave
Operation
prevents
large
rises
or or
falls
in in
even
shallow
ceilings. FDKS-EA
even
shallow
ceilings.
FDKS-EA
indoor
temperature
continuing
operation*
while
thethe
indoor
temperature
byby
continuing
operation*
while
CDXS-EA
CDXS-EA
Great
Great
forfor
you
sleeping
your
home.
This
means
that
you
areare
sleeping
or or
outout
of of
your
home.
This
means
that
hotel
use!
hotel
use!
air-conditioned
welcome
awaits
when
you
wake
anan
air-conditioned
welcome
awaits
when
you
wake
or or
return.
It also
means
that
indoor
temperature
can
return.
It also
means
that
thethe
indoor
temperature
can
quickly
return
your
favourite
comfort
setting.
quickly
return
to to
your
favourite
comfort
setting.
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
200
mm
200
mm
RX(Y)Q18TNY1(E)
RX(Y)Q20TNY1(E)
RX(Y)Q14TY1(E)
RX(Y)Q16TY1(E)
Only
700
mm
Only
700
mm
RX(Y)Q22TNY1(E)
* Home
Leave
Operation
selected
any
temperature
from
* Home
Leave
Operation
cancan
be be
selected
for for
any
temperature
from
18 18
to to
RX(Y)Q28TNY1(E)
32˚C
for
cooling
operation
to 30˚C
heating
operation.
32˚C
forRX(Y)Q24TNY1(E)
cooling
operation
andand
10 10
to 30˚C
for for
heating
operation.
RX(Y)Q30TNY1(E)
* Home
Leave
Operation
function
must
using
remote
controller
* Home
Leave
Operation
function
must
be be
setset
using
thethe
remote
controller
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
when
going
to sleep
or leaving
house,
after
waking
or returning
when
going
to sleep
or leaving
thethe
house,
andand
after
waking
up up
or returning
home.
home.
FDKS25EAFDKS35EA
FDKS35EAFDKS25CA
FDKS25EA
FDKS35CA
FDKS25CAFDKS35CA
CDXS25EACDXS35EA
CDXS35EAFDXS25C
CDXS25EA
FDXS35C
FDXS25C FDXS35C
Suspension
Suction
duct*
Suspension
bolt*bolt*Suction
duct*
Air discharge
duct*
Air discharge
duct*
x 900
x 620
x 900
x 620
mmmm
Dimensions
x 700
x 620
Dimensions
(H x(HWx xWD)x D) 200200
x 700
x 620
mmmm 200200
Air filter
Air filter
Space
Saving Type 21 21
Air discharge
grille*
Air discharge
grille*
25 25
kg kg
Weight
Weight
kg kg
3/min
Airflow
m3/min
Airflow
raterate
(H) (H)
8.78.7
m3/min
Single
Outdoor
Units
m3/min10 10
m3/min
9.59.5
m3/min
mOutdoor
Double
Units
AIR
AIR
30 30
Pa Pa
40 40
Pa Pa
External
static
pressure
External
static
pressure
18, 20 HP
22, 24 HP
240
mm
240
mm
RX(Y)Q22TSY1(E)
RX(Y)Q24TSY1(E)
Signals
from
wireless
remote
controller
Signals
from
thethe
wireless
remote
controller
areare
transmitted
to the
signal
receiver.
transmitted
to the
signal
receiver.
133535
Air suction
Air suction
grille*
grille*
Notes:
Notes:
1. prevent
To prevent
an increase
in operation
noise,
avoid
1. To
an increase
in operation
noise,
avoid
Option
Option
installing
air suction
grille
directly
below
installing
the the
air suction
grille
directly
below
the the
suction
chamber.
suction
chamber.
2. Grilles,
piping
connections,
ducts,
installation
2. Grilles,
piping
connections,
ducts,
andand
installation
parts
should
be obtained
locally.
Ceiling
parts
should
be obtained
locally.
SlimSlim
Ceiling
Mounted
Duct
models
do not
have
drain-up
Mounted
Duct
typetype
models
do not
have
drain-up
RX(Y)Q26TSY1(E)
RX(Y)Q30TSY1(E)
Suction
grille
(KDGF19A45)
Suction
grille
(KDGF19A45)
pumps.
pumps.
RX(Y)Q28TSY1(E)
RX(Y)Q32TSY1(E)
3. The
signal
receiver
must
be located
3. The
signal
receiver
unitunit
must
be located
nearnear
the the
air suction
inlet,
because
includes
air suction
inlet,
because
the the
unitunit
includes
a a
sensor
detects
room
temperature.
sensor
thatthat
detects
room
temperature.
Titanium
apatite
a photocatalytic
material
with
Titanium
apatite
is is
a photocatalytic
material
with
high
adsorption
power.
Titanium
apatite
also
high
adsorption
power.
Titanium
apatite
also
effectively
adsorbs
and
bacteria
adsorbs
decomposes
(H/L/SL)
(H/L/SL)
42,
44 HP effectively
46,and
48,
50,decomposes
52, 54, 56,bacteria
58,
60 HP
38, 40 HP
34, 36 HP
across
its
entire
surface.
The
photocatalyst
across
its
entire
surface.
The
photocatalyst
is is
FTK(X)S35FTK(X)S50
FTK(X)S50FTK(X)S60
FTK(X)S60FTK(X)S71
FTK(X)S71
FTK(X)S20/25FTK(X)S35
FTK(X)S20/25
activated
simply
exposure
light.
activated
simply
byby
exposure
to to
light.
39/26/23
43/34/31
45/36/33
46/37/34
37/25/22
39/26/23
dB dB
(A) (A)43/34/31
dB dB
(A) (A)45/36/33
dB dB
(A) (A)
46/37/34
dB dB
(A) (A)
37/25/22
dB dB
(A)(A)
Wall
Mounted
indoor
units
achieve
quiet
sound
Wall
Mounted
indoor
units
achieve
quiet
sound
Triplelevels
Outdoor
Units
levels
during
cooling
operation.
of of
2222
dBdB
(A)(A)
during
cooling
operation.
Intelligent
Eye
with
infrared
sensor
Intelligent
Eye
with
itsits
infrared
sensor
automatically
controls
conditioner
operation
automatically
controls
airair
conditioner
operation
according
human
movement
a room.
When
according
to to
human
movement
in in
a room.
When
there
movement,
it adjusts
the
temperature
there
is is
nono
movement,
it adjusts
the
temperature
2˚C
energy
savings.
byby
2˚C
forfor
energy
savings.
RX(Y)Q42TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q34TNY1(E)
RX(Y)Q36TNY1(E)
RX(Y)Q46TNY1(E)
RX(Y)Q48TNY1(E)
RX(Y)Q50TNY1(E)
RX(Y)Q52TNY1(E)
Titanium
Apatite
Titanium
Apatite
RX(Y)Q44TNY1(E)
RX(Y)Q40TNY1(E)
filter
AirAir
filter
Catches
dust
Catches
dust
RX(Y)Q54TNY1(E)
RX(Y)Q56TNY1(E)
RX(Y)Q58TNY1(E)
RX(Y)Q60TNY1(E)
Photocatalytic
Photocatalytic
Air-purifying
Filter
Air-purifying
Filter
34, 36, 38, 40 HP
3-D
Airflow
3-D
Airflow
combines
Vertical
combines
Vertical
and
Horizontal
and
Horizontal
Auto-Swing
Auto-Swing
to to
circulate
every
circulate
airair
to to
every
part
a room
part
of of
a room
forfor
uniform
cooling
even
uniform
cooling
of of
even
large
spaces.
large
spaces.
RX(Y)Q34TSY1(E) RX(Y)Q38TSY1(E)
When
in the
room
When
youyou
areare
in the
room
* Locally
obtained
parts
obtained
parts
AIR * Locally
AIR
RX(Y)Q18TY1(E)
RX(Y)Q20TY1(E)
Stylishflat
flatpanel
panelharmonises
harmoniseswith
withyour
yourinterior
interiordécor
décor
Stylish
Double Outdoor Units
26, 28, 30, 32 HP
Chamber
Chamber
Signal
receiver
Signal
receiver
wirewire
=
=
Length1,900
1,900
Length
mmmm Signal
Signal
receiver
receiver
RX(Y)Q42THY1(E)
RX(Y)Q48THY1(E)
* Remote
controllers
other
standard
accessory
wireless
remote
controller
cannot
be used.
* Remote
controllers
other
thanthan
the the
standard
accessory
wireless
remote
controller
cannot
be used.
RX(Y)Q44THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q46THY1(E)
Indoor Unit Lineup
Indoor Unit Lineup
High-COP Type
Mo/C
Outdoor Unit Lineup
Slim
Ceiling
Mounted
Duct
Type
Slim
Ceiling
Mounted
Duct
Type
The
outdoor
unit
capacity
is up
to 60 HP in increment of 2 HP.
RX(Y)Q36TSY1(E)
* This
function
is available
* This
function
isRX(Y)Q40TSY1(E)
available
forfor
FTK(X)S50/60/71F.
FTK(X)S50/60/71F.
These
filters
are
not
medical
devices.
Benefits
These
filters
are
not
medical
devices.
Benefits
Triple Outdoor Units
42, 44 HP
When
When
youyou
go go
outout
such
the
adsorption
and
decomposition
such
asas
the
adsorption
and
of of
46, 48, 50
HPdecomposition
bacteria
are
only
effective
substances
that
are
bacteria
are
only
effective
forfor
substances
that
are
collected
and
direct
contact
with
the
Titanium
collected
onon
and
in in
direct
contact
with
the
Titanium
Apatite
Photocatalytic
Air-Purifying
Filter.
Apatite
Photocatalytic
Air-Purifying
Filter.
Bacteria
Removal
Test
Bacteria
Removal
Test
Testing
method:
dropping
method
Testing
method:
dropping
method
Result
certificate:
012553-1
012553-2
Result
certificate:
No.No.
012553-1
andand
012553-2
Testing
organisation:
Japan
Spinners
Inspecting
Foundation
Testing
organisation:
Japan
Spinners
Inspecting
Foundation
RX(Y)Q42TSY1(E)
RX(Y)Q44TSY1(E)
A uniform
temperature
A uniform
temperature
is achieved
throughout
is achieved
throughout
thethe
entire
room.
entire
room.
RX(Y)Q46TSY1(E)
RX(Y)Q48TSY1(E)
RX(Y)Q50TSY1(E)
Hotline: 0976 173 173
143636
Specifications
Indoor Unit
Outdoor
UnitLineup
Lineup
Outdoor
UnitsUnits
Residential
Indoor Units with connection to BP units
VRV
Indoor
Cooling Only / Heat Pump
FDXS25C / FDXS35C
Heating capacity
FDXS50C
/ FDXS60C
High-COP Type
consumption
Double Outdoor Power
Units
12, 14, 16 HP
Cooling
3,400
4,300
5,400
6,900
8,600
10,800
13,800
Btu/h
10,900
13,600
17,100
21,500
27,300
34,100
42,700
54,600
kW
3.2
4.0
5.0
6.3
8.0
10.0
12.5
16.0
kW
0.031
0.031
0.041
Triple kW
Outdoor
Units
0.027
0.027
0.037
18, 20, 22, 24, 26, 28, 30, 32 HP
Airflow rate (H/M/L)
Sound level (H/M/L)
Dimensions (H×W×D)
Machine weight
RX(Y)Q12THY1(E)
RX(Y)Q14THY1(E)
RX(Y)Q16THY1(E) Panel
2,800
Heating
Casing
Piping
connections
kcal/h
0.095
0.095
0.194
0.219
0.075
0.090
0.090
0.180
0.199
34,
38plate
HP
Galvanised
steel
Standard accessory
mm
kg
mm
DrainRX(Y)Q18THY1(E)
246×840×840
19
23
9.5
3.2
200
RX(Y)Q14TY1(E)
RX(Y)Q18TNY1(E)
Cooling
kW mm 0.033
Power consumption
RX(Y)Q16TY1(E)
RX(Y)Q20TNY1(E)
Only 700 mm
0.027
Heating
kW
Casing
4.0
5.0
6.3
8.0
10.0
12.5
Piping
connections
Panel
(Option)
Gas (Flare)
240 mmmm
Drain
Model
Weight
RX(Y)Q18TY1(E)
RX(Y)Q20TY1(E)
36, 40 HP
16.0
mm
kg
9.5
15.9
12.7
Chamber
suction
Signal receiver
VP25 (External
Dia,wire
32/Internal Dia, 25) Air
grille*
Length = 1,900 mm
Signal
BYCP125K-W1 receiver
Option
Fresh white
Notes:
AIR
* Locally obtained parts
1. To prevent an increase in operation noise, avoid
950
50X950X
installing the air suction grille directly below the
5.5 suction chamber.
FTKS50B
1,900
2,400
kcal/h
7,500
3,100
3.6
2.8
3,400
2,800
8,500
13,600
10,900
2.5
4.0
3.2
0.073
0.076
0.064
0.068
42, 44, 46, 48, 50 HP
Casing
m3/min
Sound level (H/L) 230 V
Liquid (Flare)
Model
FXZQ40MVE
12,300
9,600
2,200
Btu/h
FXZQ32MVE
1-phase, 220-240 V/220 V, 50/60 Hz
2.2
FTKS50F / FTKS60F
kW
Cooling / FTKS71F
Power consumption
kW
FTXS50F / FTXS60F
Heating/ FTXS71F
Airflow rate (H/L)
Galvanised steel plate
9/7
9.5/7.5
FXZQ50MVE
4,800
3,900
15,400
4.5
19,100
Standard accessory*
5.6
5,400
4,300
21,500
17,100
6.3
5.0
0.115
0.089
0.080
0.107
Standard accessory*
11/8
14/10
cfm
318/247
335/265
388/282
493/353
dB(A)
30/25
32/26
36/28
41/33
mm
286×575×575
Standard
accessory*
18
kg
6.4
mmRX(Y)Q42THY1(E)* Remote
12.7 accessory wireless remote controller cannot be used.
RX(Y)Q48THY1(E)
controllers other than the standard
RX(Y)Q44THY1(E) RX(Y)Q50THY1(E)
VP20 (External Dia, 26/Internal Dia, 20)
RX(Y)Q46THY1(E)
BYFQ60B8W1
Stylish flat panel harmonises with your interior décor
Panel
(Option)
White (6.5Y9.5/0.5)
Colour
Dimensions(H×W×D)
mm
Weightachieve kg
Wall Mounted indoor units
quiet sound
Triple Outdoor
Units
levels of 22 dB (A) during cooling operation.
(H/L/SL)
42,
44 HP
38, 40 HP
34, 36 HP
4-way Flow Ceiling Suspended Type
FTK(X)S20/25 FTK(X)S35 FTK(X)S50 FTK(X)S60 FTK(X)S71
55×700×700
Titanium apatite
2.7is a photocatalytic material with
high adsorption power. Titanium apatite also
effectively adsorbs
and
bacteria
46, 48,
50,decomposes
52, 54, 56, 58,
60 HP
across its entire surface. The photocatalyst is
activated simply by exposure to light.
MODEL
FXUQ71AVEB
dB (A) 45/36/33 dB (A) 46/37/34 dB (A)
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31
Power supply
RX(Y)Q40TNY1(E)
kW
RX(Y)Q36TNY1(E)
Power consumption
Cooling
kW
Heating
kW
Casing
Airflow rate (H/M/L)
Double Outdoor Units
FXUQ100AVEB
1-phase, 220-240 V/220-230 V, 50/60 Hz
Intelligent Eye with its infrared sensor
kcal/h
6,900
automaticallyCooling
controls
air conditioner
capacity
Btu/hoperation
27,300
according to human movement in akWroom. When
8.0
there is no movement, it adjusts the
temperature
kcal/h
7,700
by 2˚C for energy
Btu/h
Heatingsavings.
capacity
30,700
RX(Y)Q42TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q34TNY1(E)
Sound level (H/M/L)
0.073
11.2
10,800
RX(Y)Q46TNY1(E)
RX(Y)Q48TNY1(E)
RX(Y)Q50TNY1(E)
RX(Y)Q52TNY1(E)
Titanium Apatite
RX(Y)Q44TNY1(E)
9.0
0.090
9,600
38,200
Photocatalytic
Fresh
white
Air-purifying
Filter
Air filter
Catches dust
42,700
RX(Y)Q54TNY1(E)
RX(Y)Q56TNY1(E)
12.5
RX(Y)Q58TNY1(E)
0.200
RX(Y)Q60TNY1(E)
0.179
31/26/21
m3/min
22.5/19.5/16
cfm
794/688/565
1,094/918/741
dB(A)
40/38/36
47/44/40
These filters are not medical devices. Benefits
Triple Outdoor Units
such as the adsorption
34, 36, 38, 40 Dimensions
HP
42, 44 HP
46, 48, 50 and
HP decomposition of
198×950×950
mm
(H×W×D)
bacteria
are
only
effective
for substances
that are
3-D Airflow Machine weight
27
kg
26
collected
on
and
in
direct
contact
with
the
Titanium
combines Vertical
9.5
Liquid (Flare)
Piping
Apatite
Photocatalytic
Air-Purifying
Filter.
and Horizontal
mm
15.9
Gas (Flare)
connections
Auto-Swing to
Drain
VP20 Removal
(ExternalTest
Dia, 26/Internal Dia, 20)
Bacteria
circulate air to every
Testing method: dropping method
Result
certificate:
No.length:
012553-1
and
012553-2
Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB,
Equivalent
piping
7.5 m,
Level
difference: 0 m.
part of a room for•• Heating:
Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB,
Equivalent
piping length:
7.5 Spinners
m, Level difference:
m.
Testing
organisation:
Japan
Inspecting0 Foundation
• Capacity
uniform cooling of
evenof indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
RX(Y)Q46TSY1(E)
large spaces.
RX(Y)Q42TSY1(E)
RX(Y)Q34TSY1(E)
RX(Y)Q38TSY1(E)
• Sound level: Anechoic chamber conversion
value, measured at a point 1.5 m downward from the
unit centre.
When you are in the room
When you go out
RX(Y)Q44TSY1(E)
RX(Y)Q36TSY1(E)
During actual operation, these
values are normally somewhat higher as a result ofRX(Y)Q48TSY1(E)
ambient conditions.
* This functionRX(Y)Q40TSY1(E)
is available for
A uniform temperature
RX(Y)Q50TSY1(E)
is achieved throughout
FTK(X)S50/60/71F.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
FXZQ25MVE
kW
kW
Piping
2. Grilles, piping connections, ducts, and installation
parts should be obtained locally. Slim Ceiling
Mounted
type
models do
not have drain-up
• Cooling: Indoor temp.: 27°CDB,
19°CWB, Outdoor temp.: 35°CDB, Equivalent
piping length:
7.5 m, Duct
Level
difference:
0 m.
RX(Y)Q22TSY1(E)
RX(Y)Q26TSY1(E)
RX(Y)Q30TSY1(E)
Suction grille (KDGF19A45)
Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: pumps.
7.5 m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB,
RX(Y)Q24TSY1(E)
RX(Y)Q32TSY1(E)
3.total
The signal
receiver
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit RX(Y)Q28TSY1(E)
is based on the
capacity
index.unit must be located near the
air suction inlet, because the unit includes a
(See Engineering Data Book for details.)
sensor
remote
are chamber conversion value, measured at a point 1.5 m downward from
Soundcontroller
level: Anechoic
the that
unit detects
centre. room temperature.
Signals from the wireless •
transmitted to the signal receiver.
133735
6.4
Cooling Only
Gas (Flare)
RX(Y)Q36THY1(E)
connections
RX(Y)Q40THY1(E)
Drain
32˚CRX(Y)Q24TNY1(E)
for cooling operation and 10 to 30˚C for
heating operation.
RX(Y)Q30TNY1(E)
0.027
0.034Operation
0.038
0.053
0.075
0.200
* Home
Leave
function
must be set
using the0.174
remote controller
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
when going toGalvanised
sleep or leaving
the
house,
and
after waking up or returning
steel plate
home.
Colour
Dimensions(H×W×D)
Cooling Only
Heat Pump
FXZQ20MVE
Btu/h
Machine weight
RX(Y)Q22TNY1(E)
* Home
Leave
can be0.066
selected for
any temperature
18 to
RX(Y)Q28TNY1(E)
0.033
0.047Operation
0.052
0.093
0.187 from0.209
26, 28, 30, 32 HP
Cooling capacity
Dimensions (H×W×D)
FDKS25EA FDKS35EA FDKS25CA
FDKS35CA
13/11.5/10 13/11.5/10 15/13/11 16/13.5/11 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5
m3/min
Airflow
rate CDXS35EA
(HH/H/L) FDXS25C FDXS35C
CDXS25EA
cfm 459/406/353 459/406/353
530/459/388
671/583/477
742/636/530
1,130/918/706 1,165/989/794
Suspension
bolt* Suction
duct*
Air discharge
duct*565/477/388
Dimensions (H x W x D) 200 x 700 x 620 mm 200 x 900 x 620 mm
Air filter
Space
Saving
Type
dB(A) 30/28.5/27 30/28.5/27
Sound level (HH/H/L)
31/29/27
32/29.5/27
34/31/28
36/33.5/31
43/37.5/32
44/39/34
Air
discharge
grille*
25 kg
Weight
21 kg
X840X840
246
mm
Dimensions
(H×W×D)
X
X840
840
288
3
3
3
Airflow rate
(H)
8.7 m /min
Single
Outdoor
Units
9.5
m /min 10Outdoor
m /min
Double
Units AIR
weight
19.5
22
25
Pa
40kgPa
External static pressure Machine30
22, 24 HP
Liquid (Flare)
MODEL
FTKS25D
Power supply/ FTKS35D
kcal/h
FTXS20D / FTXS25E / FTXS35E
Heating capacity
26
Slim12.7and smooth design
15.9
RX(Y)Q26THY1(E)
I.D. 25×O.D. 32(VP25)
suits yourBYCQ125B-W1
shallow
ceiling
RX(Y)Q34THY1(E)
RX(Y)Q28THY1(E)
6.4
RX(Y)Q20THY1(E)
Model
RX(Y)Q38THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
Fresh white
Colour
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
and CDXS-EA
series are
Low operation sound level
kW
18, 20 HP
Space Saving Type
288×840×840
Models in the FDKS-EA
(Option)
(H/L/SL)
50×950×950
Dimensions(H×W×D) mm
only 700 mm in width and 21
kg in weight,
so are
5.5
kg
Weight
FDKS25
FDKS35
FDKS50
FDKS60
easily installed
Standard
Type in limited spaces. Just 200 mm in
C(F)DXS25 C(F)DXS35 FDXS50
FDXS60
height,
all models
can be installed
in rooms
withTypeUnits
Double
Outdoor
Single
Outdoor
Units
Ceiling
Mounted
Cassette
(Round
Flow)
35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
as
little
as
240
mm
depth
between
the
drop
6, 8, 10, 12 HP
14, 16 HP
22, 24, 26 HP
18, 20 HP
28, 30, 32 HP
ceiling and ceiling slab, making
them
ideal
for
FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1 FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1 FXFQ125LUV1
MODEL
Home Leave
Operation
large rises or falls in
Power supply
1-phase,
220-240 V,prevents
50 Hz
even shallow ceilings.
FDKS-EA
the indoor
by continuing
operation*
while
6,100
7,700
9,600
12,000
2,400
3,100
3,900 temperature
4,800
kcal/h
CDXS-EA
Great for
Cooling capacity
9,600
12,300
15,400
19,100
38,200means
Btu/h
47,800
you are
sleeping
or out
of your30,700
home. This
that
24,200
hotel use!
2.8
3.6
4.5
5.6 welcome
kW
9.0 when
11.2
7.1 awaits
14.0 or
an air-conditioned
you wake
2,800
3,400
5,400
kcal/h
6,900
8,600
10,800 13,800
return.4,300
It also means
that
the indoor
temperature
can
13,600
17,100
21,500 27,300
Btu/h 10,900
Heating capacity
34,100
42,700 54,600
quickly return to your favourite comfort setting.
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
Cooling Only
High-COP Type
Heat Pump
Standard Type
Note:33.0/26.0/19.0
Remote controllers
34.5/27.5/21.0
m3/min 12.5/11.5/10.0 12.5/11.5/10.0 14.5/13.0/11.0 22.0/17.5/13.5 23.5/18.5/13.5 23.5/19.5/15.0
other than the standard
cfm 441/406/353 441/406/353 512/459/388 777/618/477 830/653/477 830/688/530
1,165/918/671
1,218/971/741
accessory
wireless
remote
controller cannot be used.
dB(A) 30/28.5/27 30/28.5/27 31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35
Liquid (Flare)
Gas (Flare)
0.080
HP
New Lineup
Specifications
Indoor Unit Lineup
VRV IV outdoor unit offers a higher capacity
of up to 60 HP,FXFQ25SVM
responding
to theFXFQ40SVM
needs ofFXFQ50SVM
large-sized
building.
FXFQ32SVM
FXFQ63SVM
FXFQ80SVM FXFQ100SVM FXFQ125SVM
MODEL
The single outdoor
unit
has
only
2
different
shapes
and
dimensions,
not
only
simplifying
the
design
process,
but also bringing the
Power supply / FDKS35EA
Cooling Only FDKS25EA
1-phase, 220 -240 V/220-230 V, 50/60 Hz
system flexibility to a new level.
kcal/h
4,800
3,100
3,900
7,700
9,600
12,000
6,100
2,400
FDKS25CA / FDKS35CA
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Cooling capacity
12,300
15,400 19,100
30,700
38,200 47,800
24,200
9,600
Btu/h
FDKS50C
/
FDKS60C
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
7.1
5.6
3.6
4.5
2.8
9.0
11.2
14.0
Heat Pump CDXS25EA / CDXS35EAkW
salt damage and atmospheric
pollution.
Mo/C
Outdoor Unit Lineup
Lineup
Wall Mounted
Ceiling
MountedType
Cassette (Compact Multi Flow) Type
Ceiling
Mounted
Cassette
with
Sensing)ofType
Slim
Ceiling
Mounted
Duct
The
outdoor
unit
capacity
is(Round
upType
to 60Flow
HP in
increment
2 HP.
the entire room.
Hotline: 0976 173 173
143836
Indoor Unit
Outdoor
UnitLineup
Lineup
Specifications
Outdoor
UnitsUnits
Residential
Indoor Units with connection to BP units
VRV
Indoor
Cooling Only / Heat Pump
Lineup
WallCeiling
Mounted
Type Duct Type (700 mm width type)
Slim
Mounted
2,200
FDXS25C / FDXS35C
Btu/h
FDXS60C
Heating
capacity/
FDXS50C
High-COP Type
Power consumption
Double Outdoor
Units
12, 14, 16 HPCasing
8,500
kW
Cooling
kW
0.077
3.2
4.0
0.092
0.092
4,300
17,100
5.0
0.130
0.097
5,400
6,900
21,500
27,300
6.3
8.0
0.130
0.161
0.097
0.126
34,plate
38 HP
18, 20, 22, 24, 26, 28, 30, 32 HPGalvanised steel
m /min
7/5
3
Airflow rate (HH/M/L)
cfm
dB(A)
220 V
mm
Dimensions (H×W×D)
9/6.5
9/6.5
12/9
12/9
247/177
318/230
318/230
424/318
424/318
32/27
34/28
34/28
34/29
34/29
26.0
26.0
26.0
31.0
32.0
RX(Y)Q14THY1(E)
RX(Y)Q16THY1(E)
Panel
Colour
13,800
54,600
10.0
16.0
0.209
0.256
0.176
0.223
Standard accessory
16.5/13 Note:26/21
33/25
Remote controllers
47.0
RX(Y)Q38THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
White (10Y9/0.5)
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
CDXS-EA
series are
Low operation sound level
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
0.066
200 mm
0.046
kW
RX(Y)Q18TNY1(E)
kW
RX(Y)Q14TY1(E)
Heating
RX(Y)Q16TY1(E)
Casing
Only 700 mm
RX(Y)Q20TNY1(E)
11/9
m3/min
cfm
388/318
FDKS25EA FDKS35EA FDKS25CA
FDKS35CA
CDXS25EA
FDXS25C FDXS35C
Sound
level (H/L)CDXS35EA
220 V dB(A)
38/33
x 620
mm
Dimensions (H x W x D)
200 x 700
x 620 mm 200
X1,110X710
Dimensions
(H×W×D)
mm x 900215
Airflow rate (H/L)
Space
Saving Type
Weight
25 kg 31
9.5
m3/min 10Outdoor
m3/min
Double
6.4
40 Pa 12.7
21 kg
Machine weight
kg
Airflow rate
(H)
8.7Liquid
m /min
Single
Outdoor
Units
(Flare)
3
Piping
External static pressure
18, 20 HP
30 Pa
connections Gas (Flare)
Drain
Model
Panel
(Option)
Colour
mm22,
24 HP
mm
0.076
0.105
RX(Y)Q22TNY1(E)
* Home
Leave
any temperature
from 18 to
0.046Operation can be selected
0.056 forRX(Y)Q28TNY1(E)
0.085
32˚CRX(Y)Q24TNY1(E)
for cooling operation and 10 to 30˚C for
heating operation.
RX(Y)Q30TNY1(E)
Galvanised steel plate
* Home
Leave Operation function must be set using the remote controller
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
11/9to sleep or leaving the
13/10
18/15
when going
house, and after waking
up or returning
home. 388/318
459/353
635/530
38/33
Air discharge duct*
215X1,110X710
Air discharge grille*
31
Units AIR
6.4
12.7
40/34
Suspension bolt*
Suction duct*
215X1,110X710
31
70X1,240X800
9.5
12.732 HP
26, 28, 30,
BYK45FJW1 Chamber
Signal receiver wire
White
(10Y9/0.5)
Length = 1,900
mm
Signal
receiver
70X1,240X800
70X1,240
X800
AIR
15.9
BYK71FJW1
Air suction
grille*
*70
Locally
obtained
X1,440
X800parts
Notes: 8.5
9.5
1. To prevent an increase in operation noise, avoid
Option
Note: Specifications are based on the following conditions;
installing the air suction grille directly below the
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5suction
m, Level
difference: 0 m.
chamber.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 2.
m,Grilles,
Level difference:
0 m. ducts, and installation
piping connections,
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity
index.
parts should be obtained locally. Slim Ceiling
(See Engineering Data Book for details.)
Mounted Duct type models do not have drain-up
RX(Y)Q18TY1(E) •Sound level: (FXCQ-M) AnechoicRX(Y)Q22TSY1(E)
RX(Y)Q26TSY1(E)
RX(Y)Q30TSY1(E)
chamber conversion value, measured
at a (KDGF19A45)
point
1.5 m downward
from the
unit centre.
Suction grille
pumps.
(FXKQ-MA) Anechoic
chamber conversion value, measured at a point
1 m in front of the unitRX(Y)Q32TSY1(E)
and 1 m downward.
RX(Y)Q24TSY1(E)
RX(Y)Q20TY1(E)
RX(Y)Q28TSY1(E)
3. The signal receiver unit must be located near the
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
air suction inlet, because the unit includes a
sensor that detects room temperature.
Signals from the wireless remote controller are
Weight
kg
8.5
8.5
transmitted to the signal receiver.
133935
Cooling capacity
Cooling Only
FTKS50B
1,900
Btu/h
7,500
Heating
Cooling
Heating
External static pressure
1 3
Dimensions (H×W×D)
RX(Y)Q36THY1(E)
Machine weight
RX(Y)Q40THY1(E)
Liquid (Flare)
FXDQ25PBVE
FXDQ25PBVET
1-phase, 220-240 V/220 V, 50/60 Hz
FXDQ32PBVE
FXDQ32PBVET
3,100
2,400
Standard accessory*
12,300
9,600
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
2.5
3.2
4.0
0.086
0.086
0.089
0.067
0.067
FTKS50F / FTKS60F /
Cooling
kW
Power consumption
FTXS50F
/ FTXS60F
/ FTXS71F
(FXDQ-PBVE) 1
Power consumption
(FXDQ-PBVET) 1
FXDQ20PBVE
FXDQ20PBVET
kcal/h
kW
FTKS71F
Sound level (HH/H/L)
kW
kW
42, 44, 46,0.067
48, 50 HP
0.070
Standard accessory*
0.067
0.070
kW
0.067
m3/min
8.0/7.2/6.4
8.0/7.2/6.4
8.0/7.2/6.4
282/254/226
282/254/226
282/254/226
dB(A)
33/31/29
33/31/29
mm
200×700×620
200×700×620
200×700×620
23.0
23.0
cfm
0.067
Galvanised steel plate
Pa
30-10
0.070
2
Standard
accessory*
33/31/29
RX(Y)Q42THY1(E)* Remote
RX(Y)Q48THY1(E)
controllers other than the standard accessory wireless remote controller cannot be used.
kg RX(Y)Q44THY1(E)
23.0 RX(Y)Q50THY1(E)
6.4
RX(Y)Q46THY1(E)
6.4
6.4
Stylish flat panel harmonises with your interior décor
Piping
Gas (Flare)
connections
Drain
mm
Cooling capacity
Btu/h
12.7
12.7
12.7
VP20 (External Dia, 26/Internal Dia, 20)
apatite is a photocatalytic material with
Mounted
indoor units
achieve
sound
Slim Wall
Ceiling
Mounted
Duct
Typequiet
(900/1,100
mmTitanium
width type)
Triple Outdoor
Units
high
adsorption
power. Titanium apatite also
levels of 22 dB (A) during cooling operation.
FXDQ40NBVE effectivelyFXDQ50NBVE
FXDQ63NBVE
with drain pump
adsorbs
and
bacteria
(H/L/SL)
MODEL
42,
44 HP
46, 48,
50,decomposes
52, 54, 56, 58,
60 HP
38, 40 HP without drain pump
34, 36 HP
FXDQ40NBVET
FXDQ50NBVET
FXDQ63NBVET
across
its
entire
surface.
The
photocatalyst
is
FTK(X)S50 FTK(X)S60 FTK(X)S71
FTK(X)S20/25 FTK(X)S35
Power supply
1-phase, 220-240 V/220 V, 50/60 Hz
activated simply by exposure to light.
4,800
6,100
kcal/h
dB (A) 46/37/34 dB3,900
(A)
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33
15,400
Intelligent Eye with its infrared sensor
kW
4.5
automatically controls air conditioner
kcal/hoperation 4,300
Heating capacity
17,100
according to human
movement in Btu/h
a room. When
kWtemperature5.0
there is no movement, it adjusts the
Cooling
0.160
kW
Power consumption
by 2˚C for energy
savings.
RX(Y)Q42TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q34TNY1(E)
RX(Y)Q36TNY1(E)
(FXDQ-PBVE)
1
Heating
kW
RX(Y)Q40TNY1(E)
Power consumption
(FXDQ-PBVET) 1
Cooling
Heating
kW
kW
Airflow rate (HH/H/L)
Double Outdoor
External Units
static pressure
m3/min
cfm
19,100
10.5/9.5/8.5
371/335/300
24,200
5.6
7.1
5,400
6,900
21,500
27,300
6.3
0.165
RX(Y)Q46TNY1(E)
0.152
0.147
RX(Y)Q44TNY1(E)
RX(Y)Q48TNY1(E)
RX(Y)Q50TNY1(E)
0.152
0.147
RX(Y)Q52TNY1(E)
0.152
0.147
Titanium Apatite
Casing
Air 215
filter X1,310X710
34
FTKS25D /
Power supply
FTXS20D
/ FTXS25E / FTXS35E
Airflow rate (HH/H/L)
42/37
6.4
VP25 (External Dia, 32/Internal Dia, 25)
240 mm
Dimensions(H×W×D)
0.066
without drain pump
FTKS35D
Casing
48.0
9.5
9.5
Slim and smooth design
15.9
15.9
suits your
shallow
ceiling
RX(Y)Q34THY1(E)
RX(Y)Q28THY1(E)
RX(Y)Q20THY1(E) BYBC32G-W1
BYBC63G-W1
BYBC125G-W1
BYBC50G-W1
Cooling
36, 40 HP
cannot be44/38
used.
37/32 controller
39/34
35.0
with drain pump
MODEL
Heating capacity
Cooling Only
Heat Pump
other than the standard
Models in the(Option)
FDKS-EA
and
(H/L/SL)
Dimensions(H×W×D) mm 53×1,030×680 53×1,030×680 53×1,030×680 53×1,245×680 53×1,245×680 53×1,430×680 53×1,920×680 53×1,920×680
only 700 mm in width Weight
and 21 kg in kg
weight,8.0so are 8.0
8.0
8.5
8.5
9.5
12.0
12.0
FDKS25
FDKS35
FDKS50
FDKS60
easily installed
Standard
Type in limited spaces. Just 200 mm in
C(F)DXS25 C(F)DXS35 FDXS50
FDXS60
height,
all models
can be installed
in rooms
with
Ceiling
Mounted
Cassette
Corner
Type
Double
Outdoor
Units
Single
Outdoor
Units
35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
as
little
as
240
mm
depth
between
the
drop
6, 8, 10, 12 HP
14, 16 HP
22, 24, 26 HP
18, 20 FXKQ25MAVE
HP
28, 30, 32
HP
FXKQ32MAVE
FXKQ40MAVE
FXKQ63MAVE
MODEL
ceiling and ceiling
slab,
making
them
ideal
for
Power supply
1-phase, 220 -240 V/220 V, 50/60 Hz
Home Leave Operation prevents large rises or falls in
even shallow ceilings.
2,400
3,100
3,900
6,100
FDKS-EA kcal/h
the indoor
temperature by
continuing operation*
while
9,600
12,300
15,400
24,200
Btu/h
CDXS-EA
Great for Cooling capacity
you are3.6
sleeping or out of4.5
your home. This 7.1
means that
kW
2.8
hotel use!
2,800
3,400
4,300awaits when you
6,900wake or
kcal/h
an air-conditioned
welcome
10,900
13,600
17,100
27,300
Heating capacity
Btu/h
return. It also means that the indoor temperature can
3.2
4.0
5.0
8.0
kW
quickly return to your favourite comfort setting.
Power consumption
Space Saving Type
582/459 accessory
918/741
1,165/883
wireless
remote
6.4
6.4
6.4
6.4
6.4
9.5
Liquid (Flare)
Piping
mm
Gas (Flare)
12.7
12.7
12.7
12.7
12.7
15.9
connections
Drain
RX(Y)Q18THY1(E) RX(Y)Q26THY1(E)
VP25 (External Dia, 32/Internal Dia, 25)
RX(Y)Q12THY1(E)
Model
8,600
34,100
Cooling Only
High-COP Type
Heat Pump
Standard Type
305×775×600 305×775×600 305×775×600 305×990×600 305×990×600 305×1,175×600 305×1,665×600 305×1,665×600
kg
Machine weight
13,600
Triple
Outdoor
Units0.059
kW
0.059
0.044
Heating
Sound level (H/L)
2.5
10,900
HP
New Lineup
Outdoor Unit Lineup
VRV IV outdoor unit offers a higher
capacity of up to 60
HP, responding
the needs
of large-sized
building.
FXCQ50MVE
MODEL
FXCQ20MVE
FXCQ25MVE toFXCQ32MVE
FXCQ40MVE
FXCQ63MVE FXCQ80MVE FXCQ125MVE
The single outdoor
unit
has
only
2
different
shapes
and
dimensions,
not
only
simplifying
the
design
process,
Power
supply
1-phase,
220-240
V/220
V,
50/60 Hz but also bringing the
Cooling Only FDKS25EA / FDKS35EA
system flexibility to a new level.
4,800
kcal/h
1,900
2,400
3,100
6,100
7,700
12,000
3,900
FDKS25CA
/ FDKS35CA
With the outdoor unit capacity
increased in increment
of7,500
2 HP, customers'
needs
can15,400
be precisely
met. 24,200
Cooling capacity
Btu/h
19,100
9,600
12,300
30,700
47,800
FDKS50C / FDKS60C type on request) are designed specifically for use in areas which are subject
Outdoor units with anti-corrosion specifications (-E
to
5.6
kW
2.2
2.8
3.6
7.1
9.0
14.0
4.5
Heat Pump CDXS25EA / CDXS35EA
salt damage and atmospheric pollution.
kcal/h
2,800
3,400
Mo/C
Photocatalytic
Galvanised steel plate
Air-purifying Filter
Specifications
Indoor Unit Lineup
Slim
Ceiling
Mounted
Duct
The
outdoor
unit
capacity
is(Double
upType
to 60Flow)
HP inType
increment of 2 HP.
Ceiling
Mounted
Cassette
8.0Air filter
Catches dust
0.181
RX(Y)Q54TNY1(E)
0.168
RX(Y)Q56TNY1(E)
RX(Y)Q58TNY1(E)
0.168
RX(Y)Q60TNY1(E)
0.168
12.5/11.0/10.0
16.5/14.5/13.0
441/388/353
583/512/459
These filters are
not medical devices. Benefits
Triple
Outdoor Units
Pa
44-15 2
in the room
1 3 you go out
35/33/31
36/34/32 of
dB(A)
Sound
34,When
36,you
38,are40
HP level (HH/H/L)When
42, 44 HP 34/32/30 such as the adsorption
46, 48, 50 and
HP decomposition
only effective for substances
that are
3-D Airflow Dimensions (H×W×D)
200×900×620 bacteria are
200×900×620
200×1,100×620
mm
collected on and
the Titanium
Machine weight
27.0
28.0in direct contact with
31.0
kg
combines Vertical
Apatite Photocatalytic
Air-Purifying Filter.
Liquid (Flare)
6.4
6.4
6.4
and Horizontal
Piping
12.7
12.7
12.7
mm
Auto-Swing toconnections Gas (Flare)
Bacteria Removal Test
VP20method:
(External
Dia, 26/Internal
circulate air to every Drain
Testing
dropping
method Dia, 20)
Result certificate: No. 012553-1 and 012553-2
part of a room for• Cooling: Indoor temp.: 27℃DB, 19℃WB, Outdoor temp.: 35℃DB, Equivalent
piping length: 7.5 m, Level difference: 0 m.
Testing
organisation:
Japan
Spinners Inspecting Foundation
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit
is based
on the total capacity
index.
uniform cooling of
even
(See
Engineering Data Book for details.)
• Heating: Indoor temp.: 20℃DB, Outdoor temp.: 7℃DB, 6℃WB, Equivalent piping length: 7.5 m, Level difference: 0 m.
large spaces.
RX(Y)Q42TSY1(E)
RX(Y)Q34TSY1(E)
RX(Y)Q38TSY1(E)
• Sound level: Anechoic chamber conversion
value, measured at a point 1.5 m downward from the RX(Y)Q46TSY1(E)
unit centre.
actual operation, these
values are normally somewhat higher as a result of ambient
conditions.
RX(Y)Q48TSY1(E)
RX(Y)Q44TSY1(E)
RX(Y)Q36TSY1(E)
* This functionRX(Y)Q40TSY1(E)
is available
for areDuring
A uniform
temperature
1: Values
based on the following
conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
is achieved
throughout
to set
by the remote controller. This pressure means "HighRX(Y)Q50TSY1(E)
static pressure - Standard". (Factory setting is
FTK(X)S50/60/71F. 2: External static pressure is changeable
room.
10 Pa for FXDQ-PB models the
and entire
15 Pa for
FXDQ-NB models.)
3: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
Hotline: 0976 173 173
144036
Indoor Unit
Outdoor
UnitLineup
Lineup
Specifications
Outdoor
UnitsUnits
Residential
Indoor Units with connection to BP units
VRV
Indoor
Cooling Only / Heat Pump
Lineup
Wall Mounted
Ceiling
MountedType
Duct Type
kcal/h
FDXS25C / FDXS35C
Btu/h
FDXS60C
Heating
capacity/
FDXS50C
High-COP Type
Double
Power
consumption
Outdoor
Units
12, 14, 16 HP Casing
Cooling
Heating
External static pressure
Sound level (HH/H/L)
Dimensions (H×W×D)
2,800
3,400
4,300
5,400
8,500
10,900
13,600
17,100
21,500
kW
2.5
kW
0.056
1
0.060
1
0.151
1
0.128
1
1
0.073
1
0.182
1
0.203
1
34,plate
38 HP
18, 20, 22, 24, 26, 28, 30, 32 HPGalvanised steel
9/7.5/6.5
cfm
318/265/230
Pa
30-100 (50)
2
Standard accessory
9/7.5/6.5
9.5/8/7
Note: Remote
controllers
16/13/11
18/16.5/15
318/265/230
335/282/247
accessory wireless
remote
565/459/388
635/582/530
30-100 (50)
2
30-100 (50)
2
RX(Y)Q16THY1(E)
Drain
33/31/29
34/32/30
39/37/35
41/39/37
mm
300X550X700
300X550X700
300X550X700
300X700X700
300X1,000X700
kg
25
6.4
VP25 (External Dia, 32/Internal
Dia, 25)
RX(Y)Q38THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
CDXS-EA
series are
Low operation
Models in the FDKS-EA and
sound level
(H/L/SL)
only 700 mm in width and 21 kg in weight, so are
FDKS25
FDKS35
FDKS50
FDKS60
MODEL
FXMQ63PVE
FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE
easily installed
spaces. Just 200
mm in
Standard
Type in limited
C(F)DXS25
C(F)DXS35
FDXS60
FDXS50
1-phase, 220-240 V/220 V, 50/60 Hz
Power supply
height,
all models
can be installed
in roomsOutdoor
with
Double
Units
Single
Outdoor
Units
kcal/h
6,100
7,700
9,600 dB (A)
12,000
13,800
35/31/29 dB (A) 35/31/29
dB (A)
37/33/31
dB (A) 38/34/32
as 240 14,
mm depth
the20
drop
6, 8,as
10,little
12 HP
HP betweenBtu/h
22, 24, 26 HP38,200
18,
HP24,200
28,
30, 32 HP 54,600
Cooling16
capacity
30,700
47,800
ceiling and ceiling slab, making them
ideal
for
kW
7.1
9.0
11.2
14.0
Home
Leave Operation
prevents
large rises 16.0
or falls in
even shallow ceilings.
kcal/h
15,500
13,800
10,800
8,600
6,900
FDKS-EA
the indoor temperature by continuing operation* while
61,400
54,600
42,700
34,100
27,300
Heating capacity CDXS-EA Btu/h
Great for
you
are sleeping12.5
or out of your16.0
home. This means
that
kW
18.0
10.0
8.0
hotel use!
an
air-conditioned
welcome
awaits
when
you
wake
or
1
1
1
1
1
kW
0.405
0.284
0.215
0.185
0.138
Cooling
Power consumption
1
1
1
1
1
return.
temperature
kW
0.449 can
0.449
0.364 that the indoor
0.286 It also means
0.218
Heating
Galvanised
steelfavourite
plate
Casing
quickly return
to your
comfort setting.
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
19.5/17.5/16
200 mm
RX(Y)Q18TNY1(E)
cfm
688/618/565
Airflow
rate (HH/H/L)
RX(Y)Q14TY1(E)
RX(Y)Q16TY1(E)
Only 700 mm
RX(Y)Q20TNY1(E)
Pa
External static pressure
Sound level (HH/H/L)
dB(A)
50-200 (100)
42/40/38
2
25/22.5/20
32/27/23
39/33/28
46/39/32
RX(Y)Q22TNY1(E)
* Home
Leave Operation can be selected forRX(Y)Q28TNY1(E)
any temperature from 18 to
883/794/706
1,130/953/812
1,377/1,165/988
1,624/1,377/1,130
32˚CRX(Y)Q24TNY1(E)
for cooling operation and 10 to 30˚C for
heating operation.
RX(Y)Q30TNY1(E)
2 remote
* Home
Leave2 Operation
be set (100)
using the
50-200
(100)
50-200function
(100) 2 must50-200
50-140controller
(100) 2
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
when going to sleep or leaving the house, and after waking up or returning
43/41/39
43/41/39
44/42/40
46/45/43
home.
FDKS25EA FDKS35EA FDKS25CA FDKS35CA
mm
300FDXS35C
X1,000X700 300X1,000X700 300X1,400X700 300X1,400X700 300X1,400X700
FDXS25C
bolt* Suction
Air
kg x 900 x 62036mm
36discharge duct* Suspension
46
46duct* Air filter
47
Dimensions (H x W x D)Machine
200 xweight
700 x 620 mm 200
Space
Saving Type 21
Air discharge grille*
25 kg 9.5
Weight
kg (Flare)
Liquid
9.5
9.5
9.5
9.5
Piping
3/min
Airflow rate
(H)
8.7Gas
m3/min
Single
Outdoor
Units
9.5
m3/min 10Outdoor
m
Double
Units
mm
(Flare)
15.9
15.9
15.9
15.9
15.9
connections
AIR
30
Pa
40 Pa
External static pressure
Drain
VP25 (External Dia, 32/Internal Dia, 25)
Dimensions
(H×W×D)
CDXS25EA
CDXS35EA
18, 20 HP
22, 24 HP
26, 28, 30, 32 HP
Note: Specifications are based on the following conditions;
• Cooling: Indoor temp.: 27°CDB,mm
19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 Chamber
m, Level difference: 0 m.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping
Air suction
Signallength:
receiver7.5
wirem, Level difference: 0 m.
grille*
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based
on
the
total
capacity
index.
=
Length 1,900 mm
Signal
(See Engineering Data Book for details.)
* Locally obtained parts
receiver
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result ofNotes:
ambient conditions.
1. To prevent an increase in operation noise, avoid
1: Power consumption values are based on conditions of rated external
Option static pressure.
installing
the air(FXMQ40P),
suction grillefourteen
directly below
the
2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P),
thirteen
(FXMQ50suction
chamber.
125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible
static
pressures. The standard static
2.
Grilles,
piping
connections,
ducts,
and
installation
pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.
parts should be obtained locally. Slim Ceiling
Mounted Duct type models do not have drain-up
RX(Y)Q22TSY1(E)
RX(Y)Q18TY1(E)
RX(Y)Q26TSY1(E)
RX(Y)Q30TSY1(E)
Suction grille (KDGF19A45)
pumps.
RX(Y)Q24TSY1(E)
RX(Y)Q20TY1(E)
RX(Y)Q28TSY1(E)
3. The signal RX(Y)Q32TSY1(E)
receiver unit must be located near the
air suction inlet, because the unit includes a
sensor that detects room temperature.
Signals from the wireless remote controller are
240
AIR
transmitted to the signal receiver.
134135
36, 40 HP
FXMQ200MAVE
MODEL
FTKS25D
/ FTKS35D
Power supply
FTXS20D / FTXS25E / FTXS35E
kcal/h
Cooling capacity
Cooling Only
FTKS50B
1-phase, 220 -240 V/220 V, 50/60 Hz
95,500
kcal/h
22.4
21,500
28.0
27,100
Btu/h
85,300
107,500
kW
kW
25.0
m /min
Sound level(H/L)
220 V
Dimensions (H×W×D)
1.465
1
1.294
1
1.465
1
mm
Liquid (Flare)
Piping
RX(Y)Q36THY1(E)
connections Gas (Flare)
RX(Y)Q40THY1(E)
Galvanised steel plate
Standard accessory*
58/50
72/62
2,542/2,189
132-221
191-270
dB(A)
kg
Machine weight
Drain
Pa
31.5
1
2,047/1,765
3
cfm
Standard accessory*
1.294
42, 44, 46, 48, 50 HP
External static pressure
24,100
76,400
FTKS50F / FTKS60F
/ FTKS71F
kW
Cooling
Power consumption
FTXS50F
/ FTXS60F
/
FTXS71F
kW
Heating
Casing
FXMQ250MAVE
19,300
Btu/h
Airflow rate (H/L)
50-200 (100)
33/31/29
m3/min
Cooling Only
Heat Pump
controller
cannot be used. 2
2
30-160 (100)
dB(A)
Liquid (Flare)
Space Saving Type
other than the standard
25
28
36
Slim256.4 and smooth
design
6.4
6.4
6.4
Piping
RX(Y)Q26THY1(E)
RX(Y)Q18THY1(E)
Gas
(Flare)
mm
12.7
12.7
12.7
12.7
12.7
RX(Y)Q12THY1(E)
suits your shallow
ceiling
connections
RX(Y)Q34THY1(E)
RX(Y)Q20THY1(E) RX(Y)Q28THY1(E)
RX(Y)Q14THY1(E)
Machine weight
Cooling Only
High-COP Type
Heat Pump
Standard Type
Heating capacity
6.3
5.0
4.0
3.2
0.056
1
Triple
Outdoor
Units
kW
0.069
0.069 1
m3/min
Airflow rate (HH/H/L)
2,200
HP
New Lineup
2
2
48/45
48/45
470X1,380X1,100
470X1,380X1,100
137
137
9.5
Standard
accessory*
9.5
RX(Y)Q48THY1(E)
mmRX(Y)Q42THY1(E)* Remote
19.1controllers other than the standard accessory wireless remote
22.2controller cannot be used.
RX(Y)Q44THY1(E) RX(Y)Q50THY1(E)
PS1B
RX(Y)Q46THY1(E)
Stylish flat panel harmonises with your interior décor
Titanium apatite is a photocatalytic material with
high adsorption power. Titanium apatite also
effectively adsorbs
and
bacteria
(H/L/SL)
42,
44 HP
46, 48,
50,decomposes
52, 54, 56, 58,
60 HP
38, 40 HP
34, 36 HP
FXHQ32MAVEacross itsFXHQ63MAVE
FXHQ100MAVEis
MODEL
entire
surface.
The
photocatalyst
FTK(X)S20/25 FTK(X)S35 FTK(X)S50 FTK(X)S60 FTK(X)S71
1-phase, 220-240
V, 50/60 Hz to light.
Power supply
activated
simplyV/220
by exposure
dB (A) 46/37/34 dB3,100
(A)
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33
9,600
kcal/h
6,100
Wall Mounted indoor units achieve quiet sound
Ceiling
Suspended
Triple
Outdoor
Units
levels
of 22
dB (A) Type
during cooling operation.
Cooling capacity
Btu/h
12,300
Intelligent Eye with its infrared sensor
kW
3.6
automatically controls air conditioner
operation
kcal/h
3,400
according to human
movement in Btu/h
a room. When
Heating capacity
13,600
there is no movement, it adjusts the
kWtemperature4.0
by 2˚C for energy savings.
RX(Y)Q42TNY1(E)
RX(Y)Q38TNY1(E)
Cooling
kW
RX(Y)Q34TNY1(E)
0.111
RX(Y)Q36TNY1(E)
Power consumption
RX(Y)Q40TNY1(E)
Heating
kW
Casing
Sound level (H/L)
12/10
cfm
424/353
dB(A)
Dimensions (H×W×D)
Double Outdoor Units
RX(Y)Q44TNY1(E)
0.111
m3/min
Airflow rate (H/L)
Outdoor Unit Lineup
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
MODEL
FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE
The single outdoor
unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
Cooling Only
1-phase, 220-240 V/220 V, 50/60 Hz
Power
supply
FDKS25EA
/
FDKS35EA
system flexibility to a new level.
kcal/h
1,900
2,400
3,100
3,900
4,800
FDKS25CA
/
FDKS35CA
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
Cooling
capacity/ FDKS60C
Btu/h
7,500
9,600
12,300
15,400
19,100
FDKS50C
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
Heat Pump CDXS25EA / CDXS35EA
kW
2.2
2.8
3.6
4.5
5.6
salt damage and atmospheric
pollution.
Mo/C
mm
36/31
195×960×680
24,200
38,200
7.1
11.2
6,900
10,800
27,300
42,700
8.0
Specifications
Indoor Unit Lineup
Slim
Ceiling
Mounted
Duct
The
outdoor
unit
capacity
is upType
to 60 HP in increment of 2 HP.
Ceiling
Mounted
Duct Type
Air filter
12.5Catches dust
RX(Y)Q46TNY1(E) RX(Y)Q54TNY1(E)
0.115
0.135
RX(Y)Q48TNY1(E) RX(Y)Q56TNY1(E)
0.115
0.135
RX(Y)Q50TNY1(E) RX(Y)Q58TNY1(E)
RX(Y)Q52TNY1(E) RX(Y)Q60TNY1(E)
Titanium Apatite
White (10Y9/0.5)
17.5/14
Photocatalytic
Air-purifying
Filter
618/494
39/34
195×1,160×680
25/19.5
883/688
45/37
195×1,400×680
These filters are not medical devices. Benefits
Triple Outdoor Units
kg
24.0
28.0
33.0
such as the adsorption
of
34, 36, 38, 40 HP
42, 44 HP
46,
48, 50 and
HP decomposition
Liquid (Flare)
6.4
9.5
9.5
bacteria are only effective for substances
that are
3-D Airflow Piping
mm
12.7
15.9
15.9
connections Gas (Flare)
collected on and in direct contact with the Titanium
combines Vertical
Drain
VP20 (External Dia, 26/Internal Dia, 20)
Apatite Photocatalytic Air-Purifying Filter.
and Horizontal
Equivalent piping length: 7.5 m, Level difference: 0 m.
Auto-Swing to • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB,
Bacteria
Removal
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB,
Equivalent
piping Test
length: 7.5 m, Level difference: 0 m.
circulate air to every
method:
dropping
method
• Capacity of indoor unit is only for reference. Actual capacity of Testing
indoor unit
is based
on the total
capacity index.
(See Engineering Data Book for details.)
Result certificate: No. 012553-1 and 012553-2
part of a room for• Sound
level: (FXMQ-MA) Anechoic chamber conversion value,Testing
measured
at
a
point
1.5
m
downward
from
the unit centre.
organisation: Japan Spinners
Inspecting
Foundation
uniform cooling of even (FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions
RX(Y)Q46TSY1(E)
large spaces.
RX(Y)Q42TSY1(E)
RX(Y)Q34TSY1(E)
RX(Y)Q38TSY1(E)
1: Power consumption values are based
on conditions of standard external static pressure.
Machine weight
When you are in the room
When you go out
2: External static pressure is changeable
to change over the connectors inside electrical box, thisRX(Y)Q48TSY1(E)
pressure means "Standard-High static pressure".
RX(Y)Q44TSY1(E)
RX(Y)Q36TSY1(E)
* This functionRX(Y)Q40TSY1(E)
is available
for
A uniform temperature
RX(Y)Q50TSY1(E)
is achieved throughout
FTK(X)S50/60/71F.
the entire room.
Hotline: 0976 173 173
144236
Indoor Unit
Outdoor
UnitLineup
Lineup
Specifications
Outdoor
UnitsUnits
Residential
Indoor Units with connection to BP units
VRV
Indoor
Cooling Only / Heat Pump
Lineup
WallStanding
Mounted Duct
Type Type
Floor
FDXS25C / FDXS35C
kcal/h
FDXS50C
Btu/h
Heating
capacity/ FDXS60C
High-COP Type
Double Outdoor
PowerUnits
consumption
12, 14, 16 HP
Cooling
2,200
2,800
3,400
4,300
5,400
6,900
8,500
10,900
13,600
17,100
21,500
27,300
kW
2.5
3.2
4.0
5.0
6.3
8.0
kW
0.019
0.028
0.030
0.020
0.033
0.050
kW
0.029
0.034
0.035
0.020
0.039
0.060
Triple Outdoor Units
Heating
18, 20, 22, 24, 26, 28, 30, 32 HP
Casing
m3/min
Airflow rate (H/L)
7.5/4.5
265/159
cfm
dB(A)
Sound level (H/L)
mm
Dimensions (H×W×D)
8.5/5.5
300/194
12/9
424/318
Standard accessory
Liquid (Flare)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
11.0
6.4
11.0
11.0
14.0
Casing
2000.049
mm
kW
RX(Y)Q18TNY1(E)
RX(Y)Q20TNY1(E)
kW
0.049
14.0
6.4
6.4
22, 24 HP
25.0
FXLQ
FXNQ
RX(Y)Q38THY1(E)
RX(Y)Q24TNY1(E)
RX(Y)Q30TNY1(E)
0.049
0.090
0.090
0.110
0.110
* Home Leave Operation function must be set using the remote controller
32˚C for cooling operation and 10 to 30˚C for heating operation.
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
Piping
connections Gas (Flare)
Drain
kcal/h
Btu/h
Sound level *1
Liquid
Piping
connections Gas
Drain
Air filter
19,300
24,100
38,700
48,200
47,800
76,400
95,500
154,000
191,000
14.0
22.4
28.0
45.0
13,800
21,500
27,100
43,000
54,600
85,300
107,500
171,000
16.0
25.0
31.5
50.0
0.59
1.41
1.68
3.97
0.59
1.41
1.68
kW
kW
kW
42, 44, 46, 48, 50 HP
Casing colour
Machine weight
RX(Y)Q36THY1(E)
RX(Y)Q40THY1(E)
12,000
mm
kg
25.0
19.0
19.0
mm
6.4
12.7
6.4
12.7
30.0
23.0
26, 28,
30.030, 32 HP
36.0
6.4 receiver wire
Signal
Length = 1,900 mm
12.7
23.0
Chamber
6.4
12.7Signal
receiver
36.0
27.0
27.0
6.4Air suction
grille*
12.7
AIR
9.5
15.9 parts
* Locally obtained
transmitted to the signal receiver.
Standard accessory*
56.0
54,200
215,000
2.62
3.97
63.0
5.02
5.02
2.62
Standard accessory*
Ivory white (5Y7.5/1)
1,670×750×510 1,670×950×510 1,670×1,170×510 1,900×1,170×720
1,900×1,470×720
kg
115
140
165
225
270
295
dB(A)
52
55
59
64
61
67
mm
mm
12.7 (Brazing)
9.5 (Brazing)
15.9 (Brazing)
19.1 (Brazing)
22.2 (Brazing)
15.9 (Brazing)
28.6 (Brazing)
28.6 (Brazing)
Standard
accessory*
Rp1 (PS 1B internal thread)
mm
Long-life filter (anti-mould resin net)
Type
RX(Y)Q42THY1(E)
RX(Y)Q48THY1(E)
kW
1.5
1.5 accessory3.7
3.7
*0.75
Remote
controllers
other than the standard
wireless remote controller
cannot 5.5
be used.
Motor output
RX(Y)Q44THY1(E)
RX(Y)Q50THY1(E)
m3/min
43
69
Airflow rate
RX(Y)Q46THY1(E)
cfm
1,518
2,436
86
134
165
172
Stylish flat panel harmonises with your interior décor
Fan
External static pressure *2
150
Pa
210
Drive system
3,036
4,730
5,825
6,072
270
380
125
480
Belt drive system
Titanium apatite is a photocatalytic material with
Wall Mounted indoor units
achievearequiet
sound
Notes: Specifications
based on
the following conditions;
: Indoor
temp. of 27°CDB, 19°CWB, and outdoor
of 35°CDB.
Triple Outdoor
Units
hightemp.
adsorption
power. Titanium apatite also
levels of 22
dB (A) during•Cooling
cooling
operation.
34, 36 HP
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
effectively
adsorbs
and
decomposes
bacteria
of indoor unit is only
for44
reference.
capacity of indoor
unit46,
is based
on
the
total capacity
index.
(H/L/SL)
42,
HP Actual
48,
50,
52,
54, 56,
58,
60 HP
38, 40 •Capacity
HP
(See Engineering Data Book for details.)
across
its
entire
surface.
The
photocatalyst
is
*1
Sound
level
:
measured
when
the
air
discharge
outlet
duct
(2
m)
is
attached
(anechoic
chamber
conversion
value).
FTK(X)S20/25 FTK(X)S35 FTK(X)S50 FTK(X)S60 FTK(X)S71
It increases by approximately 5 dB(A) when the plenum
chamber is
installed toby
deliver
direct airflow. to light.
activated
simply
exposure
*2 The value is the external static pressure with standard pulley.
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A)
Intelligent Eye with its infrared sensor
automatically controls air conditioner operation
according to human movement in a room. When
there is no movement, it adjusts the temperature
by 2˚C for energy savings.
RX(Y)Q42TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q34TNY1(E)
RX(Y)Q36TNY1(E)
RX(Y)Q46TNY1(E)
RX(Y)Q48TNY1(E)
RX(Y)Q50TNY1(E)
RX(Y)Q52TNY1(E)
Titanium Apatite
RX(Y)Q44TNY1(E)
RX(Y)Q40TNY1(E)
when white
going (5Y7.5/1)/FXNQ:
to sleep or leaving Galvanised
the house, and
after
waking up or returning
FXLQ: Ivory
steel
plate
21O.D.Notes:
1. To prevent an increase in operation noise, avoid
Option
installing the air suction grille directly below the
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5
m, Level difference: 0 m.
suction chamber.
• Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CDB, Equivalent piping length: 7.5 m,
Level difference: 0 m.
2. Grilles, piping connections, ducts, and installation
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total parts
capacity
index.
should
be obtained locally. Slim Ceiling
(See Engineering Data Book for details.)
Mounted Duct type models do not have drain-up
RX(Y)Q22TSY1(E)
RX(Y)Q18TY1(E)
RX(Y)Q26TSY1(E)
• Sound level: (FXAQ-P) Anechoic chamber conversion value, measured
at a(KDGF19A45)
point
1 m in front of
the unit RX(Y)Q30TSY1(E)
and 1 m downward.
Suction grille
pumps.
(FXLQ-MA, FXNQ-MA)
Anechoic chamber conversion value, measured
at a point
1.5signal
m in RX(Y)Q32TSY1(E)
front
of the
atbe
a height
1.5 the
m.
RX(Y)Q24TSY1(E)
RX(Y)Q20TY1(E)
RX(Y)Q28TSY1(E)
3. The
receiver
unitunit
must
locatedofnear
During actual operation, these values are normally somewhat higher as a result ofairambient
suction conditions.
inlet, because the unit includes a
sensor that detects room temperature.
Signals from the wireless remote controller are
134335
FTKS50B
Dimensions (H×W×D)
9.5
RX(Y)Q22TNY1(E)
* Home
Leave0.090
Operation can be
selected forRX(Y)Q28TNY1(E)
any
temperature from
18 to
0.049
0.090
0.110
0.110
240 mm
Liquid (Flare)
36, 40 HP
14.0
6.4
kW
FTKS50F / FTKS60F / FTKS71F
Cooling
Power consumption
FTXS50F / FTXS60F / FTXS71F
Heating
controller cannot be used.
FDKS25EA FDKS35EA FDKS25CA
FDKS35CA
m3/min
7/6
7/6
8/6
11/8.5
14/11
16/12
FDXS25C FDXS35C
cfm
247/212
247/212
282/212
388/300
494/388
565/424
Suspension
bolt*
Suction
duct*
Air
discharge
duct*
Dimensions (H x W x D) 200 x 700 x 620 mm 200 x 900 x 620 mm
Air filter
Space
Saving Type
35/32
35/32
35/32
38/33
39/34
40/35
Sound level (H/L) 220 V dB(A)
Air discharge grille*
25 kg
Weight
21 kg
FXLQ
600×1,000×222
600×1,000×222
600×1,140×222
600×1,140×222
600×1,420×222
600×1,420×222
Dimensions
3
3
3
Airflow rate
(H)
8.7 m /min
Single
Outdoor
Units
9.5
m /min 10Outdoor
m /min
Double
Units AIR
mm
(H×W×D)
610×930×220
610×930×220 610×1,070×220
610×1,070×220 610×1,350×220 610×1,350×220
30 Pa FXNQ
40
Pa
External static pressure
Machine weight
Cooling Only
Heat Pump
3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h
home.
Airflow
rate (H/L)
CDXS25EA
CDXS35EA
18, 20 HP
Cooling Only
FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16
Btu/h
Heating capacity
Slim and smooth design
15.9
suits
your
shallow
ceiling
RX(Y)Q28THY1(E)
6.4
RX(Y)Q20THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
CDXS-EA
series are
Low operation
Cooling
RX(Y)Q14TY1(E)
Power consumption
RX(Y)Q16TY1(E)
Only 700 mmHeating
Cooling capacity
Note: Remote controllers
Models in the FDKS-EA and
sound level
(H/L/SL)
only 700 mm in width and 21 kg in weight, so are
FDKS25
FDKS35
FDKS50
FDKS60
easily
installed
in limited spaces. JustFloor
200 mm
in
Floor
Standing
Standing
Type
Standard
Type Type/Concealed
C(F)DXS25
C(F)DXS35 FDXS50
FDXS60
height,
all models
can be installed
in roomsOutdoor
with
Double
Units
Single
Outdoor
Units
35/31/29FXLQ32MAVE
dB (A) 35/31/29 dB (A) FXLQ50MAVE
dB (A) 38/34/32 dB (A)
as
little
as
240
mm
depth
between
the
drop
FXLQ20MAVE
FXLQ25MAVE
6, 8, 10, 12 HP
14, 16 HP
22, 24, 26 HP FXLQ40MAVE37/33/31
18, 20 HP
28, 30, 32 HPFXLQ63MAVE
MODEL
FXNQ20MAVE
FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
ceiling and ceiling slab, making them ideal
for
Home
Leave
Operation
supply
1-phase,
220-240
V/220 V,prevents
50/60 Hz large rises or falls in
even shallowPower
ceilings.
FDKS-EA kcal/h
the indoor3,100
temperature
by continuing
1,900
2,400
3,900
4,800 operation*
6,100while
CDXS-EA Btu/h
FXLQ
Great for Cooling capacity
7,500
9,600
12,300
15,400
19,100 This means
24,200 that
you are sleeping
or out
of your home.
hotel use!
kW
2.2
2.8
3.6
4.5
7.1
an air-conditioned
welcome
awaits5.6when you wake
or
kcal/h
2,200
2,800
3,400
4,300
5,400
6,900
return. It also means that the indoor temperature can
Btu/h
8,500
10,900
13,600
17,100
21,500
27,300
Heating capacity
quickly return
to your favourite
comfort
setting.8.0
kW
2.5
3.2
4.0
5.0
6.3
FXNQ
RX(Y)Q6TY1(E)
Space Saving Type
MODEL
FTKS25D Power
/ FTKS35D
supply
FTXS20D / FTXS25E / FTXS35E
15/12
19/14
other than the standard
accessory wireless
remote
530/424
671/494
Piping
mm
12.7
12.7
12.7
12.7
12.7
connections Gas (Flare)
RX(Y)Q18THY1(E) RX(Y)Q26THY1(E)
RX(Y)Q12THY1(E)
Drain
VP13 (External Dia, 18/Internal
Dia,
13)
RX(Y)Q34THY1(E)
RX(Y)Q14THY1(E)
RX(Y)Q16THY1(E)
Cooling Only
High-COP Type
Heat Pump
Standard Type
35/31
36/31
38/31
39/34
42/37
47/41
290×795×238 290×795×238 290×795×238 290×1,050×238 290×1,050×238 290×1,050×238
kg
Machine weight
8/5
282/177
34, 38 HP
White (3.0Y8.5/0.5)
HP
New Lineup
Outdoor Unit Lineup
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
MODEL
FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
The single outdoor
unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
Cooling Only
FDKS25EA
/ FDKS35EA
Power
supply
1-phase, 220-240 V/220 V, 50/60 Hz
system flexibility to a new
level.
FDKS25CA / FDKS35CA
kcal/h of 21,900
2,400needs can
3,100
3,900
4,800
6,100
With the outdoor unit capacity increased in increment
HP, customers'
be precisely
met.
FDKS50C
/
FDKS60C
Cooling
capacity
Btu/h
7,500
9,600
12,300
15,400
19,100
24,200
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
Heat Pump CDXS25EA / CDXS35EA
kW
2.2
2.8
3.6
4.5
5.6
7.1
salt damage and atmospheric
pollution.
Mo/C
Specifications
Indoor Unit Lineup
Slim
Ceiling
Mounted
The
outdoor
unit
capacityDuct
is upType
to 60 HP in increment of 2 HP.
Wall
Mounted
Type
Air filter
Catches dust
RX(Y)Q54TNY1(E)
RX(Y)Q56TNY1(E)
RX(Y)Q58TNY1(E)
RX(Y)Q60TNY1(E)
Photocatalytic
Air-purifying Filter
Double Outdoor Units
34, 36, 38, 40 HP
3-D Airflow
combines Vertical
and Horizontal
Auto-Swing to
circulate air to every
part of a room for
uniform cooling of even
large spaces.
RX(Y)Q34TSY1(E)
RX(Y)Q38TSY1(E)
When you are in the room
RX(Y)Q36TSY1(E)
* This functionRX(Y)Q40TSY1(E)
is available for
FTK(X)S50/60/71F.
These filters are not medical devices. Benefits
Triple Outdoor Units
42, 44 HP
When you go out
such as the adsorption
46, 48, 50 and
HP decomposition of
bacteria are only effective for substances that are
collected on and in direct contact with the Titanium
Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal Test
Testing method: dropping method
Result certificate: No. 012553-1 and 012553-2
Testing organisation: Japan Spinners Inspecting Foundation
RX(Y)Q42TSY1(E)
RX(Y)Q44TSY1(E)
A uniform temperature
is achieved throughout
the entire room.
RX(Y)Q46TSY1(E)
RX(Y)Q48TSY1(E)
RX(Y)Q50TSY1(E)
Hotline: 0976 173 173
144436
Indoor Unit
Outdoor
UnitLineup
Lineup
Specifications
Outdoor
Unitsindoor
Residential
Indoor units
Units with
Residential
withconnection
connectiontotoBPBPunits
units
Cooling Only / Heat Pump
Lineup
WallCeiling
Mounted
Type
Slim
Mounted
Duct Type
FDXS25C
/ FDXS35C
Dimensions (HXWXD)
FDXS50C
/ FDXS60C
Machine
weight
High-COP Type
Piping
connections Gas (Flare)
Drain
mm
6.4
9.5
Triple Outdoor Units
Heat insulation
Model
18, 20, 22, 24, 26, 28, 30, 32 HP
Colour
Panel
(Option)
9.5
12.7
15.9
I.D ø25XO.D ø32
38pipes
HP
Both liquid 34,
and gas
Standard accessory
BYC125K-W1
5
Note: * For 220 V operation.
Slim
and
smooth design
Ceiling Mounted Cassette (Compact Multi
Flow)
Type
RX(Y)Q18THY1(E) RX(Y)Q26THY1(E)
RX(Y)Q12THY1(E)
suits your
shallow
ceiling
RX(Y)Q34THY1(E)
RX(Y)Q20THY1(E) RX(Y)Q28THY1(E)
RX(Y)Q14THY1(E)
FFQ25BV1B
FFQ35BV1B
FFQ50BV1B
FFQ60BV1B
MODEL
600 x 600
RX(Y)Q38THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
RX(Y)Q16THY1(E)
Power supply
1-phase, 220 -240 V, 50 Hz
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
Models in the FDKS-EA and CDXS-EA
series are
Low operation sound level
m3/min (cfm)
Airflow rates (H)
9.0 (318)
10.0 (353)
(H/L/SL)
15.0 (530)
12.0 (424)
only 700 mm in width Sound
and levels
21 kg
in weight,
so are29.5/24.5
dB (A)
(H/L)*
32/25
36/27
41/32
FDKS25
FDKS35
FDKS50
FDKS60
Fan speed
2 steps
easily
installed
in
limited
spaces.
Just
200
mm
in
Standard Type
C(F)DXS25 Microcomputer
C(F)DXS35
FDXS60
control FDXS50
Temperature control
height,
all models
canDimensions
be installed
in rooms
with
Single
Outdoor
Units
(HXWDouble
XD)
286X575X575
mmOutdoor Units
35/31/29 dB (A) 35/31/29
dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
as
little
as
240
mm
depth
between
the
drop
kg
Machine
weight
17.5
6, 8, 10, 12 HP
14, 16 HP
22, 24, 26 HP
18, 20 HP
28, 30, 32 HP
6.4
Liquidthem
(Flare) ideal for
ceiling and ceiling slab,
making
Piping
Gas (Flare)
9.5 Leave Operation prevents large
12.7 rises or falls in
mm
Home
even shallow ceilings.connections
FDKS-EA
Drain
VP20
(External
Dia.
26/Internal
Dia.
20)
the indoor temperature by continuing operation* while
Both liquid and gas pipes
Heat insulation
CDXS-EA
Great for
you are sleepingBYFQ60B8W1
or out of your home. This means that
Model
hotel use!
Panel
White
an air-conditioned welcome
awaits when you wake or
Colour
(Option)
mm
Dimensions (HXWXD)
X700X700
55
return. It also means that the indoor temperature can
kg
Weight
2.7
quickly return to your favourite comfort setting.
Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
higher owing to ambient conditions.
200 mm
RX(Y)Q18TNY1(E)
RX(Y)Q20TNY1(E)
RX(Y)Q14TY1(E)
RX(Y)Q16TY1(E)
Only 700 mm
Ceiling Mounted
Built-in Type
FDKS25EA FDKS35EA FDKS25CA
RX(Y)Q22TNY1(E)
* Home
Leave Operation can be selected forRX(Y)Q28TNY1(E)
any temperature from 18 to
32˚CRX(Y)Q24TNY1(E)
for cooling operation and 10 to 30˚C for
heating operation.
RX(Y)Q30TNY1(E)
* Home
Leave Operation function must be set using the remote controller
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
when going to sleep or leaving the house, and after waking up or returning
home.
FDKS35CA
CDXS25EA CDXS35EA FDXS25C FDXS35C
Air discharge duct* Suspension bolt* Suction duct*
FBQ60BV1
FBQ71BV1
Dimensions (H x W x D) 200 x 700 x 620 MODEL
mm 200 x 900 x 620 mm
Air filter
Space
Saving Type Power
Air discharge grille*
25 kg
Weight
21 kgsupply
1-phase, 220 -240 V, 50 Hz
Airflow
rates (H) 9.5
17.0 (600)
19.0 (670)
m3/min (cfm)
Airflow rate
(H)
8.7
m3/min
Single
Outdoor
Units
m3/min
10Outdoor
m3/min
Double
Units
AIR
Sound
dB
41/35
30 Palevels (H/L)*
40(A)
Pa
External static pressure
18, 20 HP
22, 24 HP
Fan speed
Machine weight
Liquid (Flare)
Piping
connections Gas (Flare)
Drain
mm
Heat insulation
RX(Y)Q18TY1(E)
RX(Y)Q20TY1(E)
Model
Colour
RX(Y)Q22TSY1(E)
Panel
(Option) Dimensions (HXWXD) RX(Y)Q24TSY1(E)
mm
Weight
Signals from the wireless remote controller are
Note: * For 220 V operation.
transmitted to the signal receiver.
134535
Chamber
300X1,000
Signal receiver
wire X800
=
Length 1,900 mm
41
Signal
mm
kg
kg
6.4
Fan speed
FTKS50B
Temperature control
Cooling Only
Heat Pump
36, 40 HP
receiver
AIR
m3/min (cfm)
1-phase, 220 -240 V/220-230 V, 50/60 Hz
9.5 (335)
8.7 (307)
dB (A)
mm
kg
External static pressure
Pa
16.0 (565)
37/33/31
38/34/32
Standard
accessory*
Microcomputer control
200X700X620
25
21
42, 44, 46, 48, 50 HP
Heat insulation
12.0 (424)
5 steps, quiet and automatic
Liquid/ (Flare)
FTKS50F / FTKS60F
FTKS71F
Piping
Gas (Flare)
mm
FTXS50F / connections
FTXS60F
/ FTXS71F
Drain
10.0 (353)
35/31/29
200X900X620
6.4
9.5
200X1,100X620
30
27
12.7
VP20 (External Dia. 26/Internal Dia. 20)
Both liquid and gas pipes
Standard accessory*
40
30
Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for F(C)DK(X)S-EA and
40 Pa for FDK(X)S-C(A). Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for
FDKS-C.
Wall Mounted Type
RX(Y)Q36THY1(E)
RX(Y)Q40THY1(E)
Standard
accessory*
–
Cooling Only
FTKS25DVM FTKS35DVM FTKS50BVMA FTKS50FVM FTKS60FVM FTKS71FVM
MODEL HeatRX(Y)Q42THY1(E)
RX(Y)Q48THY1(E)
* Remote
controllers FTXS35EVMA
other than the standard
wireless remote
controller cannot
be used.
–accessory
Pump
FTXS20DVMA
FTXS25EVMA
FTXS50FVMA
FTXS60FVMA
FTXS71FVMA
RX(Y)Q44THY1(E) RX(Y)Q50THY1(E)
1-phase, 220 - 240 V/220-230 V, 50/60 Hz
Power supply
RX(Y)Q46THY1(E)
White
Front panel colour
Stylish flat panel harmonises with your
interior décor
–
Airflow rates
(H)
Cooling
Heating*
m3/min (cfm)
Cooling
Sound levels
(A)
units
achieve quietdBsound
(H/L/SL)
Heating*
8.7 (307)
8.9 (314)
9.4 (332)
9.7 (342)
14.7 (519)
16.2 (572)
16.2 (572)
17.4 (614)
17.4 (614)
21.5 (759)
43/34/31
45/36/33
46/37/34
Titanium39/26/23
apatite44/35/32
is a photocatalytic
material
with
Wall Mounted indoor
37/28/25
38/29/26
–
42/33/30
44/35/32
46/37/34
Triple Outdoor
Units
high
adsorption
power.
Titanium
apatite
also
levels of 22 dB (A) during
cooling operation.
Fan speed
5 steps, quiet and automatic
effectively adsorbs
and
bacteria
control
Microcomputer
control
(H/L/SL)
42,
44 HP
46, 48,
50,decomposes
52, 54, 56, 58,
60 HP
38, 40Temperature
HP
34, 36 HP
Dimensions (HXWXD)
mm
290X1,050X238
283Xacross
800X195 its entire
290surface.
X795X238
The
photocatalyst
is
FTK(X)S60 kg
FTK(X)S71
FTK(X)S20/25 FTK(X)S35 FTK(X)S50
Machine weight
9
12
activated
simply by exposure to light.
Liquid (Flare)
6.4
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31
Piping dB (A) 45/36/33 dB (A) 46/37/34 dB (A)
connections Gas (Flare)
37/25/22
11.4 (402)
mm
9.5
Drain
Intelligent Eye with its infrared
sensor
automatically controlsHeat
air insulation
conditioner operation
Note: * For Heat Pump type only.
according to human movement in a room. When
there is no movement, it adjusts the temperature
forenergy
connection
to residential indoor units RX(Y)Q42TNY1(E)
BP
Units
by 2˚C for
savings.
RX(Y)Q38TNY1(E)
RX(Y)Q34TNY1(E)
RX(Y)Q36TNY1(E)
12.7
15.9
18.0
Both liquid and gas pipes
Air filter
Catches dust
RX(Y)Q46TNY1(E) RX(Y)Q54TNY1(E)
RX(Y)Q48TNY1(E) RX(Y)Q56TNY1(E)
RX(Y)Q58TNY1(E)
RX(Y)Q50TNY1(E)BPMKS967A2
BPMKS967A3
RX(Y)Q60TNY1(E)
RX(Y)Q52TNY1(E)
Titanium Apatite
RX(Y)Q44TNY1(E)
RX(Y)Q40TNY1(E)
MODEL
Power supply
W
1-phase, 220 -240 V/220-230 V, 50/60 Hz
Photocatalytic
3 (connectable to 1-3 indoor units)
2 (connectable to 1-2 indoor units)
Air-purifying Filter
10
A
0.05
X294not
(+356*)
X350
D)
Dimensions (HXWXTriple
mmOutdoor Units
These filters180are
medical
devices. Benefits
Double Outdoor Units
Air suction
grille*
* Locally obtained parts
9.5
Machine weight
Running current
Notes:
15.9
1. To prevent an increase in operation noise, avoid
Option
ø32 the air suction grille directly below the
I.D ø25XO.D
installing
chamber.
Both liquid andsuction
gas pipes
2. Grilles, piping connections, ducts, and installation
BYBS71DJW1
parts should be obtained locally. Slim Ceiling
Mounted Duct type models do not have drain-up
White
RX(Y)Q26TSY1(E)
RX(Y)Q30TSY1(E)
Suction grille (KDGF19A45)
pumps.
55X1,100
X500
RX(Y)Q28TSY1(E)
3. The
signal RX(Y)Q32TSY1(E)
receiver unit must be located near the
4.5 air suction inlet, because the unit includes a
sensor that detects room temperature.
12.7
Cooling Only
Power consumption
Microcomputer control
240 mm
Dimensions (HXWXD)
Sound levels (H/L/SL)*
Number of ports
26,
28, 30, 32 HP
2 steps
Temperature control
Cooling Only FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB
CDXS25EAVMA CDXS35EAVMA FDXS25CVMA FDXS35CVMA FDXS50CVMA FDXS60CVMA
Airflow rates (H)
Note: Remote controllers
other than the standard
accessory wireless remote
controller cannot be used.
40X950X950
kg
Weight
Space Saving Type
MODEL
Heat Pump
FTKS25D / FTKS35D
Power supply
FTXS20D / FTXS25E / FTXS35E
Dimensions (HXWXD)
White
mm
Dimensions (HXWXD)
Cooling Only
High-COP Type
Heat Pump
Standard Type
230X840X840
24
kg
Liquid (Flare)
Double Outdoor Units
12, 14, 16 HP
mm
HP
New Lineup
Outdoor Unit Lineup
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
FCQ35BVE
FCQ50BVE
FCQ60BVE
FCQ71BVE
MODEL
The single outdoor
unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
Cooling Only
Power supply
FDKS25EA
/
FDKS35EA
1-phase, 220 -240 V/220 V, 50/60 Hz
system flexibility to a new level.
Airflow rates
(H)
m3/min (cfm)
14.0 (494)
15.0 (530)
19.0 (671)
FDKS25CA
/ FDKS35CA
With the outdoor unit capacity increased
in (H/L)*
increment dB
of 2
HP, customers' needs can be precisely met.
(A)
Sound
levels
33/29
35/30
FDKS50C
/
FDKS60C
Outdoor units with anti-corrosionFan
specifications
(-E type on request) are designed specifically2for
use in areas which are subject to
speed
steps
Heat Pump CDXS25EA
/ CDXS35EA
salt damage and atmospheric pollution.
Temperature control
Microcomputer control
Mo/C
Specifications
Indoor Unit Lineup
Slim
Ceiling
Mounted
Duct
The
outdoor
unit
capacity
is upType
to 60 HP in increment of 2 HP.
Ceiling
Mounted
Cassette
Type
kg
8 as the adsorption and decomposition
7.5
Machine When
weightyou go out
in the room
such
of
34,When
36,you
38,are40
HP
42, 44 HP
46, 48, 50 HP
3
for
power
supply
(including
earth
wiring),
2
for
interunit
wiring
(outdoor
unit-BP,that
BP-BP),
Number of wiring connections
bacteria4 for
are
only
effective
for
substances
are
3-D Airflow
interunit wiring (BP-indoor unit)
collected
on
and
in
direct
contact
with
the
Titanium
combines Vertical
Main
mm
9.5X1
Liquid
Piping
Apatite
6.4X3 Photocatalytic Air-Purifying
6.4XFilter.
2
Branch mm
and Horizontal
connections
mm
19.1X1
Main
(Brazing)
Auto-Swing to
Gas
Bacteria
Test
15.9XRemoval
3
15.9X2
Branch mm
circulate air to every Heat insulation
Testing method: dropping method
Both liquid and gas pipes
Result certificate: No. 012553-1 and 012553-2
part of a room for
2.5 kW class to 7.1 kW class residential indoor units
Connectable indoor units
Testing organisation: Japan Spinners Inspecting Foundation
uniform cooling of even
Min. rated capacity of
kW
2.5
connectable indoor units
RX(Y)Q46TSY1(E)
large spaces.
RX(Y)Q42TSY1(E)
RX(Y)Q34TSY1(E)
RX(Y)Q38TSY1(E)
RX(Y)Q44TSY1(E)
RX(Y)Q36TSY1(E)
* This functionRX(Y)Q40TSY1(E)
is available forMax. rated capacity ofA uniform
kWtemperature
connectable indoor units
is achieved throughout
FTK(X)S50/60/71F.
thelength.
entire room.
Note: * Total auxiliary piping
20.8
RX(Y)Q48TSY1(E)
14.2
RX(Y)Q50TSY1(E)
Hotline: 0976 173 173
144636
Indoor Unit
Outdoor
UnitLineup
Lineup
Outdoor
UnitsIndoor Units with connection to BP units
Residential
Cooling Only /Cooling
Heat Pump
Only
Lineup
Wall Mounted Type
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building.
The single outdoor
unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing the
Cooling Only
FDKS25EA / FDKS35EA
system flexibility to a new level.
FDKS25CA / FDKS35CA
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.
FDKS50C / FDKS60C
Outdoor units with anti-corrosion specifications (-E type on request) are designed specifically for use in areas which are subject to
Heat Pump CDXS25EA / CDXS35EA
salt damage and atmospheric pollution.
FDXS25C / FDXS35C
FDXS50C / FDXS60C
Double Outdoor Units
12, 14, 16 HP
Triple Outdoor Units
34, 38 HP
Cooling Only
High-COP Type
Heat Pump
Standard Type
Space Saving Type
FTKS25D / FTKS35D
FTXS20D / FTXS25E / FTXS35E
Cooling Only
Cooling Only
Heat Pump
36, 40 HP
Standard accessory*
FTKS50B
FTKS50F / FTKS60F / FTKS71F
FTXS50F / FTXS60F / FTXS71F
42, 44, 46, 48, 50 HP
RXQ26THY1(E) RXQ28THY1(E) RXQ30THY1(E) RXQ32THY1(E) RXQ34THY1(E) RXQ36THY1(E) RXQ38THY1(E) RXQ40THY1(E)
RXQ6TY1(E) RXQ8TY1(E) RXQ8TY1(E) RXQ6TY1(E) RXQ6TY1(E)
RXQ8TY1(E)
–
–
–
Note: Remote controllers
other than the
standard
RXQ6TY1(E)
RXQ8TY1(E)
accessory wireless remote
controller cannot
be used.
RXQ8TY1(E)
RXQ8TY1(E)
RXQ6TY1(E) RXQ8TY1(E) RXQ8TY1(E) RXQ8TY1(E)
RXQ8TY1(E)
RX(Y)Q18THY1(E)
RX(Y)Q20THY1(E)
RX(Y)Q22THY1(E) RX(Y)Q30THY1(E)
RX(Y)Q32THY1(E)
RX(Y)Q24THY1(E)
CDXS-EA
series are
Low operation
200 mm
RX(Y)Q18TNY1(E)
RX(Y)Q20TNY1(E)
FDKS25EA FDKS35EA FDKS25CA FDKS35CA
CDXS25EA CDXS35EA FDXS25C FDXS35C
Dimensions (H x W x D) 200 x 700 x 620 mm 200 x 900 x 620 mm
Space
Saving Type 21 kg
25 kg
Weight
Airflow rate
(H)
8.7 m3/min
Single
Outdoor
Units
9.5
m3/min 10Outdoor
m3/min
Double
30 Pa
40 Pa
External static pressure
18, 20 HP
22, 24 HP
240 mm
Suspension bolt*
Suction duct*
Air discharge grille*
Units AIR
Signal
Wall Mounted indoor units achieve quiet sound
Triple Outdoor
Units
levels of 22
dB (A) during cooling operation.
34, 36 HP
(H/L/SL)
42,
44 HP
38, 40 HP
FTK(X)S20/25 FTK(X)S35 FTK(X)S50 FTK(X)S60 FTK(X)S71
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A)
Titanium apatite is a photocatalytic material with
high adsorption power. Titanium apatite also
effectively adsorbs
and
bacteria
46, 48,
50,decomposes
52, 54, 56, 58,
60 HP
across its entire surface. The photocatalyst is
activated simply by exposure to light.
Intelligent Eye with its infrared sensor
automatically controls air conditioner operation
according to human movement in a room. When
there is no movement, it adjusts the temperature
by 2˚C for energy savings.
RX(Y)Q42TNY1(E)
RX(Y)Q38TNY1(E)
RX(Y)Q34TNY1(E)
RX(Y)Q36TNY1(E)
RX(Y)Q46TNY1(E)
RX(Y)Q48TNY1(E)
RX(Y)Q50TNY1(E)
RX(Y)Q52TNY1(E)
Titanium Apatite
RX(Y)Q44TNY1(E)
RX(Y)Q40TNY1(E)
Air suction
grille*
air suction inlet, because the unit includes a
sensor that detects room temperature.
Air filter
Catches dust
RX(Y)Q54TNY1(E)
RX(Y)Q56TNY1(E)
RX(Y)Q58TNY1(E)
RX(Y)Q60TNY1(E)
Photocatalytic
Air-purifying Filter
34, 36, 38, 40 HP
3-D Airflow
combines Vertical
and Horizontal
Auto-Swing to
circulate air to every
part of a room for
uniform cooling of even
large spaces.
RX(Y)Q34TSY1(E)
RX(Y)Q38TSY1(E)
When you are in the room
Note: 1. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels,
motor,* Locally
and electric
obtained parts
receiver fan
AIR
component box, in addition to the fins of the heat exchanger. These models are designed specifically
Notes: for use in areas which are
subject to salt damage and atmospheric pollution. Please contact DaikinOption
for more information. 1. To prevent an increase in operation noise, avoid
installing the air suction grille directly below the
2. Specifications are based on the following conditions;
suction chamber.
2. Grilles,
piping connections,
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5
m, Level
difference:ducts,
0 m.and installation
parts should be obtained locally. Slim Ceiling
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit atMounted
a height
of
1.5
m.
Duct type models do not have drain-up
RX(Y)Q22TSY1(E)
RX(Y)Q18TY1(E)
RX(Y)Q26TSY1(E)
Suction higher
grille (KDGF19A45)
During actual operation, these values are normally somewhat
as a result of pumps.
ambientRX(Y)Q30TSY1(E)
conditions.
RX(Y)Q24TSY1(E)
RX(Y)Q20TY1(E)
RX(Y)Q28TSY1(E)
3. The signal RX(Y)Q32TSY1(E)
receiver unit must be located near the
Signals from the wireless remote controller are
transmitted to the signal receiver.
RXQ8TY1(E) RXQ12TY1(E) RXQ12TY1(E)
Stylish flat panel harmonises with your interior décor
Air filter
26, 28, 30, 32 HP
Chamber
RXQ8TY1(E)
RX(Y)Q42THY1(E)* Remote
RX(Y)Q48THY1(E)
controllers other than the standard accessory wireless remote controller cannot be used.
RX(Y)Q44THY1(E) RX(Y)Q50THY1(E)
RX(Y)Q46THY1(E)
Double Outdoor Units
Signal receiver wire
Length = 1,900 mm
RXQ8TY1(E)
RX(Y)Q36THY1(E)
RX(Y)Q40THY1(E)
RX(Y)Q38THY1(E)
RX(Y)Q22TNY1(E)
* Home
Leave Operation can be selected forRX(Y)Q28TNY1(E)
any temperature from 18 to
32˚CRX(Y)Q24TNY1(E)
for cooling operation and 10 to 30˚C for
heating operation.
RX(Y)Q30TNY1(E)
* Home
Leave Operation function must be set using the remote controller
RX(Y)Q26TNY1(E)
RX(Y)Q32TNY1(E)
when going to sleep or leaving the house, and after waking up or returning
home.
Air discharge duct*
RXQ8TY1(E)
RXQ8TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ12TY1(E) RXQ14TY1(E)
Standard
accessory*
Models in the FDKS-EA and
sound level
(H/L/SL)
only 700 mm in width and 21 kg in weight, so are
FDKS25
FDKS35
FDKS50
FDKS60
easily installed
Standard
Type in limited spaces. Just 200 mm in
C(F)DXS25 C(F)DXS35 FDXS50
FDXS60
height,
all models
can be installed
in roomsOutdoor
with
Double
Units
Single
Outdoor
Units
35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
as
little
as
240
mm
depth
between
the
drop
6, 8, 10, 12 HP
14, 16 HP
22, 24, 26 HP
18, 20 HP
28, 30, 32 HP
ceiling and ceiling slab, making them ideal for
Home Leave Operation prevents large rises or falls in
even shallow ceilings.
FDKS-EA
the indoor temperature by continuing operation* while
CDXS-EA
Great for
you are sleeping or out of your home. This means that
hotel use!
an air-conditioned welcome awaits when you wake or
return. It also means that the indoor temperature can
quickly return to your favourite comfort setting.
RX(Y)Q14TY1(E)
RX(Y)Q16TY1(E)
Only 700 mm
RXQ8TY1(E)
Standard accessory*
RXQ10TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E)
Slim and smooth design
RX(Y)Q26THY1(E)
suits your shallow
ceiling
RX(Y)Q34THY1(E)
RX(Y)Q28THY1(E)
RX(Y)Q12THY1(E)
RX(Y)Q14THY1(E)
RX(Y)Q16THY1(E)
134735
HP
18, RXQ14THY1(E)
20, 22, 24, 26,
28, 30, 32RXQ18THY1(E)
HP
RXQ12THY1(E)
RXQ16THY1(E)
RXQ20THY1(E) RXQ22THY1(E)
StandardRXQ24THY1(E)
accessory
RXQ6TY1(E) RXQ6TY1(E) RXQ8TY1(E) RXQ6TY1(E) RXQ6TY1(E)
RX(Y)Q6TY1(E)
RX(Y)Q8TY1(E)
RX(Y)Q10TY1(E)
RX(Y)Q12TY1(E)
New Lineup
Specifications
Indoor Unit Lineup
High-COP Type
Mo/C
Outdoor Unit Lineup
Ceiling
Mounted
TheSlim
outdoor
unit
capacityDuct
is upType
to 60 HP in increment of 2 HP.
RX(Y)Q36TSY1(E)
* This functionRX(Y)Q40TSY1(E)
is available for
FTK(X)S50/60/71F.
These filters are not medical devices. Benefits
Triple Outdoor Units
42, 44 HP
When you go out
such as the adsorption
46, 48, 50 and
HP decomposition of
bacteria are only effective for substances that are
collected on and in direct contact with the Titanium
Apatite Photocatalytic Air-Purifying Filter.
Bacteria Removal Test
Testing method: dropping method
Result certificate: No. 012553-1 and 012553-2
Testing organisation: Japan Spinners Inspecting Foundation
RX(Y)Q42TSY1(E)
RX(Y)Q44TSY1(E)
A uniform temperature
is achieved throughout
the entire room.
RX(Y)Q46TSY1(E)
RX(Y)Q48TSY1(E)
RX(Y)Q50TSY1(E)
Hotline: 0976 173 173
144836