savic-net FX
Integration System Construction Guide

日付入力

Copyright  2008 Yamatake Corporation All Rights Reserved.


Contents
1.

Current available communication protocols with FX2

2.

Communication protocol checklist for each
manufacture

3.

Selection guide of communication protocols

4.

Special remarks of BACnet system

5.

Case study of BACnet



6.

Special remarks of Modbus system

7.

Case study of Modbus
Copyright  2008 Yamatake Corporation All Rights Reserved.

2


1. Current available communication
protocols with FX2
OA network

FX IBMS

SM
S

Client PC

Intranet
Internet

Alarm
Management


Maintenance
Management

Help Desk

Facility
Booking

Billing

BACnet IP
FX
BEMS

FX BMS

EDS

SMS

Building Wide IT Network Infrastructure
(Ethernet, 100Mbps)

FX SEC
DSS

SDS
IDS

BMS Network (Ethernet, 100Mbps)


ACC
SCS
Infilex
IP type
(DDC)
Infilex
(DDC)

BACnet IP
Modbus TCP
Modbus RTU

Modbus
Device
CCTV
System

Fire Alarm
System

Lighting Public Address Car Park
System
System
System

Lift/Escalator
System

Sub systems


LonTalk

Modbus TCP
Modbus RTU
Copyright  2008 Yamatake Corporation All Rights Reserved.

3


2. Communication protocol checklist
for each manufacture
Equipments

Manufactures

BACnet IP

Communication Protocols
BACnet
Modbus
Modbus
MS/TP
TCP
RTU

LON

OPC


CNA'
Quantum
Carrier
Chiller
TRANE
YORK
VRV
DAIKIN
Lighting
Panasonic
産電
Power
LG産電
Schneider
Monitoring
CIRCUTOR
GE
Janitza
Power Meter
M-System
Mitsubishi
SATEC
Schneider
GE
PLC
Mitsubishi
Edwards
GST(China)
Fire Alarm
NOHMI

Notifier
Simplex
Public Address TOA
Car Park
Lift / Escalator
FA System
TOP Server
IBMS

Installed

Possible, but not installed

Need to discuss

Impossible
Copyright  2008 Yamatake Corporation All Rights Reserved.

4


3. Selection guide of communication
protocols
A)

Communication protocol that Yamatake has already
installed to an actual project is our first priority.

B)


Our priorities in order are as follows when you’re going
to communicate with first manufactures or products for
Yamatake.

C)

1.

Modbus

2.

BACnet IP

3.

LON

Let us know if OPC Server / OPC Client is required for
your projects. BSC is still considering to use 3rd party
software for OPC.
Copyright  2008 Yamatake Corporation All Rights Reserved.

5


4. Special remarks of BACnet system
FX2 can only use BACnet IP. Promote Modbus or LON instead of
BACnet if other BACnet protocols like BACnet Ethernet, BACnet MS/TP,
etc. are required.

Get a Protocol Implementation Conformance Statement (PICS) of the
product on the other end of the communication as soon as possible and
confirm their BACnet communication specifications like the protocol
revision, network type and object types, etc.
Get the object list on the other end of the communication for our system
engineering.
For the Yamatake HOST system, note as below.
a.

Estimate one or more SCS for the exclusive use of BACnet processing when
FX2 has trending function or time program for other manufacturer’s products.

b.

Estimate SCOL Management function (BSY45310Z0502) when FX2 has
trending function for other manufacturer’s objects. FX2 needs SCOL program
(analog copy output) to convert SCS external data of manufacturer’s objects
to dummy points.
Copyright  2008 Yamatake Corporation All Rights Reserved.

6


5. Case study of BACnet (NOHMI)
・Objects reading / writing
・Alarm event sending
・Device monitoring

Client PC


< System name >
Integlex fire alarm system
B-OWS
(MIS)

< Protocol revision >
ANSI/ASHRAE 135-2004

< Information type and objects>
Fire representative information
(BV)

BACnet IP

Fir alarm status (BI)
B-BC
(SCS)

B-BC

Exhaust-gas protection
equipments running status
(MI)
Exhaust-gas protection control
status (MO)
Device information (Device)
Notification-Class

< Function >
Fire Alarm System


Fire alarm monitoring
Copyright  2008 Yamatake Corporation All Rights Reserved.

7


5. Case study of BACnet (TRANE)
・Objects reading / writing
・Alarm scan (every 2
min.)
・Device monitoring

Client PC

< System name >
Tracer Summit

B-OWS
(MIS)

< Protocol revision >
ANSI/ASHRAE 135-1995

< Objects >
AI/AO

BACnet IP

BI/BO

B-BC
(SCS)

B-AAC
(BCU)

Device

< Function >
On / Off
Status monitoring
Failure monitoring

Chiller Plant
Control System

Analog measurement
Analog setting
Copyright  2008 Yamatake Corporation All Rights Reserved.

8


5. Case study of BACnet (DAIKIN)
Client PC

B-OWS
(MIS)

・Objects reading

/ writing
・Alarm scan
(every 2 min.)
・Device
monitoring

BACnet IP

B-ASC
(BACnet
Gateway)
B-BC

D-BACS

< Protocol revision >
ANSI/ASHRAE 135-2004

< Objects >
Accumulator
AI/AO/AV
BI/BO/BV
Device
MI/MO
Notification-Class

< Function >

(Exclusive SCS
for BACnet)


・External data
collection
(for trending)
・Time program

< System name >

Status / alarm monitoring
Time program
Event program
Analog measurement /
setting
Trending
VRV System
Copyright  2008 Yamatake Corporation All Rights Reserved.

9


6. Special remarks of Modbus system
FX2 can only use Modbus RTU and Modbus TCP. Modbus ASCII
and Modbus Plus cannot be supported with FX2.
Get Modbus communication specifications of the product on the
other end of the communication as soon as possible and confirm
the possibility of communication with FX2.
Create a Modbus Device chart for the Modbus engineering at first.
FX2 logically uses a Modbus device as a NC-bus controller. So
one Modbus devices has 99 points in maximum. Add one more
Modbus device in case of using over 100 points per Modbus

device.
The latest recommended Modbus Media Converter is MOXA
MB3170.
/>Copyright  2008 Yamatake Corporation All Rights Reserved.

10


7. Case study of Modbus (Power
Meter)
Client PC

< Function >
MIS

Metering
Current
Modbus TCP

BACnet IP

Voltage
Power

SCS with
Modbus

Modbus
Gateway


Power Factor
Frequency
etc.

Modbus RTU

Power Meter
Copyright  2008 Yamatake Corporation All Rights Reserved.

11


7. Case study of Modbus (Panasonic)
Client PC

< System name >

MIS

FULL-2WAY system
Modbus TCP

< Function >
Individual Load
Control

BACnet IP

SCS with
Modbus


Modbus
Gateway

OPIU
(Modbus_IFU)

One OPIU can manage
256 circuits. But
maximum 99 points
per controller for
SCS makes a priority.

Group Control
Pattern Control

Modbus RTU

Dimmer Load Control
System Status Monitor
Lighting Control System
Copyright  2008 Yamatake Corporation All Rights Reserved.