FOR COMMENT

A
Rev
Owner

16-Jan-13
Date

S.J Cho
Prepared

C.K Kim
Checked

Y.M Cho
Approved

For Comment
Details of Revision

AES-VCM MONG DUONG
POWER COMPANY LIMITED
Consultant

POWER ENGINEERING CONSULTING
JOINT STOCK COMPANY 2
Contractor

Doosan Heavy Industries & Construction Co., Ltd
PC



Project :

T10206

MONG DUONG II 2 x 560MW(NET)
THERMAL POWER PLANT

UAS
DN02
UNIT
P0
KKS

Title

COMMISSIONING PROCEDURE
FOR
11KV MV SWITCHGEAR OF SITE TEST
Document No.

BBG
Reg. No.
840001
Rev.
A
Pages –No.

T10206-DN02-P0BBG-840001


1 of 27


Rev. A

Table of Contents

1.0 GENERAL PURPOSE.............................................................................................. 4
2.0 INSPECTION AND TEST ITEM...............................................................................7
2.1 Scope 7
2.2 Code and Standard...................................................................................................................7
2.3 General test...............................................................................................................................7
2.4 Circuit Breaker test...................................................................................................................7
2.5 Current Transformer test...........................................................................................................7
2.6 Potential Transformer test.........................................................................................................7
2.7 Protection Relay test.................................................................................................................7
2.8 Meter & TD test.........................................................................................................................7
2.9 Di-electric Strength & Insulation Resistance test.....................................................................7
2.10 Check for Phase Sequence(After energizing)........................................................................7
2.11 NSPB(Non-Segregated Phase Bus duct)...............................................................................7

3.0 INSPECTION AND TEST METHODS......................................................................8
3.4 Potential Transformer test ; Confirm the following items........................................................11
3.5 Protective Relay test ; Confirm the following items................................................................12
3.10 Contact Resistance test for Breaker and Bus bar spouts.;..................................................13
3.11 NSPB(Non-Segregated Phase Bus duct).............................................................................14
3.12 NSPB – Insulation Resistance Test ; Confirm The Following Items....................................14
3.13 NSPB – Di-Electric Strength Test.........................................................................................15

4.0 RESULT OF CHECK SHEETS...............................................................................16

4.1 General test record.................................................................................................................17
4.2 Circuit Breaker Test Record....................................................................................................18
4.10 NSPB - Bus Duct Test Record..............................................................................................27

5.0 ATTACHMENTS..................................................................................................... 28
Attachment 5.1 SLD FOR #1 11KV SWGR A(P1BBA01)
Attachment 5.2 SLD FOR #1 11KV SWGR B(P1BBA02)
Attachment 5.3 SLD FOR #2 11KV SWGR A(P2BBA01)
Attachment 5.4 SLD FOR #2 11KV SWGR B(P2BBA02)
Attachment 5.5 SLD FOR INTAKE SWGR A(P0BBG03)

Page 2 of 27


Rev. A
Attachment 5.6 SLD FOR FGD 11KV MV SWGR(P0BBJ01, P0BBJ02)
Attachment 5.7 SLD FOR CHS, ASH, NSPB
(P0BBE01, P0BDD01, P1BDD01, P2BDD01, 11KV NSPB 3200A)

Page 3 of 27


Rev. A

1.0
1.1

GENERAL PURPOSE
Introduction and commissioning boundary
This procedure covers the activities required for testing and commissioning of the following

Overall 11kV MV SWGR system for Unit 1, 2, consist of the below table

1.2

KKS Number

Description

P1BBA01

11kV SWGR for UNIT 1 (BOP, BLR, TBN)

P1BBA02

11kV SWGR for UNIT 1 (BOP, BLR, TBN)

P2BBA01

11kV SWGR for UNIT 2 (BOP, BLR, TBN)

P2BBA02

11kV SWGR for UNIT 2 (BOP, BLR, TBN)

P0BBG03

11kV SWGR for Intake

P0BBJ01


11kV SWGR for FGD 1

P1BBJ01

11kV SWGR for FGD 1A

P1BBJ02

11kV SWGR for FGD 1B

P0BBJ02

11kV SWGR for FGD 2

P2BBJ01

11kV SWGR for FGD 2A

P2BBJ02

11kV SWGR for FGD 2B

P0BBE01

11kV SWGR for CHS

P0BDD01

11kV SWGR for ASH (Common)


P1BDD01

11kV SWGR for ASH UNIT 1

P2BDD01

11kV SWGR for ASH UNIT 2

-

11kV NSPB, 3200 A

Scope of Commissioning Package
The commissioning package for Overall 11kV MV SWGR system, consist of the following
packages :
KKS Number

Description

Page 4 of 28


Rev. A

1.3
1.3.1

P1BBA01

11kV SWGR for UNIT 1 (BOP, BLR, TBN)


P1BBA02

11kV SWGR for UNIT 1 (BOP, BLR, TBN)

P2BBA01

11kV SWGR for UNIT 2 (BOP, BLR, TBN)

P2BBA02

11kV SWGR for UNIT 2 (BOP, BLR, TBN)

P0BBG03

11kV SWGR for Intake

P0BBJ01

11kV SWGR for FGD 1

P1BBJ01

11kV SWGR for FGD 1A

P1BBJ02

11kV SWGR for FGD 1B

P0BBJ02


11kV SWGR for FGD 2

P2BBJ01

11kV SWGR for FGD 2A

P2BBJ02

11kV SWGR for FGD 2B

P0BBE01

11kV SWGR for CHS

P0BDD01

11kV SWGR for ASH (Common)

P1BDD01

11kV SWGR for ASH UNIT 1

P2BDD01

11kV SWGR for ASH UNIT 2

-

11kV NSPB, 3200 A


The Safety Knowledge in operation
Before the start of any testing it should be confirmed that all power supplies to the system have
been isolated or that they are in a known condition. The Commissioning engineer is
responsible for the safety of those personnel working of the system Check for the presence of
harmful electrical or mechanical potential energy before starting work.

1.3.2

Project lockout / Tagout(LOTO) procedures must be adhere to all test area.

1.3.3

Fire is strictly prohibited on site, no smoking there must be a warning mark in hazardous area.

1.3.4

Strictly comply with the safety and environmental protection regulations of local government.

1.3.5

In order to ensure the reliable operation of every part of the system, strictly obey the
corresponding procedures.

1.3.6

Have a regular maintenance for the long-time standby equipment

1.3.7


Obey the relevant safety regulations of the power plant during commissioning all along. Ensure
the successful commissioning work.

1.3.8

All personnel directly involved with the commissioning that will attend a kickoff safety meeting to
review for the dangers. Ensure that all personnel understand the process and the operation.

Page 5 of 28


Rev. A
Any personnel involved in the commissioning have the authority to terminate the operation at
any time, if a serious problem or safety issue develops.

Page 6 of 28


Rev. A

2.0

INSPECTION AND TEST ITEM

2.1

Scope
This procedure is applied for the site inspection and test of the overall 11kV MV SWGR
on site.


2.2

Code and Standard
- IEC 62271-2
- IEC 62271-1
- Specification & Drawing

2.3

General test

2.4

Circuit Breaker test

2.5

Current Transformer test

2.6

Potential Transformer test

2.7

Protection Relay test

2.8

Meter & TD test


2.9

Di-electric Strength & Insulation Resistance test

2.10

Check for Phase Sequence(After energizing)

2.11

NSPB(Non-Segregated Phase Bus duct)

Page 7 of 28


Rev. A

3.0

INSPECTION AND TEST METHODS

3.1

General test

- Visual inspection ; Confirm the following items
No
Procedure


Criteria

1

Check the arranged condition of all panels

2

Check the mounted conditions of each component
& device

3

Check the tightened condition of bolts & the
marking of bolts for tightening

4

Check the wire conditions

5

Check the color of panels, painting condition

6

Check the Labeling of Power, Control wiring and
panels.

Method


Approval Spec & Drawing

- Dimension inspection ; Confirm the following items
No
Procedure

Visual
Torque
wrench

Criteria

Method
 

1

Check the dimension of panel enclosure
 
 
 

Approval Spec & Drawing
   

- Wiring check for CT,PT ; Confirm the following items
No
Procedure
1


Check the wire spec, color and size

 

Criteria
 

Method
Visual

Approval Spec

& Drawing
2
Check the continuity of wiring for CT & PT circuit
 
       
- Wiring check for CT,PT ; Confirm the following items
- Check of the operational sequence ;
All control circuits shall be
checked in accordance with the
schematic drawing by simulation
at the rated voltage
No
Procedure
Criteria
1
Input control power(AC/DC)
 

AC 230V, DC220V
2
Check the Annunciation & lamp
 
3
Check the Circuit breaker operation
 
(Local & Remote Mode)
 
Approval Spec
Check the electrical interlock(2 Out of 3 interlock & Drawing
4
checks)
5

Visual

 

 

Buzzer Tester
   

 

Method

Visual & Operation


Check the external contacts

Page 8 of 28


Rev. A

3.2

Circuit Breaker test

No

Procedure

1

Check the structure, nameplate data

2

Check the manual charging operation

3

Check the manual close operation
(In the test position)

4


Check the manual trip operation
(In the test position)

5

Nameplate
& Shop Test Report

Visual

Approval Spec & Drawing

Visual
Test Instrument

Approval Spec & Drawing

Visual
Test Instrument

check (In the Test position)
Check the automatic charging operation

7

Check the manual close
(In the connection position) and automatic
charging

8


Check the manual trip operation
(In the connection position)

9

Check the insulator

10

Check the circuit and contact

3.3

Method

Repeat 3 times close/open operation

6

11

Criteria

Operation characteristic Test

open : less than 40ms
close : less than 60ms
Time difference between
phase and phase :

less than 4ms

Current Transformer test ; Confirm the following items

No

Procedure

1

Verification with manufacturer's test certificates,
nameplates details etc

2

Ratio check

3

Polarity check

Subtractive

Check the continuity of wiring for CT
secondary circuit and ground connection
CT Excitation Test(To be performed with
CT which is used for protection relay)

Approval Spec
& Drawing


4
5
6

CB analyzer
(Refer to Note 5)

Insulation test on secondary winding
(Using DC 500V Megger)

Criteria
Approval
Drawing

Spec

Approval Spec
Above 5  

Method
&

Visual
CT Tester
(Refer to Note 1)
CT Tester or
Polarity checker
(Refer to Note 1, 2)
Visual

Buzzer tester
CT Tester
(Refer to Note 1)
Megger or CT Tester
(Refer to Note 1)

Page 9 of 28


Rev. A

▣ Note 1 : Test method for CT
- Safety Precaution
1. Wear the insulation glove, shoes and helmet.
2. Install the safety tape around test site.
- Test method
1. Make connections per diagram.
2. Select run test
3. Select resistance, excitation & ratio test
4. Select voltage and current range
5. Set Name Plate Ratio
6. Select default Test Note
7. Start test
8. Print test results

▣ Note 2 : Polarity check method for PT

1. Verify that the current transformer is being isolated from power source.
2. Make test setup as shown above.
A 6 10 V lantern-type battery can be used as DC voltage source.

3. Watching the analog-type meter, apply DC voltage momentarily by using the switch.( An analog-type
milli-ammeter or milli-voltmeter can be used on this test)
4. Record the polarity of current transformer.

Page 10 of 28


Rev. A

3.4

Potential Transformer test ; Confirm the following items

No

Procedure

1

Verification with manufacturer's test
certificates, nameplates details etc

2

Ratio check
- PT Primary voltage input and measuring of
secondary output

3


Insulation test(Using DC 500V Megger)
- Secondary- Ground, Primary-Ground

Criteria

Method
Visual

Approval Spec
& Drawing

2nd ; above 5 MΩ
1st ; above 50MΩ

Primary voltage
injection
(Refer to Note 3)
Megger

▣ Note 3 : Ratio check method for PT
After connecting the power supply to primary winding, read the primary voltage V1
and induced secondary voltage V2, Calculate the ratio with readings and record it
on attachment 1.

▣ Note 4 : Polarity check method for PT
Connect the circuit as follows(see Fig.2).
Close the switch(SW1) momentarily and observe the deflection of voltmeter(V). If
polarity is in accordance with terminal marking, voltmeter will deflect momentarily
to upscale when switch is closed.


Page 11 of 28


Rev. A
3.5

Protective Relay test ; Confirm the following items

No

Procedure

Criteria

1

Verification with manufacturer's test

 

certificates, nameplates details etc

 

2

Check the continuity of wiring

 


3

Check the set value of each output

 

 

contact and indications

4

Check the measuring values of display

5

Operation test

 

- According to the commission method

 

3.6

Buzzer tester

 


   

Approval Spec

 

& Drawing

 

 

Visual

 

 
   

 

Secondary injection

 

 

 

   


Relay tester

 
 

Meter test ; Confirm the following items
Procedure

Criteria

Method

 

1

Verification with manufacturer's test

 

certificates, nameplates details etc

 

2

Check the bolts, fittings, mountings

 


3

Check the enclosure for crack & integrity

 

Operation test

 

- Apply voltage or current to Test Termianl Block

 

- Check the measuring values

 

Approval

Visual

Spec

Relay tester

 

& Drawing


Secondary

 

injection

 

 

 

 

TD test ; Confirm the following items

No
1

 

Visual

recommended by Relay manufacturer

No

3.7


Method

Procedure

Criteria

Method

 

Verification with manufacturer's test
certificates, nameplates details etc

 

2

Check the bolts, fittings, mountings

 

3

Check the enclosure for crack & integrity

 

Operation test

 


- Apply voltage or current to CTT,PTT

 

- Check the measuring values

 

Visual
Approval Spec

Relay tester

 

& Drawing

Secondary injection

 
 

 

 

Page 12 of 28



Rev. A

3.8
No

1

2

3

3.9
No

Di-electric Strength & Insulation Resistance test ; Confirm the following items
Procedure
Insulation Resistance test
- This test conduct brefore and after
dielectric test using DC1000V Megger
※ Test Condition
- All electronic devices are disconnected
and C.T secondary circuits shorted.
- All CB is connected position and Close
- The fuse of PT is removed.
Di-electric Strength test
Main busbar parts and earthing bus bars
will be tested with the following voltage
for 1 minute
- Earth to phase : 30kV DC
- Phase to phase : 30kV DC

※ Test Condition(Common)
- All electronic devices are disconnected
and C.T secondary circuits shorted.
- All CB is connected position and Close
- The fuse of PT is removed.

2

Check the Phasing out between sources

1

2

Megger Tester

Criteria
  Clock-wise
Reference only

Method
  Phase Detector
Power Analyzer

Contact Resistance test for Breaker and Bus bar spouts.;
Confirm the following items
Procedure

Criteria


Method

Verification with manufacturer's test
certificates, nameplates details etc

 

Check the 1st and 2th part's connection

 

condition between breaker to bus bar
3

Connect the contact resistor.

 

 

contact resistance of Breaker

 

 

will tested with the following ampare

 


- phase to ground
; Above 50 
- Phase to phase
; Above 50 

Disruptive discharge
should not be
occurred

Procedure
Check the Phase sequence

No

Method

Check for Power Quality(After energizing)

1

3.10

Criteria

- input ampare : DC 100A

- Standard value

Contact resistance


 

: 100uΩ

tester

 
 
 

 

 

   

 

Page 13 of 28


Rev. A
▣ Note 5 : check method for Operation Characteristic Test
1. Check operating rightly by close, open CB in local /remote condition.
2. Earth by connecting earth wire to earth terminal of test equipment.
3. Connect main contact connection jack to main contact connection terminal and
then connect main contact wire to both ends of ES or bushing.
4. One end of close, open source connection jack connect to test equipment and
the other end connect to close, open terminal of VCB terminal
5. Figure out property data by operating circuit breaker(Operate over 3 times manually)

5.1 open : less than 40ms
5.2 close : less than 60ms
5.3 Time difference between phase and phase : less than 4ms

3.11

NSPB(Non-Segregated Phase Bus duct)

- Visual inspection ; Confirm the following items
No

Procedure

1

Arranged condition of Transformer

2

Mounted conditions of fix bolt

Criteria

Method

Approval Spec & Dwg

Visual
3


Tightened condition of bolts connections

4

Check the cleanliness of Transformer

3.12
No

1

NSPB – Insulation Resistance Test ; Confirm The Following Items
Procedure
Insulation Resistance test
- Measure of insulation resistance
- Using DC1000V Megger
※ Measured points
- Line to Line
- Phase to earth

Criteria

Method

; Above 50  

Megger Tester

Page 14 of 28



Rev. A
3.13

NSPB – Di-Electric Strength Test

No

Procedure

Criteria

Method

Di-electric Strength test
Apply the test voltage between each
1

electrically isolated

Disruptive discharge
should not be

- Earth to phase

occurred

DC dielectric tester
- Apply to table #1


- Phase to phase

#Table 1

Rated Voltage

Specified Value

600V or below

2500V

11kV

28000V

Auxiliary circuit

1500V

Apply Time

Remarks

1 Minute

 

Page 15 of 28



Rev. A

4.0

RESULT OF CHECK SHEETS

4.1

General Test Record

4.2

Circuit Breaker Test Record

4.3

Current Transformer Test Record

4.4

Potential Transformer Test Record

4.5

Protection Relay Test Record

4.6

Indicating Meter With Transducer Test Record


4.7

Transducer Test Record

4.8

Di-electric Strength & Insulation Resistance Test Record

4.9

Di-electric Strength & Insulation Resistance Test Record

4.10

NSPB – Bus Duct Test Record

Page 16 of 28


Rev. A
4.1

General test record
GENERAL TEST RECORD
(ECTR-E-COM-010A)

Sub
contractor


LS Industrial Systems Co., Ltd.

Equipment Description
Locatio
n
DWG
NO.

Contractor

Doosan Heavy Industries & Construction
Co., Ltd.

 

 

KKS NO.

 

 

Sheet NO.

 

TEST DATA
NO.


ITEMS

1

Visual Inspection

RESULT

REMARK

 

 

 

  Check the arranged condition of all panels

 

 

 

  Check the mounted conditions of each component & device

 

 


 

Check the tightened condition of bolts & the marking of bolts for
 
tightening

 

 

 

  Check the wire conditions

 

 

 

  Check the color of panels, painting condition

 

 

 

  Check the Labeling of Power, Control wiring and panels.


 

 

 

2

Check the dimension, wire spec, color and size of panel enclosure

 

 

3

Check the continuity of wiring for CT & PT circuit

 

 

4

Operational sequence test

 

 


 

 

 

 

 

 

 

 

 

 

  Check for control power line to supply power by multi-meter
Clsoe & open test for circuit breaker in test positon according to
sequence
Clsoe & open test for circuit breaker in run positon according to
sequence
Indicating lamp check according to operation condition of ciruit
breaker and fault
Electrical interlock check between upstream and downstream/each
other


 

 

 

 

 

 

 

 

 

  Binary input & output check for protection relay

 

 

 

  Trip test of MCCB by test button

 


 

 

  Trip test of protection relay by relay tester

 

 

 

  External contacts check(open & close condition)

 

 

NO.

TEST EQUIPMENT

CONTROL NO.

DUE DATE

1

 


 

 

 
 

Prepared by LSIS

 

 

DATE

 

 

 

NAME

 

 

 

SIGN.


 

 

 

Page 17 of 28


Rev. A
4.2

Circuit Breaker Test Record
CIRCUIT BREAKER TEST RECORD
(ECTR-E-COM-010B)

Sub contractor: LS Industrial Systems Co., Ltd.
Equipment Description : MV SWGR(SWGR No)

Contractor: Doosan Heavy Industries & Construction Co.,
Ltd
Document No.
Q-SITP-010

Location

 

DWG No.


 

Single Line DWG

 

KKS NO.

 

BREAKER NAME PLATE DATA
Manufacture

Type

Rating(Amps)

Serial Number

Operating
Voltage(V)

 

 

 

 


 

TEST DATA
1. Check The Breaker Rating and Identification Number is corrected
2. Insulation Resistance( )/Using by 500V Megger
Performed by(LSIS)

 
    Date
Ambient
Breaker Closed
Breaker Opened
L1
L2
L3
Temperature
L1
L2
L3
L1-L2
L2-L3
L3-L1

Pri - Sec
Pri - Sec Pri - Sec
Test Value
 
 
 

 
 
 
 
 
 
3. Operation Mechanism Check
Performed by(LSIS)
 
    Date
3.1 Manual Charging Operation
3.2 Manual Close Operation (In the Test position)
3.3 Manual Trip Operation (In the Test position)
3.4 Repeat 3 times Close/Open operation check (In the Test position)
3.5 Automatic Charging
3.6 Manual Close (In the Connection position) and Automatic Charging
3.7 Manual Trip Operation (In the Connection position)
3.8 Insulator Inspection
3.9 Circuit and contact Inspection
3.10 Breaker Mechanism is correct and No Wear and Damage
3.11 Lubrication is Correct in Accordance with Manual
Performed by(LSIS)
 
    Date
4. Operation Characteristic Test
   
   
 
 
 

   
 
 
         
order
1
2
3
4

work
Mesure CB trip time
Mesure CB close time
Mesure CB time difference
between phase and phase

cretia
less than 40ms
less than 60ms
Open
less than
4ms
Close

Attatch Time (open) record

Measure
 
 
 

 

Judgement
 
 
 
 

Attatch Time (Close) record
Performed by(LSIS)
   

4. Restoration
(CB and its circuit are restored to original configuration.)
Test Equipment
Control No.
Cal. Due Date

 

 

Performed by(LSIS)
Verified by(
)

 

 


 

Name/Signature

 

 

 

Date

 

 

 

 

 

 

Name/Signature

 

 


 

Date

 
   
 
 
 

Approved by

 

    Date
     
    Date

 

 
 
   

 

Page 18 of 28


Rev. A

4.3

Current Transformer Test Record
CURRENT TRANSFORMER TEST RECORD
(ECTR-E-COM-010C)

Sub contractor: LS Industrial Systems Co., Ltd.

Contractor: Doosan Heavy Industries & Construction Co., Ltd
Document
No.
DWG No.
KKS NO.

Equipment Description : MV SWGR(SWGR No)
 
 

Location
Single Line DWG No.
Nameplate Ratio :
Serial No.

Q-SITP-010
 
 

Used For(Meter or Relay No.):
Rφ:


Yφ:

Bφ:

TEST DATA
1.
Visual
 
   
   
Inspection
Current transformer is installed
satisfactory.

 

 

2. Ratio Tests

 

 

 

 

 


Accuracy Class :
Calculated Ratio :
Accept Error ≤ ±
 

 

3. Polarity Tests

 

 

 

 

 

 

   

Performed by(LSIS):

 

 

 


   

 

 

□Volt

 

 



Date
:

%er
r
 
 
 

rati
o
 
 
 


 

 

 

 

 

 

%err
 
 
 
Date
:
 

 

 

 

Date :

Performed by(LSIS):


 

 

 

Date :

5. Insulation test on secondary winding(Using DC 5000V Megger)

 

 

 

 

 

 

%er
r
 
 
 

 


 

 

 
 

 

 

□ Additive

 

 

   

 

□ Subtractive

Performed by(LSIS):

 

rati
o
 

 
 

□Not Required

 

 



 

 

 



rati
o
 
 
 

 

 

 


 

Polarity Test Result

 

Measured Ratio

Single Tap
 
Multi
Tap
 

[%]

Check Applied Method

 

 

 

Check Applied Method :

 

 


 
Performed
by(LSIS):

 

 

 

 

 

 

4. Secondary Circuit and ground connection Check
 

 

 

 

 

 


   

All secondary winding - Ground : Accept : Above 5  

 

 

 

 

 

 

 

 

 

 

 

   

Performed by(LSIS):


6. Restoration :

 

 

 

   

 

 

 

 

 

 

 

Date :

 

 


 

 

 

 

CT and its circuit are restored to original configuration.
 

 

 

 

Test Equipment

 

 

   

 

 

Performed by(LSIS):


Control No.

Due Date

 

 

 

Verified by(

 

 

Date:

 

 

 

 

 

 


 

 

 

 

)

 

Name/Signature

 

 

 

 

 

 

   

 


 

 

 

 

 

 

 

 

   

 

 

 

Date
 
Approved by

 


 

 

Name/Signature

 

 

 

Date

 

 
 

 

 

Page 19 of 28


Rev. A
4.4


Potential Transformer Test Record
POTENTIAL TRANSFORMER TEST RECORD
(ECTR-E-COM-010D)

Sub contractor: LS Industrial Systems Co., Ltd.

Contractor: Doosan Heavy Industries & Construction Co., Ltd

Equipment Description : MV SWGR(SWGR No)
Location
 
Single Line DWG No.
 

Document No.
DWG No.
KKS NO.

Q-SITP-010
 
 

Used For(Meter or Relay No.):
NAMEPLATE DATA
MFGR.:

Insu.Rating[BIL]:

Nominal Ratio :


Accuracy Class :

Serial No.

Rφ :
     

1. Visual Inspection

 

 

[kV]

Yφ :
TEST DATA
     

 

Rated Pri .Volt:

[V]

Thermal Rating :
at
[℃]
Bφ :


[VA],

     

 

   
 

Potential transformer is installed satisfactory.
 
2. Ratio and Polarity

        Performed by(LSIS) :
   
 
 
     

  Date :
 

 

 

 

Performed by(LSIS) :
Date :


 
 

     

 

 

    Ratio

 







 

 

 

     

3. Insulation test on Primary & Secondary winding with ground.


   
Readings

 

   

All secondary winding – Ground : Accept: above 5 MΩ(Using DC 5000V Megger)
All primary winding – Ground : Accept: above 5 MΩ(Using DC 5000V Megger)
 

        Performed by(LSIS) :
 

4. Restoration Completed
 

 

     

        Performed by(LSIS) :

  Date :
 

     

 


  Date :

 
 

   
   

Remark :
Test Equipment

Control
No.

Due Date

 

 

 

 

 

 

Date


 

 

 

Approved by(

 

 

 

 

 

 

Verified by(

 

)

 

   
 


Name/Signature
   

 

   

)
 

Name/Signature
Date

Page 20 of 28


Rev. A

4.5

Protection Relay Test Record
Protection Relay Test Record
(ECTR-E-COM-010E)

Sub contractor: LS Industrial Systems Co., Ltd.
Equipment Description : MV SWGR(SWGR No)
Location
 
Single Line DWG No.

 
Manufacturer
Relay Description :
C.T Ratio

 

Type or Model

 

P.T Ratio

Contractor: Doosan Heavy Industries & Construction Co., Ltd
Document No.
Q-SITP-010
DWG No.
 
KKS NO.
 
NAMEPLATE DATA
 
Serial No.
 
 
TEST DATA

 

Rated current


1. Visual Inspection
2. Mashalling-Trip Relay

3. Mashalling-LED Indications

4. Measuring Values
Injection
[Current/Voltage]
50% [0.5A/31.8V]
R:
75% [0.75A/47.6V]
R:
100% [1A/63.5V]
R:
5. Secondary injection test
Setting
Test Item
tap/time
50

 
 
 

Test
Value(%)
100
110
110

I2 *3
I2 *3

Standard
time(Sec)
 
 
 
 
 

R/Y/B

I Motor
Start
* 0.9

 

Actual
time(Sec)
 
 
 
 
 
 
 

R/Y/B


200
300

 
 

I Motor
Norminal
*5

 

G
G
G
R/Y/B
R/Y/B

46

49

51LR

Test
Phase
R/Y/B
R/Y/B
R/Y/B

R/G

Test
Value(%)
200
200
300
500
200
200
200
100
100

/
/
/

Actual
time(Sec)
 
 
 
 
 
 
 
 
 


50G(N)-2
50G(N)-1
50G(N)
27
59

81
87M
87L

Y:
Y:
Y:

Tolerances

Standard
time(Sec)
 
 
 
 
 
 
 
 
 

R/Y/B


Setting
tap/time

 
 
 

Test
Phase
R/Y/B

51

Test Item

/
/
/

Measuring Values
Current[A] / Voltage[kV]
 
/
  B:
 
 
/
  B:
 
 

/
  B:
 

 
 
 

N:
N:
N:

 
 
 

/
/
/

 
 
 

1% of measured
value or 0.5% of
I / VNom

Pick-up
(A or V)

 

Drop-out
(A or V)
 

 

 

 
 
 
 
 

 
 
 
 
 

Pick-up
(A or V)
 
 
 
 

Drop-out

(A or V)
 
 
 
 

 

 

 
 
 

 

 

□ Check the
66 Trip &
Restart Inhibit

 

 

R/Y/B

66


6. Results
:
Remarks :
Test Equipment
 
 

Tested by(LSIS) :
Control No.
 
 

Due Date
 
 

Date :

Verified by(
)
Name/Signature
Date

Page 21 of 28


Rev. A

 
 


 
 

 
 

Approved by
Name/Signature
Date

Page 22 of 28


Rev. A

4.6

Indicating Meter with Transducer Test Record
Indicating Meter with Transducer Test
Record(ECTR-E-COM-010F)

Sub contractor: LS Industrial Systems Co., Ltd.

Contractor: Doosan Heavy Industries & Construction Co., Ltd

Equipment Description : MV SWGR(SWGR No)

Document No.


Q-SITP-010

Location

 

DWG No.

 

Single Line DWG No.

 

KKS NO.

 

1.

NAMEPLATE DATA
Type or Model
 
P.T Ratio
 

 
 

Manufacturer

C.T Ratio

TEST DATA
Visual Inspection
 
               
1.1 Instrument is de-energized/Check the nameplate data
1.2 Bolts, Fittings, Mountings are tightened

 
 

Serial No.
Accuracy

       

 

 

 

     

           
 
 
 


1.3 Check the enclosure for crack & integrity
   
2.

 

 

   

Description

Rating

Current
transformer
for metering

Voltage
transformer
for metering

 

   

Performed by(LSIS):

Date :


Expected
Value
   

Actual
value
 

Phase

Injected
Value

R

0.25A

Y

0.25A

 

 

 

B

0.25A


 

 

R

0.5A

 

 

Y

0.5A

 

B

0.5A

R

1A

13200/
110


Error(%)

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 


 

 

 

 

 

 

1A

 

 

 

 

 

Y
B
R-Y

1A
1A

110V

 
 
 

 
 
 

 
 
 

 
 
 

 
 
 

110V
110V

 
 
 

 

 
 

 
 
 

 
 
 

 
 
 

P(MW)

Y-B
B-R
--

Q(MVAR)

--

 

 

 


 

 

S(MVA)

--

 

 

 

 

 

 

 

 

 

 

 


 

 

 

 

   
   
   
   
   
Performed by(LSIS):

 
 
 
 
 

 
 
 
 
 

 
 

 
 
 

F(HZ)

--

--

PF(%)

--

KWH
KVARH

--R
R
R

Current
transducer
3.

     

Calibration by secondary injection

--


1A/110V
36.9Deg(5
Min)

0A
0.5A
1A

Date :

Restoration is completed
Performed by(LSIS):

Remarks :
Test Equipment
 
 
 
 
 
 

Control No.
 
 
 
 
 
 


Due Date
 
 
 
 
 
 

Date :

Verified by(
)
Name/Signature
Date
Approved by
Name/Signature
Date
     

 

 

 

   

 


 

 

Page 23 of 28


Rev. A

4.7

Transducer Test Record
Transducer Test Record
(ECTR-E-COM-010G)
Contractor: Doosan Heavy Industries & Construction Co.,
Ltd

Sub contractor: LS Industrial Systems Co., Ltd.
Equipment Description : MV SWGR(SWGR No)
Location

 

Single Line DWG No.

 

Manufacturer

 


C.T Ratio

 

Document No.

Q-SITP-010

DWG No.

 

KKS NO.

 

NAMEPLATE DATA
Type or Model
 

Serial No.

 

Accuracy

 

 


P.T Ratio
TEST DATA

1.

 

 

 

 

 

 

                       
 

1.2 Bolts, Fittings, Mountings are tightened

 

1.3 Check the enclosure for crack & integrity

 

2.


 

 

 

 

     

 

    Performed by(LSIS):
       

Calibration by secondary injection
Description

Rating

 
 

3.
 

                 

1.1 Instrument is de-energized/Check the nameplate data


 

 

 

Visual Inspection

Phase

Injected
Value

 

 

 

 

 

 

 

 


 

 

 

 

     

 

 

 

 

 

     

Expected
Value

 

 

 


           

                       

Actual
value

Error(%)

Remarks

 

 

 

 

 

 

 

 

 


 

 

 

 

 

           
 

 

    Performed by(LSIS):

Restoration is completed
 

 

Date :

 

Date :
 

 


 

 

    Performed by(LSIS):

                       
Date :

             

Remarks :

Test Equipment

Control No.

Due Date

Verified by(

 

 

 

Name/Signature


 

 

 

Date

 

 

 

 

 

 

Name/Signature

 

 

 

Date


                     

)

 
                       

Approved by :

 

 

 
 

                       

Page 24 of 28


Rev. A
4.8

Di-Electric Strength & Insulation resistance Test Record
DI-ELECTRIC STRENGTH &
INSULATION RESISTANCE TEST RECORD
(ECTR-E-COM-010H)

Sub contractor: LS Industrial Systems Co., Ltd.


Contractor: Doosan Heavy Industries & Construction Co., Ltd

Equipment Description : MV SWGR(SWGR No)
 

Location

 

Amb. Temp.

Document No.

Q-SITP-010

Single Line DWG

 
 

Humidity(%)
DI-ELECTRIC STRENGTH TEST DATA

Circuit

Test condition

Duration
(Min)


Test
Volt

Judgement
(Disruptive discharge
should not be occurred)

Remarks

1 Min.

30kV

 

 

1 Min.

30kV

 

 

1 Min.

30kV


 

 

CB is closed.
R-Y+B+E

PT is opened.
CT is shorted.
CB is closed.

Y-B+R+E

PT is opened.
CT is shorted.
CB is closed.

B-R+Y+E

PT is opened.
CT is shorted.

 

 

 

 


    Performed by(LSIS):

         

Date :

   

 

 

 

 

 

INSULATION RESISTANCE TEST DATA
Circuit

 

Test condition

Test

Acceptance Criteria

Test Results(GΩ)


R-Y+B+E

Before
Di-electric

DC 1000V

 

Y-B+R+E

Before
Di-electric

DC 1000V

 

B-R+Y+E

Before
Di-electric

DC 1000V

R-Y+B+E

After
Di-electric


DC 1000V

 

Y-B+R+E

After
Di-electric

DC 1000V

 

B-R+Y+E

After
Di-electric

DC 1000V

 

 

 

   

 

50MΩ Above

  Performed by(LSIS):

           

Date :

   

 

 

 

 

 

 

 

 

 

 


 

Remarks
Test Equipment

Control No.

Due Date

Verified by(

)

 

 

 

Name/Signature

 

 

 

Date

 


 

 

 
   

 

 

 

 

Approved by
 

Name/Signature
 

 

 

 

Date


   

 

 

 

 

 

Page 25 of 28


×