TECHNICAL NOTE TN 15/2001
Rules of Thumb (UK 3rd edition)
Guidelines for assessing building services
Edited by Martin Boushear
Supported by
Contents
Space and weight allowances
TABLE
TABLE
TABLE
TABLE
TABLE
TABLE
TABLE
TABLE
1: Floor space allowance for services
2: Space allowances for plant rooms
3: Miscellaneous services
4: Space allowances for on-floor services
5: Space allowances for service ducts and shafts
6: Space allowances for catering facilities
7: Floor space allowance per occupant
8: Plant weight allowances
Equipment and solar loads
TABLE
TABLE
TABLE
TABLE
14
1: Cooling loads
2: Cooling plant
3: Solar gains
4: Heat loads
Comfort factors
TABLE
TABLE
TABLE
TABLE
TABLE
TABLE
6
16
1: External conditions
2: Ventilation and air conditioning
3: Information technology
4: Room air movement
5: Noise levels
6: Comfort data sheet
System features
20
TABLE 1: Sizing and operating characteristics of plant
TABLE 2: Water treatment
Energy and carbon issues
24
TABLE 1: Energy conversions
TABLE 2: Energy benchmarks (offices)
TABLE 3: Lighting benchmarks
Electrical systems
26
TABLE 1: Electrical supplies and loads
Cost data
27
TABLE 1: Capital and maintenance costs
TABLE 2: Services costs as a percentage of total costs
TABLE 3: System capital and maintenance costs
References
Rules of Thumb BSRIA 2001
32
3
Acknowledgements
The story behind the guide
This publication is the third update of the Technical Note TN 17/95: Rules
of Thumb last issued in 1995. The rules have been collected from various
contemporary sources in the building services industry and can reasonably
be held to reflect current design practices. The sources include major
design offices, individual engineers and public domain information
published by BSRIA and others.
The industry review team for this project comprised: John Louis Auguste
(Bovis Lend-Lease), Dennis Bastow (NHS Estates), Brian Charlesworth
(Troup Bywaters & Anders), Laurie Clark (Cundall Johnston & Partners),
Michelle Field (Buro Happold), Manus Freeman (SVM Partnership),
Nigel Hawkes (Fulcrum Consulting), Glen Irwin (Roberts & Partners),
Bob Keenan and Dr Ian Selby (Sheppard Robson, on behalf of the
British Council for Offices), Nick Mead (ACDP), Richard Tudor (WSP
Group), and Gay Lawrence Race and John Sands (BSRIA). We would
also like to thank AMEC Capital Projects, BAA plc, N G Bailey, Bryan
Franklin, Building Design Partnership, Foggo Associates, Foremans Ltd,
Hoare Lea & Partners, Max Fordham & Partners, Stanhope, and Whitby
Bird & Partners for their help.
Finally, BSRIA would like to make special acknowedgement to the
consulting engineers Foremans Ltd, whose financial support has enabled
BSRIA to extend the print run. BSRIA also acknowledges the editing
help of Nigel Pavey, author of the second edition of Rules of Thumb and
now chief engineer with Foremans Ltd.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval
system, or transmitted in any form or by any means electronic or mechanical including
photocopying, recording or otherwise without prior written permission of the publisher.
BSRIA TN 15/2001 August 2001
4
Rules of Thumb BSRIA 2001
ISBN 086022 587 9
Printed by The Chameleon Press Ltd
How to use this guide
What this guide will do
Rules of Thumb has been written to help engineers in the initial stages of
designing a building and its services. By gathering many of the most
common rules of thumb into one document, BSRIA has provided a
powerful source of inital design data that every engineer should find
indispensable.
Thumb rules (or heuristics as they are more properly known) are
extremely useful values for use at various stages of design, such as project
inception and outline briefing, feasibility planning, the assessment of
global loads and space requirements. They are also useful for getting a
initial grasp of costs. Rules of thumb come in handy for carrying out
"what if" calculations, and for use by senior engineers when checking the
work of junior engineers.
The data have been derived from a wide variety of authoratative sources,
all of which are referenced. All the figures quoted have also been
assessed for usefulness and relevance by a panel of experienced,
practising services engineers.
What this guide will not do
While every effort has been made to establish current practice, the
guide's authors are keen to point out that the rules of thumb are merely
aids to the design process. They must not be used in place of detailed
design data. The responsibility for the safe and appropriate use of this
data therefore rests with the engineer.
Rules of Thumb has been designed to be your own personal reference
document. Use it, add your own data to it, and guard it jealously. And
please let us know how it works and where it can be improved.
Roderic Bunn
Publisher
Rules of Thumb BSRIA 2001
5
6
Space and weight allowances
When to use: During the early stages of design prior to plant selection or system analysis
Where to use: Plant room sizes, riser cupboard locations and plant capacities
Watch out for: Poor information that fails to allow for installation, commissioning or maintenance
TABLE 1: Floor space allowance for services (as a percentage of floor area)
Rules of Thumb BSRIA 2001
Design area
Application
All services
Air conditioning (excluding
boilers & refrigeration)
Other information
Rule of thumb
Ref
Simple factory
Offices and commercial
Hi-tech building
4%
6 – 10%
15 – 30%
26
26
26
Fan coil system
VAV system
1⅐⅐ 5 – 2⅐⅐ 5%
3 – 4⅐⅐ 5%
26
26
0⅐⅐3 – 1⅐⅐5%
26
Electrical services (excluding
sub-stations and standby
generation sets)
0⅐⅐5 – 1⅐⅐ 5%
26
Lift motor rooms
0⅐⅐2 – 0⅐⅐ 5%
26
Central plant
1 – 2%
26
Toilet extract
Supply and extract system
All air low velocity system
0⅐⅐3 – 1%
3 – 5%
4 – 6%
26
26
26
Cooling towers and air-cooled
condensers
Refrigeration (excluding
cooling towers)
Ventilation
For references see page 32
Your notes and comments
TABLE 2: Space allowances for plant rooms (floor area)
Design area
Application
Air cooled condenser and
controls
Air handling units
Other information
Rule of thumb
Ref
space for
installation and
maintenance
25 + kW/200 m2
29
With extract
/recirculation
8 m2 per m3/s
29
Without extract
/recirculation
5 m2 per m3/s
29
Rules of Thumb BSRIA 2001
Boilers
(percentage floor area)
Boiler plant
& calorifiers
Oil tank room
0⅐⅐ 8 – 1⅐⅐ 8%
1 – 2%
26
26
Boilers
(floor area and height)
Boilers, pumps,
piping and space for
installation and
maintenance
Output: 100 kW
Output: 200 kW
Output: 1000 kW
Output: 4000 kW
15 m2 x 3 m
25 m2 x 3 m
80 m2 x 4 m
140 m2 x 5 m
29
29
29
29
Calorifiers
(floor area and height)
Calorifiers, pumps,
pipework, controls
and space for
installation and
maintenance
Vertical
Vertical
Vertical
Vertical
(1 m3)
(5 m3)
(10 m3)
(15 m3)
Horizontal
Horizontal
Horizontal
Horizontal
(1 m3)
(5 m3)
(10 m3)
(15 m3)
10
20
25
60
m2
m2
m2
m2
x
x
x
x
3
4
5
3
m
m
m
m
29
29
29
29
25
30
45
60
m2
m2
m2
m2
x
x
x
x
3
3
3
3
m
m
m
m
29
29
29
29
Your notes and comments
Table 2 continued Ł
7
For references see page 32
8
Space and weight allowances
TABLE 2: Space allowances for plant rooms (floor area)
Rules of Thumb BSRIA 2001
Design area
Application
Other information
Rule of thumb
Ref
Chillers (water cooled)
Floor area times height
With pumps,
pressurisation,
pipework and
control panels
Output: 1000 kW
Output: 2000 kW
Output: 3000 kW
Output: 4000 kW
50 m2 x 3 m
63 m2 x 3 m
83 m2 x 3⅐⅐ 5 m
108 m2 x 4 m
29
29
29
29
Chillers (air cooled)
Located outside.
Includes space for
installation and
maintenance
Output: 200 kW
Output: 400 kW
Output: 600 kW
Output: 800 kW
Output: 1000 kW
Output: 1200 kW
39 m2
53 m2
75 m2
84 m2
98 m2
116 m2
29
29
29
29
29
29
Cold water storage
Single cold water tank
Includes space for
installation and
maintenance but add
space for
pressurisation plant
or circulation pumps
FA: Floor area
V: gross storage m3
1 m high
2 m high
3 m high
FA: 10 + V/0⅐⅐75 m2
FA: 10 + V/1⅐⅐ 6 m2
FA: 10 + V/2⅐⅐ 4 m2
29
29
29
Minimum for
hot and cold
outlets
Offices
10-20 litres/person
4
Cold water storage
Hotels, children’s home,
residential nursery,
convalescent home
135 litres/bed space
Your notes and comments
4
Table 2 continued Ł
For references see page 32
Design area
Application
Other information
Rule of thumb
Ref
Cold water storage
(domestic) continued
Minimum for
hot and cold
outlets
Restaurant
Day school
Hostel
7 litres/meal
15-20 litres/pupil
90 litres/bed space
20
20
20
FA: Floor area
(kW: heat rejection)
FA: 50 + kW/66 m2
29
HV switchgear
HV + LV switchgear
47 m2
14 m2
27 m2
29
29
29
Standby sets and
accessories
FA: Floor area
FA:15 + kVA/30 m2
29
Single module system
(add space for
batteries)
FA: Floor area
FA: (2 + kW/200) x 2 m2
29
Other information
Rule of thumb
Ref
1200 – 1800 mm
18
Tank contents + 10%
19
Cooling towers
Sub-station
Rules of Thumb BSRIA 2001
Standby generation
Uninterruptible power supply
2000 kVA
transformers
Switchgear
Your notes and comments
TABLE 3: Miscellaneous services
Design area
Application
Control panels & distribution
boards
Front panel controls, Fixing height range
wall-mounted or floor (above finished floor
standing
or operating platform
level)
LTHW boiler plant
component criteria for
leakage containment
Oil storage tanks,
distillate & residual
fuel oils
9
For references see page 32
If tank fails, walls and
doors treated to
contain spillage
Your notes and comments
10
Space and weight allowances
TABLE 4: Space allowances for services (depth of clear space in ceiling/floor void)
Design area
Application
Air conditioning
Rules of Thumb BSRIA 2001
Rule of thumb
Ref
VAV
VRV
Recessed chilled beams
Surface chilled beams
Chilled ceilings
Fan coils
Ducted air system
350 – 750 mm
450 mm
350 – 450 mm
250 mm
250 mm
450 mm
450 mm
16
16
16
16
16
27
27
Drainage
Soil and waste
100 mm dia.
150 mm dia.
10 – 25 mm per m run
7 – 16 mm per m run
27
27
Lighting
Fluorescent
Downlighter
100 – 150 mm ( םaccess) 16
150 – 300 mm
16
Power and communications
Multi-core cables and
lighting cables
100 – 200 mm
16
Power and data
(heavy line)
200 – 250 mm
16
Computer rooms
300 mm
16
For references see page 32
Other information
Your notes and comments
TABLE 5: Space allowances for service ducts and shafts
Design area
Application
Air ducting
Lift shafts
Mechanical service
riser
Simple pipework
riser
Rules of Thumb BSRIA 2001
Three-sided riser
11
For references see page 32
Rule of thumb
Ref
Typical ducting size
0⅐⅐2 m2/m3/s
30
3+A(N-4)/250 m2
30
Between 4 – 18 floors Internal shaft area
in office-type buildings A: floor area/
storey (250 m2 min),
N: Floors
Pipework
Service ducts
Other information
Vertical service duct
Depth needed to open
access door/pane when
width of door varies
with size/type of pipe
or depth of service/duct 690 mm
17
Pipe: 20 mm dia.
Pipe: 25 mm dia.
Pipe: 32 mm dia.
100 mm x 100 mm
120 mm x 120 mm
130 mm x 130 mm
30
30
30
Minimum depth
from services to (open)
access door/panel
690 mm
17
Floor space served by
vertical service (radius)
15 – 23 m
30
Aspect ratio of vertical
service duct
2:1 – 4:1
30
Total duct area as %
of gross floor area
2%
30
Your notes and comments
12
Space and weight allowances
TABLE 6: Space allowances for catering facilities
Rules of Thumb BSRIA 2001
Design area
Application
Other information
Rule of thumb
Ref
Kitchen and dining facilities
Kitchens including
preparation and
storage
Min. requirements:
Up to 100 meals
Up to 500 meals
0⅐⅐4 m2/meal
0⅐⅐ 25 m2/meal
31
31
For single sittings
Ratio of kitchen
space to dining space
0⅐⅐33:1 to 0⅐⅐ 5:1
31
Ratio of kitchen space
to dining space
1:1
31
For multiple sittings
Your notes and comments
TABLE 7: Floor space allowance per occupant (net internal area)
Design area
Rule of thumb
Ref
General offices
12 – 17 m2/person
4
Trading desks, call
centre, work stations
4 – 6 m2/person
4
15 m2 (or more)
per person
4
Enclosed offices
For references see page 32
Application
Other information
Your notes and comments
TABLE 8: Plant weight allowances
Design area
Application
Single boiler
Rules of Thumb BSRIA 2001
Rule of thumb
Ref
500 kW
1500 kW
2500 kW
1500 kg
4250 kg
6500 kg
39
39
39
Single storage steel calorifier
4 m3
8 m3
12 m3
1250 kg
2500 kg
3300 kg
39
39
39
Single non-storage mild-steel
heating calorifier
500 kW
1000 kW
1500 kW
2000 kW
150
225
275
325
kg
kg
kg
kg
39
39
39
39
1500 kW
3000 kW
4500 kW
10 000 kg
20 000 kg
30 000 kg
39
39
39
Single air-cooled liquid chiller
500 kW
1000 kW
1500 kW
6 000 kg
11 000 kg
14 000 kg
39
39
39
Single generator
500 kVa
1000 kVa
1500 kVa
5000 kg
8000 kg
11 000 kg
39
39
39
100 kVa
300 kVa
500 kVa
1250 kg
2750 kg
4250 kg
39
39
39
Single water-cooled
liquid chiller
Single UPS system
13
For references see page 32
Other information
Your notes and comments
14
When to use:
How to use:
Watch out for:
Equipment and solar loads
For estimates of thermal loads used to assess plant and terminal equipment sizes
To determine total solar and internal gains, multiply the loads by total floor area
Solar gains depend on glazing and shading, and contribution of thermal mass
TABLE 1: Cooling loads
Design area
Application
Other information
Rules Of Thumb BSRIA 2001
Rule of thumb
Ref
Banks
160 W/m2
34
Computer suites
400 W/m2 approx
34
Hotels
150 – 300 W/m2
34
Offices (general)
125 W/m2
34
75 W/m2
34
120 W/m2
180 W/m2
34
34
Restaurants
220 W/m2
34
Retail buildings
140 W/m2
34
Other information
Rule of thumb
Ref
Central cooling plant
Load/m2 of floor area
Load/m3 of floor vol.
125 W/m2
40 W/m3
36
36
Distributed cooling plant
Load/m2 of floor area
Load/m3 of floor vol.
140 W/m2
45 W/m3
36
36
Central plant
Distributed plant
0⅐⅐5 kW/kW
0⅐⅐ 78 kW/kW
36
36
Interior zones more
than 7 m from windows
Perimeter zones
up to 6 m
60% glazing
65% glazing
Your notes and comments
TABLE 2: Cooling plant
Design area
Electrical power for
refrigeration plant
For references see page 32
Application
kW/kW cooling
capacity
Your notes and comments
TABLE 3: Solar gains (over floor area)
Rules Of Thumb BSRIA 2001
Design area
Application
Other information
Rule of thumb
Ref
Windows with
internal blinds
(June-Sept)
(June-Sept)
South facing
East-West facing
250 W/m2 of glass
150 W/m2 of glass
34
34
Clear double-glazed with
internal blinds
Out-of-town building
All data for 6 m deep,
1500 mm wide module.
U-value 3⅐3 W/m2K.
2650 W instant
2490 W lag (mass)
39
39
As above with flat slab
Plus brise soleil
1860 W instant
1710 W lag (mass)
39
39
As above with coffered slab
Plus brise soleil
1860 W instant
1680 W lag (mass)
39
39
Other information
Rule of thumb
Ref
Floor area
90 W/m2 (30 W/m3)
34
Educational buildings
100 W/m2
34
Industrial buildings
80 W/m2
34
Offices
70 W/m2
34
Residential buildings
60 W/m2
34
Infiltration: air heating load
7⅐⅐ 5 W/m3
34
Retail buildings
110 W/m2
34
10 W/m2
12 W/m2
15 – 25 W/m2
16
16
16
Your notes and comments
TABLE 4: Heat loads
Design area
Application
General buildings
Other heat gains
Offices
General offices
15
For references see page 32
Metabolic
Lighting
Office equipment
Your notes and comments
16
When to use:
Where to use:
Watch out for:
Comfort factors
During the early stages of design
When setting inernal environmental conditons based on known or assumed loads
Specific client requirements, and contexts that allow greater latitude in design settings
TABLE 1: External conditions
Design area
Application
Winter design temperatures
for heating
Without surplus
boiler capacity
With 20% surplus
boiler capacity
Other information
Single-storey building
Other buildings
Rules of Thumb BSRIA 2001
Rate of lowering
outdoor design temp.
with altitude above
sea level
Rule of thumb
Ref
-4ЊЊC
37
-3ЊЊ C
-1ЊЊC
37
37
-0⅐⅐6ЊЊ C/100 m
37
Summer design temperature
Dry bulb temp.
28ЊЊC
37
for air conditioning
Wet bulb temp.
19ЊЊC
37
Your notes and comments
TABLE 2: Ventilation and air conditioning
Design area
Application
Other information
Rule of thumb
Ref
Ventilation: recommended
maximum temperature
Offices
95% operation/year
25ЊЊ C
4
Air conditioning: recommended
maximum temperature
Offices
95% operation/year
24ЊЊC (or lower)
4
IT rooms by classification
Type A IT rooms
Specifically designed
and built for IT equipment
(ideally, isolated from
office areas)
Dedicated IT room
required
For references see page 32
38
Your notes and comments
TABLE 3: Information technology
Design area
Application
Other information
IT rooms by classification
(continued)
Type B IT rooms
Designed for intensive
use of IT equipment at
workstations (where
air-conditioning must
be used)
Type C IT rooms
Rules of Thumb BSRIA 2001
Rule of thumb
Ref
Air-conditioned office,
room or workspace
38
Non air-conditioned
office, room or
workspace
38
Other information
Rule of thumb
Ref
In Winter
In Summer
At 21ЊC
At 22ЊC
At 23ЊC
At 24ЊC
On back of neck
0⅐⅐15 m/s
0⅐⅐ 25 m/s
0⅐⅐ 15 m/s
0⅐⅐ 2 m/s
0⅐⅐ 25 m/s
0⅐⅐ 3 m/s
0⅐⅐ 2 m/s
37
37
37
37
37
37
37
Papers will lift at
velocities in excess of
0⅐⅐8 m/s
37
0⅐⅐2 – 0⅐⅐ 3 m/s
2
Your notes and comments
Room where IT
equipment is used at
workstations (may use
natural or mechanical
ventilation)
TABLE 4: Room air movement
Design area
Maximum recommended
mean air velocities
Application
Television and
broadcasting studios
17
For references see page 32
Your notes and comments
18
Comfort factors
TABLE 5: Noise levels
Design area
Application
Other information
Rule of thumb
Ref
Recommended maximum
background noise levels
Very quiet rooms
Concert halls, sound
studios
Bedrooms, theatres,
churches
Small offices, libraries,
living rooms
General offices,
classrooms, small shops
Reception areas,
restaurants
Kitchens, computer
rooms, large shops
Factories
NR 20
37
NR 25
37
NR 30
37
NR 35
37
NR 40
37
NR 45
NR 50 or above
37
37
Intelligibility of telephone
conversation at background
noise levels
Satisfactory
Slightly difficult
Difficult
Unsatisfactory
Up to NR 50
Up to NR 60
Up to NR 75
Over NR 75
37
37
37
37
External noise level criteria for
new noise (above background noise)
If more than 10 dBA
If less than 5 dBA
Complaints expected
Marginal
37
37
Limiting distances for speech
intelligibility (background noise
level)
Up to NR 40
Up to NR 45
Up to NR 50
Up to NR 55
Over NR 70
7m
4m
2⅐⅐ 2 m
1⅐⅐ 2 m
Too noisy
37
37
37
37
37
Quiet rooms
Private rooms
Public rooms
Rules of Thumb BSRIA 2001
General areas
Work areas
Industrial areas
For references see page 32
Your notes and comments
TABLE 6: Comfort data sheet
Building Type
Internal design temperature
Summer
Winter
Humidity
(% RH)
Infiltration
(ac/h)
Ventilation
fresh air
Ventilation
air change
Lighting level
(Lux)
Noise level
(NR)
Cinemas (sedentary role)
21-23ЊC
19-21ЊC
50ע10% RH
0⅐5 ac/h
8 l/s/person
6-10 ac/h
300 lux
NR25-NR30
Computer rooms (general)
21-23ЊC
19-21ЊC
50ע5% RH
1 ac/h
8 l/s/person
4-15 ac/h
300 lux
NR35-NR45
Education (teaching spaces)
21-23ЊC
19-21ЊC
50ע5% RH
2 ac/h
8 l/s/person
6-10 ac/h
300 lux
NR25-NR35
Exhibition hall/conference facilities
21-23ЊC
19-21ЊC
50-55% RH
0⅐25-0⅐5 ac/h
8 l/s/person
1 ac/h
300 lux
NR40
Factory/warehouse
21-23ЊC
11-21ЊC
50ע10% RH
0⅐25-2⅐5 ac/h
8 l/s/person
6 ac/h
750-1000 lux
NR45-NR65
Fitness/health clubs (equipment rooms)
>18ЊC
12-18ЊC
40-70% RH
0⅐75 ac/h
8 l/s/person
4 ac/h
300 lux
NR30-NR40
Hospitals (ward and patient areas)
23-25ЊC
22-24ЊC
50-60% RH
2 ac/h
8 l/s/person
3 ac/h
50-100 lux
NR30-NR35
Hotels (bedrooms)
21-23ЊC
19-21ЊC
50ע10% RH
1 ac/h
8 l/s/person
6-10 ac/h
50-100 lux
NR20-NR30
Rules of Thumb BSRIA 2001
Libraries (reading rooms)
24-25ЊC
22-23ЊC
50ע5% RH
0⅐25-0⅐75 ac/h
8 l/s/person
3-4 ac/h
300 lux
NR30-NR35
Museums and galleries (display, storage)
21-23ЊC
19-21ЊC
50-55% RH
1 ac/h
8 l/s/person
3-4 ac/h
200 lux
NR30-NR35
Offices (general, BCO data)
24ЊC
22ЊC
35-40% RH
0⅐25-0⅐5 ac/h
8-12 l/s/person
4-6 ac/h
300-500 lux
NR25-NR40
Retail (shops/stores)
21-23ЊC
19-21ЊC
45ע5% RH
0⅐5-1 ac/h
8 l/s/person
3-8 ac/h
500-750 lux
NR35-NR45
300 lux
NR 40-NR50
19
For references see page 32
Swimming pools (pool halls)
Your notes and comments
23-26ЊC
23-26ЊC
40-70% RH
0⅐5 ac/h
2
0-15 l/s/m (of wetted area)
20
When to use:
Where to use:
Watch out for:
System features
During outline design before the architect has finalised space planning
For determining the spatial and operational characteristics of main plant
The rules for boiler and cooling plant are based on unit floor area or unit volume
TABLE 1: Sizing and operating characteristics of plant
Design area
Air handling units
Air face velocity
Application
Other information
Rules of Thumb BSRIA 2001
Coil water velocity
36
16
Heating mode
Cooling mode
30ЊC (max)
13ЊC (min)
16
16
Air discharge
0⅐⅐6 – 2 m/s
36
10 – 40 kPa
0⅐⅐ 33 – 1⅐⅐ 72 bar
16
36
8m
Not to exceed
50 mm within 1m
of diffuser outlet
36
Maximum height
66% of ceiling height
36
Allowance for grille
Allow 0⅐⅐3 m
width
36
120 W/m2 floor area
40 W/m3 volume
36
36
Water pressure drop
Steam pressure drop
Air distribution
From source
Ceiling diffusers
Non-zoning partitions
Sill diffusers
Boiler plant capacity
Power per unit area
Ref
2⅐⅐5 – 4 m/s
1⅐⅐ 0 – 2⅐⅐ 5 m/s
Heating coil
Cooling coil
Air supply
temperatures
Rule of thumb
Limit of throw
Surface projections
Your notes and comments
36
Table 1 continued Ł
For references see page 32
Design area
Application
Other information
Rule of thumb
Ref
Boiler plant efficiency
Boiler efficiency
Efficiency losses
Typical efficiency
Blowdown (steam)
Casing
Flue
75%
2%
3%
15 – 20 %
36
36
36
36
Condensing boilers
Underfloor or warm
water system
90%
22
Standard size radiators,
variable temp circuit
(weather
compensation)
87%
22
Standard fixedtemperature emitters
(83/72ЊC flow/return)
85%
22
Modern high efficiency
boilers
80 – 82%
22
Good modern boiler
design closely matched
to demand
75%
22
Typical good boiler
70%
22
1 kW/person
36
Volume per kW
40 litres/kW
36
Low velocity systems
High velocity systems
3 – 5 m/s
7⅐⅐ 5 – 15 m/s
36
36
Boiler plant
Typical seasonal
efficiencies
Rules of Thumb BSRIA 2001
Non-condensing
boilers
Chiller plant capacity
Fuel storage
Ductwork
Typical duct velocities
Class D oil
Your notes and comments
Table 1 continued Ł
21
For references see page 32
22
System features
Design area
Application
Other information Rule of thumb
Ductwork
Inlet louvres
(through free area)
Maximum pressure drop
rates (per m run)
Ref
Rules of Thumb BSRIA 2001
2⅐⅐5 m/s
36
Low velocity systems
High velocity systems
1 Pa/m
8 Pa/m
36
36
Typical system resistances
(including air handling plant)
Low velocity supply
Low velocity extract
High velocity supply
900 Pa
400 Pa
1⅐⅐ 5 – 2 kPa
36
36
36
Air leakage system loss (%)
Low pressure systems
Med. pressure systems
High pressure systems
6%
3%
2%
15
15
15
Fans
Electrical input (kW)
1⅐⅐6 x total fan pressure
(kPa) x volume flow
rate (m3/s)
36
1ЊC per kPa
36
Offices
Restaurants
Retail stores, halls, theatres
1⅐⅐4 litres/s per m3
3⅐⅐ 5 litres/s per m3
2⅐⅐ 1 litres/s per m3
23
23
23
Total system volume
(system size, in litres)
Domestic systems
Commercial systems
6 x boiler size (kW)+10% 3
10 x boiler size (kW)+10% 3
Capacity per unit area of
radiator surface
Conventional system
1 litre/m2
36
Capacity per unit of power
produced (boilers, radiators)
Boilers
Aluminium, cast radiator
1⅐⅐5 litres/kW
3 litres/kW
36
36
Temperature rise of air
Fan capacity of ventilated space
Class A
Class B
Class C
Total fan pressure
Your notes and comments
Heating systems
Approx. value
Approx. value
Table 1 continued Ł
For references see page 32
Design area
Pipework
Capacity per unit length of
of steel pipe
Application
Rule of thumb
Ref
E xtruded aluminium
Steel panel radiators
1⅐⅐2 litres/kW
5 litres/kW
36
36
15 mm diameter pipe
20 mm diameter pipe
25 mm diameter pipe
32 mm diameter pipe
40 mm diameter pipe
0⅐⅐25 litres/m
0⅐⅐ 4 litres/m
0⅐⅐ 6 litres/m
1⅐⅐ 2 litres/m
1⅐⅐ 5 litres/m
36
36
36
36
36
15 – 50 mm pipe dia.
Over 50 mm pipe dia.
0⅐⅐75 – 1⅐⅐ 5 m/s
1⅐⅐ 25 – 3 m/s
36
36
Initial pressure
per 100 m pipe run
6%
36
Over 50 mm pipe dia.
100 – 300 Pa/m
16
Corrosive water
1 m/s
1⅐⅐ 2 m/s
2 m/s max
36
36
36
Superheated steam
Saturated steam
Exhaust
40 – 60 m/s
30 – 40 m/s
20 – 30 m/s
36
36
36
4⅐⅐9 litres/m2
36
Pressure (in kPa),
length (m)
0⅐⅐36 x circuit length
36
Copper pipework
With steel pipework
Add 10% to water
36
Frost protection
Glycol concentration
30% of system vol.
16
Water velocity
Conventional systems
Rules of Thumb BSRIA 2001
Steam pressure drop
Water pressure
Conventional systems
Water velocity (system)
Small bore
Microbore
Steam velocity
Capacity per unit of finned area
Finned tube coils
Pumps
Head pressure (pump head)
Water treatment
Additives required
23
For references see page 32
Other information
Your notes and comments
24
When to use:
Where to use:
Watch out for:
Energy and carbon issues
When determining total building energy consumption
From briefing onwards through to design and operation (See also CIBSE TM22)
Change to the carbon conversion ratios which are continually being updated
TABLE 1: Energy conversions
Design area
Carbon dioxide emission
(Kg CO2/kWh delivery) by fuel
Application
Natural Gas
Oil
Electricity
Coal
Other information
Average
CO2 to Carbon
Rule of thumb
Ref
0⅐⅐19
0⅐⅐ 25
0⅐⅐ 46
0⅐⅐ 30
1
1
1
1
kg
kg
kg
kg
CO2/kWh
CO2/kWh
CO2/kWh
CO2/kWh
Divide by 3⅐⅐ 67
1
Your notes and comments
Rules of Thumb BSRIA 2001
TABLE 2: Energy benchmarks (offices)
Design area
Application
Other information
Rule of thumb
Ref
Naturally ventilated (cellular)
Type 1, simple relatively
small building, sometimes
converted residential,
100 – 3000 m2
Energy costs over
treated floor area (tfa)
Good practice
Typical
£3.50 m2 tfa
£6.00 m2 tfa
1
1
Gas or oil
(delivered)
Good practice
Typical
79 kWh/m2
151 kWh/m2
1
1
Electricity
(delivered)
Good practice
Typical
33 kWh/m2
54 kWh/m2
1
1
Good practice
Typical
£4.50 m2 tfa
£7.00 m2 tfa
1
1
Good practice
Typical
79 kWh/m2
151 kWh/m2
1
1
Good practice
Typical
54 kWh/m2
85 kWh/m2
1
1
Naturally ventilated (open plan) Energy costs over
Type 2, purpose-built, sometimes
treated floor area
converted industrial space, 500 m2
– 4000 m2
Gas or oil
(delivered)
Electricity
(delivered)
Your notes and comments
Table 2 continued Ł
For references see page 32
Rules of Thumb BSRIA 2001
Design area
Application
Other information
Rule of thumb
Ref
Air conditioned (standard)
Type 3, purpose-built, speculative
often intensively used,
2000 – 8000 m2
Energy costs
Good practice
Typical
£8.00 m2 tfa
£14.00 m2 tfa
1
1
Gas or oil
(delivered)
Good practice
Typical
97 kWh/m2
178 kWh/m2
1
1
Electricity
(delivered)
Good practice
Typical
128 kWh/m2
226 kWh/m2
1
1
Energy costs
Good practice
Typical
£13.00 m2 tfa
£20.00 m2 tfa
1
1
Gas or oil
(delivered)
Good practice
Typical
114 kWh/m2
210 kWh/m2
1
1
Electricity
(delivered)
Good practice
Typical
234 kWh/m2
358 kWh/m2
1
1
Design area
Application
Other information
Rule of thumb
Ref
Lighting benchmarks
Type 1
Good practice
Typical
12 W/m2
15 W/m2
1
1
Type 2
Good practice
Typical
12 W/m2
18 W/m2
1
1
Type 3
Good practice
Typical
12 W/m2
20 W/m2
1
1
Type 4
Good practice
Typical
12 W/m2
20 W/m2
1
1
Air conditioned (prestige)
Type 4, national or regional
head office, purpose-built to high
standards, intensively used and
extensive storage, parking and
leisure facilities, 4000 – 20 000 m2
Your notes and comments
TABLE 2: Lighting systems
25
For references see page 32
Your notes and comments
26
When to use:
Where to use:
Watch out for:
Electrical systems
To determine electrical supply requirements in buildings
When assessing the connected capacity in terms of unit floor area
Allowances for expansion, particularly for on-floor communications rooms
TABLE 1: Electrical supplies and loads
Design area
Application
Other information
Rule of thumb
Ref
Electrical supply
Electrical motors
Electrical motors
Above 3 kW rating
Up to and including
3 kW rating
3-phase supply
16
Direct on-line
starting
16
Assisted start
16
Lighting
10 – 12 W/m2
16
Small power
15 – 45 W/m2
16
Air conditioning
60 W/m2
35
Passenger lifts
10 W/m2
35
Electrical motors
Rules of Thumb BSRIA 2001
Electrical services load
(per m2 of building floor area)
Total load (kVA)
Design allowance for future
expansion (%)
For references see page 32
Above 4 kW rating
Small computer room
Net area
200 – 400 W/m2
16
Bespoke call centre
Net area
500 – 1000 W/m2
16
Total building load
Total kW/0⅐⅐8
35
% increase in load
Add 25% to
existing capacity
35
Your notes and comments