Doors for each
room.
Direction of
opening doors
for the room
containing less
than 15 people
KT : 02 Article
7.24
The smallest
width of
opening doors
for each room
KT: 01 ;KT :
02 and KT:09
Bc= 0,7m B>/0,8m Article
7.17
[1]
Unaccept
able
Hydraulic
height
KT:09 hMIN=1,9m hMIN>/1,9m Article
7.18
[1]
2 Corridor and elevator
Length KT: 01 and
KT : 02
The farthest
length to the stair
is 32.5m
From the farthest to ladder is
40m (for office building and
for rent)
Article
7.7
Table
5
[1]
Acceptab
le
Width KT: 01 and
KT : 02
The smallest
width of the hall.
>/1.8m Article
4.5
TCVN
3978-
1984
Acceptab
le
The cabinet in
the Corridor
KT: 01 ; KT :
02
No cabinet in the
Corridor
No wall cabinet in the hall,
except from the technical
cabinets and the fire
extinguisher for firefighting
Article
7.19
[1]
Acceptab
le
Stair wall KT: 08 The covering and bearing
structure has limited
refractory not smaller than 60
minutes
Article
8.4
[TCV
N
6160-
1996]
Acceptab
le
Obstacles in
the elevator
KT: 01;
KT : 02
No obstacles in
the elevator.
No obstacles in the escape
elevator
Article
7.20
KT: 03 [1]
3. Emergency ladder
KT: 01 and
KT : 02
The ladders from
the ground to
upstairs are
ventilate
The ladders from the ground
to upstairs must be ventilate
Acceptab
le
Number of
Emergency
ladder
KT: 01 and
KT : 02
2 No less than 02 Emergency
Ladders with emergency exit
Article
7.7
[1]
Acceptab
le
The width of
stairs
KT : 08 The smallest
width of two
<b>sides of the stairs </b>
is 1,2 m
The smallest horizontally
clearance is 1,05m
Article
7.17
[1]
Acceptab
le
Total width of
two sides of
ladder
KT : 08 ∑btt= 1,43+1,475=2,9m ∑bct=
KxN/100
=1,0x500/ 100= 1,5m
Article
7.15
[1]
Acceptab
le
The gap
between two
sides of the
stairs
KT : 08 The gap between
two sides of the
stairs is 345mm
The gap between two sides of
stairs at least is 1,05
Article
7.17
[1]
Acceptab
le
The width of
the landing
KT : 08 The smallest
width of the
landing is 345m
The width of the landing is
not smaller than the width of
two sides of elevators
Article
7.20
[1]
Acceptab
le
Obstacles in
the elevator
No obstacles in
No obstacles in the escape
elevator
Article
7.20
[1]
4
Safe distance from fire
The Distance
to the nearby
constructions
The distance
from the
independent
building to
the others
>/15m
The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the Fire
walls
5
Accessibility for Firefighting
Distance to the
nearby
constructions
The distance
from the
independent
building to
the others
>/15m
The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the Fire
walls
Article
8.3 [1]
H- Female dormitory
Door
Number of exit KT:01 1 door >/2 doors Article
7.7
[1]
unaccept
able
Doors
Direction of
opening doors for
the room
containing less
than 15 people
KT:01 and
KT: 02
Open inside Open inside is acceptable Article
7.24
[1]
Acceptab
le
The smallest
width of doors
for each room
KT:01; KT:
02 and KT :
08
Bc=0,7 B>/0,7 Article
7.17
[1]
Unaccept
able
Hydraulic height KT: 08 hMIN= 1,9m hMIN>/ 1,9m Article
7.18
[1]
Acceptab
le
Corridor and inside elevator
Length KT:01and
KT: 02
The farthest
distance to the
elevator is 16,6m
The farthest place to elevator (
Offices and rented offices ) is
40 m
Article
Acceptab
le
Width KT:01and
KT: 02
The smallest
width of corridor:
2,02m
>/1,8m Article
4.5
TCVN
3978-
1984
Acceptab
le
Cabinet in the
hall
KT:01; KT:
02 and
No cabinet in the
hall
No wall cabinet in the hall,
except from the technical
cabinets and the box for
Article
7.19
[1]
firefighting
Stair wall KR:09 110mm Bearing and covering
structure are not limited
refractory smaller than 60
minutes
Article
8.4
[TCV
N
6160-
1996]
Acceptab
le
Obstacles in the
elevator
KT:01 ; KT:
02; KT: 08
No Obstacles in
the elevator
No Obstacles in the escape
elevator
Article
7.20
[1]
Acceptab
le
Emergency
ladder
KT:01 and
KT: 02
No obstacles No obstacles Article
8.4
[TCV
Acceptab
le
Number of
Emergency
ladder
KT:01 and
KT: 02
1 Emergency
ladder
Number of emergency out of
the house with the farthest to
Article
7.7
[1]
Acceptab
le
The width of the
landing
KT: 09 The smallest
width of the
landing is 1,43m
The smallest hydraulic width
is 1, 05 m
Article
7.7
[1]
Acceptab
le
The total width
of the landing
KT: 09 ∑btt=
1,43+1,475=2,9m
∑bct= KxN/100= 1,0x500/
100= 1,5m
Article
7.15
[1]
Acceptab
The gap between
two sides of the
stairs
KT: 09 The gap between
two sides of the
stairs is 345mm
The smallest gap between the
<b>two sides of the stairs is </b>
50mm
Article
7.17
[1]
Acceptab
le
The width of the
landing
KT: 09 The smallest
width of the
The width of screening off
stairs is not smaller than the
Article
7.20
<b>landing : </b>
6,355m
width of two sides of the
stairs
[1]
Safe distance from fire
The distance to
the nearby
constructions
The distance
from the
independent
building to
the other
structures>/15
KT: 02; KT:06
and KT :07
The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the
Article
8.3
[1]
Acceptab
le
Firefighting traffic
The distance
to the nearby
constructions
The distance
from the
independent
building to
the other
structures>/15
KT: 02; KT:06
and KT :07
The distance to the second
building with the I, II
refractory step is 6m, III is
8m, IV, V is 10m. to the
firewalls
Article
8.3
[1]
Acceptab
le
III. Firefighting system
3 Checking
Content
Drawing
symbols
design Standard
TCVN 2622-1995
[1]
specifi
ed
standa
rd
provisi
ons
Recomm
endation
3.1 Fire fighting system indoor
1 Choose agent
fire according
to fuel
Explanation water Feature of the solid burning Article
31
table 3
TCVN
5760-1993
Acceptab
le
2 System to
provide water
for fire
fighting
Explanation
PCCC: 02;
PCCC: 03
Pipeline is
designed to
provide water for
fire fighting
within
the firefighting system is
Designed inside for
administrative offices with
over six-level height, public
sites have over 5000m3
Article
10.12
[1]
Acceptab
le
3 Arrangement
of water pipes
Explanation
PCCC:09 to
Placed in the
halls and
Placed at the entrance on the
landing position, in the hall,
for firefighting
system
PCCC: 27 corridors of each
floor.
easily and visibly. [1]
4 Water pipe
height
Explanation
PCCC: 07
The distance
from The Center
of water pipe to
the floor is
1,25m
The distance from The Center
of water pipe to the floor is
1,25m
Article
10.19
[1]
5 Tubs of
firefighting
box
Explanation
Each box has
valve, coil of
wire 20 m and a
tub B 50
Each box has valve which can
be locked, the length of water
pipe based on reality.
Article
10.20
[1]
6 Water pipe
system for
one-sided
wall.
Explanation
PCCC:03
There are 68
water boxes
placed on
one-sided wall in the
building. Water
supply system for
firefighting is
If 12 water boxes are placed
inside the building, the water
supply system must have at
least 2 water pipes to carry
water into the building and is
designed in the form a ring
Article
10.16
[1]
7 Water volume
of each box
Explanation 2,51 l/s Table 14 TCVN
2622-1995
10.14
[1]
8 Water
pressure of
water pipe
Explanation Water pressure of
water pipe is
assured by fire
Water pressure of water pipe
inside the building must
assure fat beams with the
height >/6m
Article
10.15
[1]
9 water stored,
anti-fire water
tank
Explanation
PCCC:07
Underground
water tank is the
volume is 135m3
The water should be stored
must be based on the volume
needed for firefighting for 3
hours. Measured water
volume stored
Wc
Article
10.22
[1]
Article
10.27
[1]
10 Diameter of
water pipes
PCCC:08
To PCCC:09
The main water
pipe
The water pipe should be steel
pipe with diameter is 50m.
4513-88]
11 Number of
plumbers
Explanation
PCCC:04
There are 2
plumbers only
for firefighting
Plumbers for housing
consumer, and firefighting
separately or combinatedly
extra plumbers has equivalent
to the main plumbers
Term
a,
Article
10.24
[1]
12 Fire pumps
-an electric
pump
-a petrol pump
explanation +Capacity:
22,5KW
+current: Q MAX
= 48m3/hour
+ column
pressure: HMAX
= 84,5m
+Capacity:
+current: Q MAX
= 48m3/hour
+ column
pressure: HMAX
= 84,5m
Ensure current and column
pressure when occur fire.
Calculated:
+ H>/ 75,1 m.c.n
+Q >/ 45 m3/hour
acceptabl
e
Number of box needed for each floor.
1 Administrative
house
PCCC:09 and
PCCC:10
1 box High Administrative house is
allowed to set 1 box
Article
10.14
[1]
Acceptab
le
2 Kindergarten PCCC:21and
PCCC:22
1 box Table 14 TCVN 2622-1995 Article
10.14
[1]
Acceptab
le
3 Primary
school
PCCC:17and
PCCC:18
2 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]
Acceptab
le
4 Secondary
school
PCCC:19 and
PCCC:20
1st<sub>:05 boxes</sub>
2nd<sub>: 03 boxes</sub>
Table 14 TCVN 2622-1995 Article
10.14
[1]
Acceptab
le
5 Library PCCC:24 and
PCCC:25
2 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]
Acceptab
le
6 Teacher
PCCC:15and
PCCC:16
2 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]
7 Male
dormitory
PCCC:11 and
PCCC:12
02 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]
Acceptab
le
8 Female
dormitory
PCCC:13 and
PCCC:14
01 boxes Table 14 TCVN 2622-1995 Article
10.14
[1]
Acceptab
le
<b>Fire fighting system outdoor</b>
<b>Fire fighting </b>
<b>system </b>
<b>outdoor</b>
PCCC:02and
PCCC:03
fire extinguisher High building must be
designed and set firefighting
inside and outside.
Article
12.5
[1]
Acceptab
le
fire extinguisher
fire
extinguisher
PCCC:08and
PCCC:28
45 cylinders MT3
and 90 containers
MFZ4 is 135
Need to set fire extinguisher
system
QCXD
VN
1997
TCVN
5760-
1993
Acceptab
le
Position of
fire
extinguisher
PCCC:09 to
PCCC: 27
On the corridor,
clear sight
On the corridor, clear sight Article
5.2:
TCVN
7435/1
- 2004
Acceptab
le
Number of
fire
Extinguisher
for each floor.
PCCC:09 to
PCCC: 27
>/2 boxes Each floor must set at least 2
boxes
Article
7.2.2:
TCVN
7435/1
- 2004