PHF12-670WS-X
pure lead tech.
FEATURES
Application Fields
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Low self-discharge rate, lower than 2% capacity loss
per month
Gas recombination efficiency over 99%
Computer designed lead, Pure lead
grid for high power density.
The battery is designed for high rate usage
Excellent high rate discharge performance
Long Life
Office Machines and Computers
Telecommunications
UPS Equipment
Electrical facilities
Vending machine
High consistency
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
12 V
670W/cell @ 15 min rate F.V.(1.67V/cell)
61Kg(134.4 lbs.)
Internal Resistance
Max. Discharge Current
3m
(Fully Charged )
1000 A (5 sec.)
Max. Charge Current
Operating Temperature Range
80 A
Charge -10 oC~60oC
Discharge -20oC~60oC
Storage. -20oC~60oC
Container Material
ABS
Dimensions
SI Units
English Units
Length
522mm
20.55inch
Width
238mm
9.37inch
Height
218mm
8.58inch
Total Height
223 mm
8.78inch
Constant Current Discharge ( Amperes ) at 25℃
End Voltage/
10min
15min
20min
30min
45min
volt per cell
1.60
500
378
304
230
60min
169
139
1.67
462
354
285
216
159
131
1.75
423
330
265
201
149
122
1.80
397
314
253
193
142
116
Constant Power Discharge ( Watts per cell ) at 25℃
End Voltage/
10min
15min
20min
30min
45min
volt per cell
60min
1.60
950
720
575
424
310
250
1.67
878
670
539
403
294
238
1.75
804
620
501
385
283
229
1.80
754
590
478
370
273
223
(Note)The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.
All data shall be changed without prior notice, VISION reserves the right to explain and update the information contained hereinto.
A/0
REV. Mar. 2011
Powered by
Shenzhen Center Power Tech. Co., Ltd