PHF12-360W-X
pure lead tech.
FEATURES
Application Fields
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Low self-discharge rate, lower than 2% capacity loss
per month
Gas recombination efficiency over 99%
Computer designed lead, Pure lead
grid for high power density.
The battery is designed for high rate usage
Excellent high rate discharge performance
Long Life
Office Machines and Computers
Telecommunications
UPS Equipment
Electrical facilities
Vending machine
High consistency
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
12 V
360W/cell @ 15 min rate F.V.(1.67V/cell)
31.5Kg(69.4 lbs.)
Internal Resistance
Max. Discharge Current
3.2m
(Fully Charged )
900 A (5 sec.)
Max. Charge Current
Operating Temperature Range
40 A
Charge -10 oC~60oC
Discharge -20oC~60oC
Storage. -20oC~60oC
Container Material
ABS
Dimensions
SI Units
English Units
Length
330mm
13.0inch
Width
171mm
6.73inch
Height
215mm
8.46inch
Total Height
220mm
8.66inch
Constant Current Discharge ( Amperes ) at 25 ℃
End Point
Volts/Cell
5min
10min
15min
30min
1.60
351
271
222
1.67
320
249
205
1.75
288
227
1.80
276
218
45min
60min
90min
138
101
78.7
55.4
128
93.8
73.3
51.7
188
117
86.4
67.8
47.9
181
114
84.3
66.3
46.9
Constant Power Discharge ( Watts per cell ) at 25 ℃
End Point
Volts/Cell
5min
10min
15min
30min
45min
60min
90min
1.60
627
470
380
243
180
140.00
100.00
1.67
587
444
360
231
172
134.50
96.40
1.75
547
418
338
219
164
129.00
92.40
1.80
520
400
325
211
158
125.00
89.80
(Note)The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.
All data shall be changed without prior notice, VISION reserves the right to explain and update the information contained hereinto.
A/0
REV. Mar. 2011
Powered by
Shenzhen Center Power Tech. Co., Ltd