Doors for each
room.


Direction of
opening doors
for the room
containing less
than 15 people


KT : 02 Article


7.24


The smallest
width of
opening doors
for each room


KT: 01 ;KT :
02 and KT:09


Bc= 0,7m B>/0,8m Article


7.17
[1]


Unaccept
able


Hydraulic
height



KT:09 hMIN=1,9m hMIN>/1,9m Article


7.18
[1]
2 Corridor and elevator


Length KT: 01 and


KT : 02


The farthest
length to the stair
is 32.5m


From the farthest to ladder is
40m (for office building and
for rent)


Article
7.7
Table
5
[1]


Acceptab
le


Width KT: 01 and



KT : 02


The smallest
width of the hall.


>/1.8m Article


4.5
TCVN
3978-
1984


Acceptab
le


The cabinet in
the Corridor


KT: 01 ; KT :
02


No cabinet in the
Corridor


No wall cabinet in the hall,
except from the technical
cabinets and the fire


extinguisher for firefighting



Article
7.19
[1]


Acceptab
le


Stair wall KT: 08 The covering and bearing


structure has limited


refractory not smaller than 60
minutes


Article
8.4
[TCV
N
6160-
1996]


Acceptab
le


Obstacles in
the elevator


KT: 01;
KT : 02



No obstacles in
the elevator.


No obstacles in the escape
elevator


Article
7.20


</div>
<span class='text_page_counter'>(2)</span><div class='page_container' data-page=2>

KT: 03 [1]


3. Emergency ladder


KT: 01 and
KT : 02


The ladders from
the ground to
upstairs are
ventilate


The ladders from the ground
to upstairs must be ventilate


Acceptab
le


Number of
Emergency
ladder



KT: 01 and
KT : 02


2 No less than 02 Emergency


Ladders with emergency exit


Article
7.7
[1]


Acceptab
le


The width of
stairs


KT : 08 The smallest
width of two
<b>sides of the stairs </b>
is 1,2 m


The smallest horizontally
clearance is 1,05m


Article
7.17
[1]



Acceptab
le


Total width of
two sides of
ladder


KT : 08 ∑btt= 1,43+1,475=2,9m ∑bct=
KxN/100


=1,0x500/ 100= 1,5m


Article
7.15
[1]


Acceptab
le


The gap
between two
sides of the
stairs


KT : 08 The gap between
two sides of the
stairs is 345mm


The gap between two sides of
stairs at least is 1,05



Article
7.17
[1]


Acceptab
le


The width of
the landing


KT : 08 The smallest
width of the
landing is 345m


The width of the landing is
not smaller than the width of
two sides of elevators


Article
7.20
[1]


Acceptab
le


Obstacles in
the elevator


No obstacles in


the elevator


No obstacles in the escape
elevator


Article
7.20
[1]
4


Safe distance from fire
The Distance
to the nearby
constructions


The distance
from the
independent
building to
the others
>/15m


The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the Fire
walls


</div>
<span class='text_page_counter'>(3)</span><div class='page_container' data-page=3>

5



Accessibility for Firefighting
Distance to the


nearby
constructions


The distance
from the
independent
building to
the others
>/15m


The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the Fire
walls


Article
8.3 [1]


H- Female dormitory
Door


Number of exit KT:01 1 door >/2 doors Article


7.7
[1]



unaccept
able
Doors


Direction of
opening doors for
the room


containing less
than 15 people


KT:01 and
KT: 02


Open inside Open inside is acceptable Article
7.24
[1]


Acceptab
le


The smallest
width of doors
for each room


KT:01; KT:
02 and KT :
08


Bc=0,7 B>/0,7 Article



7.17
[1]


Unaccept
able


Hydraulic height KT: 08 hMIN= 1,9m hMIN>/ 1,9m Article


7.18
[1]


Acceptab
le


Corridor and inside elevator


Length KT:01and


KT: 02


The farthest
distance to the
elevator is 16,6m


The farthest place to elevator (
Offices and rented offices ) is
40 m


Article


7.7
Table
[1]


Acceptab
le


Width KT:01and


KT: 02


The smallest
width of corridor:
2,02m


>/1,8m Article


4.5
TCVN
3978-
1984


Acceptab
le


Cabinet in the
hall


KT:01; KT:
02 and


KT:09


No cabinet in the
hall


No wall cabinet in the hall,
except from the technical
cabinets and the box for


Article
7.19
[1]


</div>
<span class='text_page_counter'>(4)</span><div class='page_container' data-page=4>

firefighting


Stair wall KR:09 110mm Bearing and covering


structure are not limited
refractory smaller than 60
minutes


Article
8.4
[TCV
N
6160-
1996]


Acceptab
le



Obstacles in the
elevator


KT:01 ; KT:
02; KT: 08


No Obstacles in
the elevator


No Obstacles in the escape
elevator


Article
7.20
[1]


Acceptab
le


Emergency
ladder


KT:01 and
KT: 02


No obstacles No obstacles Article


8.4
[TCV


N

6160-1996]


Acceptab
le


Number of
Emergency
ladder


KT:01 and
KT: 02


1 Emergency
ladder


Number of emergency out of
the house with the farthest to


Article
7.7
[1]


Acceptab
le


The width of the
landing



KT: 09 The smallest
width of the
landing is 1,43m


The smallest hydraulic width
is 1, 05 m


Article
7.7
[1]


Acceptab
le


The total width
of the landing


KT: 09 ∑btt=


1,43+1,475=2,9m


∑bct= KxN/100= 1,0x500/


100= 1,5m


Article
7.15
[1]


Acceptab


le


The gap between
two sides of the
stairs


KT: 09 The gap between
two sides of the
stairs is 345mm


The smallest gap between the
<b>two sides of the stairs is </b>
50mm


Article
7.17
[1]


Acceptab
le


The width of the
landing


KT: 09 The smallest
width of the


The width of screening off
stairs is not smaller than the



Article
7.20


</div>
<span class='text_page_counter'>(5)</span><div class='page_container' data-page=5>

<b>landing : </b>
6,355m


width of two sides of the
stairs


[1]
Safe distance from fire


The distance to
the nearby
constructions


The distance
from the
independent
building to
the other
structures>/15


KT: 02; KT:06
and KT :07


The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the


firewalls


Article
8.3
[1]


Acceptab
le


Firefighting traffic
The distance
to the nearby
constructions


The distance
from the
independent
building to
the other
structures>/15


KT: 02; KT:06
and KT :07


The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the
firewalls



Article
8.3
[1]


Acceptab
le


III. Firefighting system
3 Checking


Content


Drawing
symbols


design Standard


TCVN 2622-1995
[1]


specifi
ed
standa
rd
provisi
ons


Recomm
endation



3.1 Fire fighting system indoor
1 Choose agent


fire according
to fuel


Explanation water Feature of the solid burning Article
31
table 3
TCVN

5760-1993


Acceptab
le


2 System to
provide water
for fire
fighting


Explanation
PCCC: 02;
PCCC: 03


Pipeline is
designed to
provide water for
fire fighting
within



the firefighting system is
Designed inside for


administrative offices with
over six-level height, public
sites have over 5000m3


Article
10.12
[1]


Acceptab
le


3 Arrangement
of water pipes


Explanation
PCCC:09 to


Placed in the
halls and


Placed at the entrance on the
landing position, in the hall,


</div>
<span class='text_page_counter'>(6)</span><div class='page_container' data-page=6>

for firefighting
system



PCCC: 27 corridors of each
floor.


easily and visibly. [1]
4 Water pipe


height


Explanation
PCCC: 07


The distance
from The Center
of water pipe to
the floor is
1,25m


The distance from The Center
of water pipe to the floor is
1,25m


Article
10.19
[1]


5 Tubs of
firefighting
box


Explanation


PCCC: 07


Each box has
valve, coil of
wire 20 m and a
tub B 50


Each box has valve which can
be locked, the length of water
pipe based on reality.


Article
10.20
[1]
6 Water pipe


system for
one-sided
wall.


Explanation
PCCC:03


There are 68
water boxes
placed on
one-sided wall in the
building. Water
supply system for
firefighting is


designed in the
form of a ring.


If 12 water boxes are placed
inside the building, the water
supply system must have at
least 2 water pipes to carry
water into the building and is
designed in the form a ring


Article
10.16
[1]


7 Water volume
of each box


Explanation 2,51 l/s Table 14 TCVN
2622-1995


10.14
[1]
8 Water


pressure of
water pipe


Explanation Water pressure of
water pipe is
assured by fire


extinguisher


Water pressure of water pipe
inside the building must
assure fat beams with the
height >/6m


Article
10.15
[1]
9 water stored,


anti-fire water
tank


Explanation
PCCC:07


Underground
water tank is the
volume is 135m3


The water should be stored
must be based on the volume
needed for firefighting for 3
hours. Measured water
volume stored


Wc



Article
10.22
[1]
Article
10.27
[1]
10 Diameter of


water pipes


PCCC:08
To PCCC:09


The main water
pipe


The water pipe should be steel
pipe with diameter is 50m.


</div>
<span class='text_page_counter'>(7)</span><div class='page_container' data-page=7>

4513-88]
11 Number of


plumbers


Explanation
PCCC:04


There are 2
plumbers only
for firefighting



Plumbers for housing
consumer, and firefighting
separately or combinatedly
extra plumbers has equivalent
to the main plumbers


Term
a,
Article
10.24
[1]
12 Fire pumps


-an electric
pump


-a petrol pump


explanation +Capacity:
22,5KW


+current: Q MAX
= 48m3/hour
+ column


pressure: HMAX
= 84,5m


+Capacity:


22,5KW


+current: Q MAX
= 48m3/hour
+ column


pressure: HMAX
= 84,5m


Ensure current and column
pressure when occur fire.
Calculated:


+ H>/ 75,1 m.c.n
+Q >/ 45 m3/hour


acceptabl
e


Number of box needed for each floor.
1 Administrative


house


PCCC:09 and
PCCC:10


1 box High Administrative house is
allowed to set 1 box



Article
10.14
[1]


Acceptab
le


2 Kindergarten PCCC:21and
PCCC:22


1 box Table 14 TCVN 2622-1995 Article


10.14
[1]


Acceptab
le


3 Primary
school


PCCC:17and
PCCC:18


2 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]


Acceptab
le



4 Secondary
school


PCCC:19 and
PCCC:20


1st<sub>:05 boxes</sub>


2nd<sub>: 03 boxes</sub>


Table 14 TCVN 2622-1995 Article
10.14
[1]


Acceptab
le


5 Library PCCC:24 and


PCCC:25


2 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]


Acceptab
le


6 Teacher


dormitory


PCCC:15and
PCCC:16


2 boxes Table 14 TCVN 2622-1995 Article
10.14


</div>
<span class='text_page_counter'>(8)</span><div class='page_container' data-page=8>

[1]


7 Male


dormitory


PCCC:11 and
PCCC:12


02 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]


Acceptab
le


8 Female
dormitory


PCCC:13 and
PCCC:14



01 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]


Acceptab
le


<b>Fire fighting system outdoor</b>
<b>Fire fighting </b>


<b>system </b>
<b>outdoor</b>


PCCC:02and
PCCC:03


fire extinguisher High building must be
designed and set firefighting
inside and outside.


Article
12.5
[1]


Acceptab
le


fire extinguisher
fire



extinguisher


PCCC:08and
PCCC:28


45 cylinders MT3
and 90 containers
MFZ4 is 135


Need to set fire extinguisher
system


QCXD
VN
1997
TCVN
5760-
1993


Acceptab
le


Position of
fire


extinguisher


PCCC:09 to
PCCC: 27



On the corridor,
clear sight


On the corridor, clear sight Article
5.2:
TCVN
7435/1
- 2004


Acceptab
le


Number of
fire


Extinguisher
for each floor.


PCCC:09 to
PCCC: 27


>/2 boxes Each floor must set at least 2
boxes


Article
7.2.2: