OSS Series
AUTOMATIC
TRANSFER
SWITCHES
SMALL
STRONG
SAFE
SMART
Outstanding technology captivates the world!
Superior Quality satisfies our customers!
Contents
Company History
3
OSS
4
- T, TB Type (60~400A)
Information to Order (
Features (
Specification (
Outline Dimension (
Wiring Diagram (
OSS - TN, TBN Type (60~600A)
Information to Order (
Features (
7
External View (
Application and Selection (
Specification (
Outline Dimension (
Wiring Diagram (
2 I Automatic Transfer Switches
OSS - PC Type (400~6300A)
Information to Order (
Features (
Specification (
Outline Dimension (
Wiring Diagram (
12
ATS Controller
Specification & Function (
Wiring Diagram (
ACD21, ACSD, ACD
21
Technical Details (
)
24
Safety Manual (
)
26
Company History
Dec. 1986
Oct. 1987
Feb. 1990
Established O-Sung Industrial Company.
Became a member of Korea Electrical Manufacturers Association (KOEMA).
Awarded two prizes for product development & excellent export records
from KOEMA.
Mar. 1990 Selected as "Intensive Technological Enterprise" by the Ministry of
Commerce, Industry and Energy.
Sep. 1993 Acquired "Quality Product" for Automatic Transfer Switch by the
Ministry of Commerce, Industry and Energy.
Nov. 1995 Awarded the Presidential Prize in the contest for Quality Control Team.
Jun. 1995 Became a member of Korea International Trade Association (KITA).
Nov. 1995~ Acquired Certificate of Quality Registration from Korea Standards
Association (KSA 9001, ISO 2000)
Apr. 1999 Acquired Certificate of Short Circuit Rating for ACB(2000A, 50kA)
from ASTA Certification Services.
Feb. 2000 Acquired Certificate of Short Circuit Rating for ACB(1600A, 3200A, 5000A
50kA) from ASTA Certification Services.
May. 2000 Certified by Taiwan Power Corporation(TPC) for ACB(1600~5000A 65kA).
Jul. 2002 Acquired CE mark for Automatic Transfer Switch
Oct. 2005 Passed Chinese Compulsory Certification Test for ACB in China.
Oct. 2005 Registered in the Small and Medium Business Administration as a Venture
Enterprise.
Aug. 2006 Acquired CB test Certificate for Air Circuit Breaker with electronic
overcurrent protection from Korea Testing Laboratory(KTL).
Nov. 2006 Acquired EC- Attestation of Conformity for Air Circuit Breaker with
electronic overcurrent protection from Product Service in Germany.
Automatic Transfer Switches I
3
OSS - T, TB Type
ATS(60~400A)
Information to Order
A Rated Current
OSS - 6
B Type
06
1
2
4
60A
100A
200A
400A
C Number of Poles
T : T-Type
TB : TB-Type
- - PA B C D
D Operating Voltage
2 : 2P
3 : 3P
4 : 4P
A1 : AC 110V
A2 : AC 220V
D1 : DC 110V
D2 : DC 125V
Features
Certain operation by latching mechanism
High current capability with low operating current
Excellent open and close performance
Compact and light weight.
Suitable for emergency power supply facilities.
Specification
606 -T, 606 -TB
61 -T, 61 -TB
TYPE
Rated Operational Voltage
Ue
Rated Current
Ie
60A, 100A
200A
400A
60A, 100A
200A
400A
Double Throw
Kind of Throw
Front(T), Back(TB)
Connection
Number of poles
Weight
Rated Short-Time Withstand Current (1sec)
Icw
Short-Circuit Making Capacity
Icm
Switching Capacity
2P
3P
4P
2P
3P
4P
2P
3P
4P
14kg
16kg
18kg
16kg
19kg
22kg
16kg
19kg
22kg
5kA
10kA
12kA
7.65kA
17kA
24kA
AC - 33B (6Ie making / 6Ie breaking cos = 0.5 )
DC - 31B (1.5Ie making / 1.5Ie breaking L/R = 1ms )
60 times per an hour
Switching Frequency
Operating Current
Operating Time
Cautions
64 -T, 64 -TB
AC 600V, DC 125V
Neutral Phase Current
Number of Operating
Cycles
62 -T, 62 -TB
DC 110V ~125V
14A
14A
14A
AC 100V ~110V
7A / 14A
7A / 14A
7A / 14A
AC 200V ~ 240V
3.5A / 7A
3.5A / 7A
3.5A / 7A
Change - over time
80 ms
Opening time
60 ms
Without Current
10,000
With Current
5,000
1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. If the control sources are supplied to A side and B side at the same time, the switching coil can be damaged.
3. Control Relay should be selected considering sufficient contact capacity to withstand against more than control current.
1.
2.
3.
4 I Automatic Transfer Switches
OSS - T, TB Type
ATS(60~400A)
Outline Dimension
OSS - T Type
Operating circuit terminal
Manual handle inlet
A Power source side main circuit terminal
A
Load side main circuit terminal
B Power source side main circuit terminal
B
Change over indicator
OSS - TB Type
PANEL CUT
Automatic Transfer Switches I
5
OSS - T, TB Type
ATS(60~400A)
Wiring Diagram
AC 110V, AC 220V
DC 110V, DC 125V
'A'-Power Source
A1
ATS
B1
'A'-Power Source
a1 b1 a3 b3
A1
ATS
Xb
Xa
a1 b1 a3 b3
B1
Xa
Xb
To Load
C1
To Load
C2
Si
C1
C2
A2
B2
Si
A2
B2
a 2 b2 a 4 b4
a2 b2 a4 b4
'B'-Power Source
'B'-Power Source
A1 , A2
A-Power Closing Terminal
B1 , B2
B-Power Closing Terminal
a1, a2, a3, a4
A-Power Aux Switch
C1
A-Power Closing Coil
b1, b2, b3, b4
B-Power Aux Switch
C2
B-Power Closing Coil
Si
Control Switch
Xa , Xb
Silicon Rectifier
Typical Operating Circuit
Using a changeover switch
Standard
MANU
Using a timer
AUTO
A1
B1
T - TYPE
TB - TYPE
27
A2
84
B2
from B-power source
84
27
84
A1
B1
T - TYPE
TB - TYPE
27
A2
84
from A-power source
from B-power source
27
from A-power source
from B-power source
from A-power source
27
B2
27
T1
84
A1
27
T1
84
A2
T2
Wiring Diagram
DC Operating and Control
P
27X
C/S
84X
B1
T - TYPE
TB - TYPE
27T
84X
ATS
AUX
27T
A1
27X
ATS
AUX
84T
A2
R
B2
G
27T
AUTO 84T
27X
AUTO
C/S
MANU 27X
27X
C/S
84X
ATS
AUX
R
G
B1
T - TYPE
TB - TYPE
27T
ATS
AUX
27T
A1
27X
84X
84T
A2
DC control source
C/S
from B-power source
27X
AUTO
from A-power source
from B-power source
from A-power source
AUTO 84T
MANU
MANU 27X
MANU
27T
B2
N
Source-B Operating Relay
27X
Source-A Operating Relay
84X
27T
27X Operating Delay Relay
84T
84X Operating Delay Relay
Automatic , Manual
C/S
Control Switch
AUTO,MAN
6 I Automatic Transfer Switches
B1
T - TYPE
TB - TYPE
27
AC Operating and Control
T2
B2
OSS - TN, TBN Type
ATS(60~600A)
Information to Order
A Rated Current
06
60A
1
2
OSS - 6
B Type
4
6
100A 200A 400A 600A
TN : TN-Type
TBN : TBN-Type
C Number of Poles
2 : 2P
3 : 3P
4 : 4P
- - PA B C D
D Operating Voltage
A1 : AC 110V
A2 : AC 220V
D1 : DC 110V
D2 : DC 125V
Features
Off position stop method
In case with the uninterrupted power system, it is
recommended to stop at the OFF position set by tripping
mechanism for the stable power. Instantaneous transfer without
stop can be also performed by operating signal.
A Off B, B Off A, and A Off A, B Off B
And also, instantaneous transfer can be performed by operating
signal.
O
One-Coil Application
One-coil is employed for the transfer to normal power source
and emergency power source.
Compact & Lightweight Design
Compact & lightweight design makes the minimized mounting
space and convenient installation.
Excellent Breaking Capacity
Designed for suffciently large chamber to extinguish the arc
when transferred. Arc-extinguishing area is designed for
convenient inspection and maintenance.
Protection against the remaining power source
Time delay to transfer is available so that the remaining power
can not be induced to the main power to protect the load.
Construction for Safety
For safe operation, molded construction is employed on
breaking parts. And also, latching indicator is prepared to
indicate the operating condition.
External View
Earthing Terminal
Manual Operating Shaft (Anti-Clockwise)
Circuit Diagram
Name Plate
Trip Button
Selective Button for “B” Power-Closing
On/Off Indicator
Circuit Terminal for “A” Power
Contacts
Arc-Extinguishing Chamber
Aux Switch
Circuit Terminal for “B” Power
Control Circuit Terminal Block
Main Circuit Terminal for Load
Amateur for Closing Coil
Automatic Transfer Switches
I7
OSS - TN, TBN Type
ATS(60~600A)
Application and Selection
Applicable Standards
IEC 60947-6-1
KSC 4504
JEM 1038
KSC 0703
UL 1008
IEC 60947-6-1
KSC 4504
JEM 1038
KSC 0703
UL 1008
Control Order
It is recommended to give more than 0.5 sec for operation,
though transfer time is completed within 0.3 sec.
Interlock
Interlocking is required for control circuit so that control order
should not suppy to both A power source side and B power
source side simultaneously. For TN type ATS, Sequence setting
is required so that closing or tripping order should not supply in
the same direction.
Control Circuit
ATS is designed so that operation current should be off by
internal switch after completion of operation. If operation current
is off with auxiliary switch of the unit, it may cause a malfunction.
Specification
606 -TN, TBN
61 -TN, TBN
TYPE
Rated Operational Voltage
Ue
Rated Current
Ie
AC 600V, DC 125V
60A, 100A
60A, 100A
Neutral Phase Current
Number of poles
Weight
Rated Short-Time Withstand Current (1sec)
Icw
Short-Circuit Making Capacity
Icm
Switching Capacity
200A
400A, 600A
2P
3P
4P
2P
3P
4P
2P
3P
4P
14kg
16kg
18kg
16kg
19kg
22kg
16kg
19kg
22kg
5kA
10kA
12kA
7.65kA
17kA
24kA
AC - 33B (6Ie making / 6Ie breaking cos = 0.5 )
DC - 31B (1.5Ie making / 1.5Ie breaking L/R = 1ms )
60Time / Hour
Switching Frequency
Operating Current
DC 110V ~ 125V
6A
6A
7A
AC 100V ~ 110V
3A / 6A
3A / 6A
3.5A / 7A
AC 200V ~ 240V
1.5A / 3A
1.5A / 3A
2A / 3.5A
DC 110V = 2.5A, AC 110A = 2.5A, AC 220V = 1.5A
Trip Coil Current
“A” POWER
“B” POWER
Cautions
400A, 600A
Front(TN), Back(TBN)
Connection
Number of Operating
Cycles
200A
Double Throw
Kind of Throw
Operating Time
64 -TN, TBN
66 -TN, TBN
62 -TN, TBN
Making
55 ms
55 ms
60 ms
Breaking
20 ms
20 ms
25 ms
Making
80 ms
80 ms
90 ms
Breaking
20 ms
20 ms
10,000
25 ms
Without Current
With Current
5,000
1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.
3. Control Relay should be selected considering sufficient contact capacity to withstand against more than control current.
1.
2.
3.
8 I Automatic Transfer Switches
OSS - TN, TBN Type
ATS(60~600A)
Outline Dimension
60A, 100A
200A
400A, 600A
606-TN, 61-TN
62-TN
64 -TN, 66-TN
* Arc space for main circuit
- 30mm for AC 220V
- 60mm for AC 660V
Automatic Transfer Switches I
9
OSS - TN, TBN Type
ATS(60~600A)
Outline Dimension
606-TBN~66-TBN
* Arc space for main circuit
- 30mm for AC 220V
- 60mm for AC 600V
PANEL CUTTING
10 I Automatic Transfer Switches
TERMINAL THICKNESS
OSS - TN, TBN Type
ATS(60~600A)
Wiring Diagram
Typical Operating Circuit
Standard
Using a changeover switch
Using a timer
Using a condensor tripping device
Automatic Transfer Switches I
11
OSS - PC Type
ATS(400~6,300A)
Information to Order
OSS - 6
- - P- A B C D E
A Rated Current
08
10
800A
1000A
12
16
1250A 1600A
B Type
PC
20
25
2000A 2500A
32
40
50
63
3200A
4000A
5000A
6300A
C Number of Poles D Operating Voltage
: Standard
3 : 3P
4 : 4P
Features
One coil mechanism
One coil mechanism is applied.
Transfer indicator provided
Transfer indicator is fitted to indicate the transfer status.
Easier busbar arrangement
If the ATS is installed with the ACB in switchgear, Busbars can
be easily arranged.
Fixed type & Drawout type available
Fixed type and Drawout type are available for customer's
convenient applicaion.
Quick replacement of ATS
If malfunction occurs, drawout type of ATS can be changed
within 5 minutes.
Perfect transfer mechanism
By spring transfer mechanism, ATS can be completely and
perfectly transferred. There will be NO unattached position in
any case.
Sufficient current capacity
Sufficient current carrying contacts are designed to withstand
against over current.
Minimized opening & Closing impact
Opening and closing impact is minimized.
12 I Automatic Transfer Switches
A1 : AC 110V
A2 : AC 220V
D1 : DC 110V
D2 : DC 125V
E
Mounting System
F : Fixed
D : Draw out
OSS - PC Type
ATS(400~6,300A)
Specification
TYPE
Rated Voltage
Ue
Rated Current
Ie
608-PC
610-PC
800A
1000A
800A
1000A
616-PC
620-PC
1250A
1600A
2000A
1250A
1600A
2000A
AC 600V, DC 125V
Neutral Phase Current
Double Throw
Kind of Throw
Back
Connection
Number of Poles
Weight
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
Fixed
55kg
65kg
55kg
65kg
60kg
70kg
65kg
75kg
75kg
90kg
Drawout
80kg
95kg
80kg
95kg
90kg
105kg
95kg
110kg
110kg
140kg
Rated Short-Time Withstand Current (1sec)
25kA
25kA
30kA
35kA
40kA
52.5kA
52.5kA
63kA
73.5kA
84kA
Icw
Short-Circuit Making Capacity
Icm
Switching Capacity
AC - 33B (6 Ie making / 6 Ie breaking cos = 0.5 )
DC - 31B (1.5 Ie making / 1.5 Ie breaking L/R = 1ms )
60Time / Hour
Switching Frequency
Operating Current
Operating Time
Number of Operating
Cycles
Cautions
20Time / Hour
45A
50A
65A
AC 100V ~ 110V
23A / 45A
25A / 50A
33A / 65A
AC 200V ~ 240V
15A / 30A
20A / 40A
25A / 50A
Change - over time
120 ms
Opening time
90 ms
Without Current
With Current
1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.
1.
2.
Rated Voltage
Ue
Rated Current
Ie
625-PC
632-PC
2500A
3200A
2500A
3200A
Number of Poles
4000A
5000A
6300A
4000A
5000A
6300A
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
Fixed
75kg
90kg
80kg
100kg
145kg
180kg
160kg
200kg
160kg
200kg
Drawout
110kg
140kg
125kg
155kg
220kg
275kg
245kg
305kg
245kg
305kg
Rated Short-Time Withstand Current (1sec)
Icw
Short-Circuit Making Capacity
Icm
Switching Capacity
50kA
50kA
65kA
65kA
65kA
105kA
105kA
143kA
143kA
143kA
AC - 33B (6 Ie making / 6 Ie breaking cos = 0.5 )
DC - 31B (1.5 Ie making / 1.5 Ie breaking L/R = 1ms )
10Time / Hour
Switching Frequency
Number of Operating
Cycles
663-PC
Back
Connection
Operating Time
650-PC
Double Throw
Kind of Throw
Operating Current
640-PC
AC 600V, DC 125V
Neutral Phase Current
Weight
10Time / Hour
DC 110V ~ 125V
TYPE
Cautions
612-PC
DC 110V ~ 125V
65A
80A
AC 100V ~ 110V
33A / 65A
40A / 80A
AC 200V ~ 240V
25A / 50A
33A / 65A
Change - over time
120 ms
Opening time
90 ms
Without Current
With Current
1. For complete operation, Be sure to provide control source for more than 0.5sec.
2. When control source will be provided to A side and B side simultaneously, Coil may be damaged.
1.
2.
Automatic Transfer Switches I
13
OSS - PC Type
Outline Dimension
ATS(800~6,300A)
800~1600A Fixed
unit : mm
OSS-608~610-PC
OSS-612-PC
OSS-616-PC
14 I Automatic Transfer Switches
OSS - PC Type
ATS(800~6,300A)
2000~3200A Fixed
Outline Dimension
unit : mm
128
530
341
381
431
OSS-620~625-PC
381
104
53
69
507
OSS-632-PC
381
104
79
53
521
Automatic Transfer Switches I
15
OSS - PC Type
ATS(800~6,300A)
4000~6300A Fixed
Outline Dimension
unit : mm
380
227(3P)
380
342(4P)
432
381
39
530
70
834
123
1,064(4P)
451
1,096(4P)
OSS-640-PC
381
70
256
256
247
282
53
69
527
OSS-650~663-PC
256
70
256
381
247
282
53
79
541
Panel cutting (Fixing hole)
16 I Automatic Transfer Switches
158
OSS - PC Type
Outline Dimension
ATS(800~6,300A)
800~1600A Draw Out
unit : mm
OSS-604~610-PC
OSS-612-PC
OSS-616-PC
Automatic Transfer Switches I
17
OSS - PC Type
Outline Dimension
ATS(800~6,300A)
2000~3200A Draw Out
unit : mm
OSS-620~625-PC
OSS-632-PC
18 I Automatic Transfer Switches
OSS - PC Type
Outline Dimension
ATS(800~6,300A)
4000~6300A Draw Out
unit : mm
OSS-640-PC
OSS-650~663-PC
Automatic Transfer Switches I
19
OSS - PC Type
ATS(800~6,300A)
Wiring Diagram
AC 110V, AC 220V
A1
B1
C1
DC 110V, DC 125V
'A'-Power Source
a1
C2
a3
b1
b3
A1
MG1 MG2
A2
Xb
'A'-Power Source
a1
C2
Xa
CC
MG1 MG2
C1
a3
b1
b3
MG1 MG2
Xa
Si
B1
MG1 MG2
To Load
MG1
MG1 MG2
a2
B2
a4
b2
Xb
CC
To Load
b4
A2
MG2
a2
B2
a4
b2
b4
'B'-Power Source
'B'-Power Source
A1 , A2
A-Power Closing Terminal
AX , BX
Control Switch
B1 , B2
B-Power Closing Terminal
MG1 , MG2
Magnetic Coil
CC
Si
Closing Coil
a1, a2, a3, a4
A-Power Aux Switch
Silicon Rectifier
b1, b2, b3, b4
B-Power Aux Switch
Typical Operating Circuit
Standard
Using a changeover switch
Using a timer
MANU
AUTO
B1
C2
C1
PC - TYPE
27
B2
A2
84
from B-power source
A1
84
A1
B1
C1
C2
PC - TYPE
27
A2
84
B2
from A-power source
84
27
from A-power source
27
from B-power source
from B-power source
from A-power source
27
T1
84
27
A1
B1
27
T1
84
A2
T2
B2
27
Wiring Diagram
AC Operating and Control
DC Operating and Control
P
MANU
27X
84X
ATS
AUX
ATS
AUX
27T
A1
B1
C1
C2
PC - TYPE
R
27X
27T
84X
84T
A2
B2
G
27
AUTO 84T
27
C/S
AUTO
MANU 27
27
C/S
84X
ATS
AUX
ATS
AUX
R
G
27
A1
B1
C1
C2
PC - TYPE
27X 27T 84X 84T
A2
B2
DC control source
27
MANU
27X C/S
from B-power source
AUTO
AUTO 84T
from A-power source
from B-power source
from A-power source
MANU
27T
N
27X
Source-A Operating Relay
84X
Source-B Operating Relay
27T
27X Operating Delay Relay
84T
84X Operating Delay Relay
Automatic , Manual
C/S
Control Switch
AUTO,MANU
Caution : More than 2.0mm2 power cable used for less than 1,600A ATS.
More than 3.5mm2 power cable used for more than 2,000A ATS.
20 I Automatic Transfer Switches
C1
PC - TYPE
T2
C2
ATS Controller
ACD21 / ACSD
External View
B-power source indicating LED for Emergency
A-power source indicating LED for Utility
ATS A-power transfer status indicating LED
SYC(In-phase Monitor) indicating LED
Selection switch of A-power source
Selection switch of B-power source
ATS B-power transfer status indicating LED
Selection switch of automatic or manual
Specification
Rated operating voltage : 220VAC
Frequency : 50 / 60Hz
Contacts capacity for ATS control : AC250V, 10A
(No-load contacts)
Contacts capacity for Abnormal power source : AC250V,
10A (No-load contacts)
Basic Function
Automatic or manual ATS control
Indicating lights for A-power (Utility), B-power (Emergency)
and ATS transfer status
- Power source : A-power (Green LED), B-power (Red LED)
(Displayed when voltage is above 85%)
- Transfer status : A-power (Green LED), B-power (Red LED)
Manual operation buttons
- For A-power(Utility) : Green
- For B-power(Emergency) : Red
- Note : Built-in LED is on for selective button
Setting for automatic transfer time
- Time setting at rear side to avoid unnecessary setting change
- Variable time settings (0~30sec)
While timer is working, indicating lamp for transferable ATS
is flickering
Detection for open phase of Utility power source
(For 3 4W, 220/380VAC only)
Detecting the power failure, low voltage and abnormal
condition of Utility source, the ACD sends the engine
starting signal to the Generator.
In-phase Monitor
on
Opti
On & Off of In-Phase Monitor can be selected by selection switch
- When In-Phase Monitor is selected, Transfer is made manually
or automatically when synchronized.
- When In-phase Monitor is not selected, synchronizing
indication lamp is not on.
When synchronized, Yellow LED is flickered.
When synchronized more than 3 cycles, Tranfer will be made.
Under the manual mode, when the selection button is
selected for Utility or Generator, Built in LED will be
flickering until synchronized.
Ordering Information
ACD21 (ATS control device) : Basic Function
ACSD (ATS control synchronizing device) : Built-in In-phase Monitor
-
-
on
Opti
-
ATS Controller
ACD21 / ACSD
Wiring Diagram
3 4W 380/220V
OSS
3 4W 220/127V
- T, TB Type
OSS - TN, TBN Type
OSS - PC Type
Outline Dimension
22 I Automatic Transfer Switches
3 3W 220V
ATS Controller
ACD
Controller
Specification
Rated operating voltage : 220VAC
Frequency : 50 / 60Hz
Contacts capacity for ATS control : AC250V, 10A
(No-load contacts)
Contacts capacity for Abnormal power source : AC250V,
10A (No-load contacts)
Fitment : Front Type
Basic Function
Automatic or manual ATS control
Built-in indicator for A-power (Utility), B-power (Emergency)
and ATS transfer status
- Power source : A-power (Green LED), B-power (Red LED)
(Displayed when voltage is above 85%)
- Transfer status : A-power (Green LED), B-power (Red LED)
Manual operation buttons
- For A-power(Utility) : Green
- For B-power(Emergency) : Red
- Note : Built-in LED is on for selective button
Setting for automatic transfer time
- Transferring time setting is available at rear side to avoid
unnecessary touch.
- Variable time settings (0~30sec)
While timer is working, indicating lamp for transferable ATS
is flickering
Detection for open phase of Utility power source
(For 3 4W, 220/380VAC only)
Monitering for power failure, and low voltage of A power and
B power .
-
Wiring Diagram
OSS - PC Type
OSS - TN, TBN Type
OSS
- T, TB Type
PANEL CUTTING : W157
H131 (unit:mm)
Technical Details
Standard Operating Conditions
Ambient Temperature: -5 C~+40 C(but, the average temperature for 24 hours shall be lower than +35 C)
Altitude: Below 2000m
Environmental conditions
Relative humidity shall be less than 85% at max. temp. +40 C, less than 90% at 20 C
It shall not be allowed to use or store within the area of petrochemicals, ammonia, and corrosive gas.
Storage Temp.: -20 C~+60 C(but, the average temperature for 24 hours shall be lower than +35 C)
Applicable current by the temperature
Under the environment with over than 40 , please note the rating current as follow.
Rated current
Ambient
temperature
Note) IEC 60947-1 Standard is applied to the data for 40 C.
Bolt tightening torque(for nut)
Selection of TR Capacity
TR capacity should be selected more than the value
calculated by the following formula.
Operation Voltage x Operation Current x 0.5 = ( )VA
e.g.) Operation Voltage AC 220V, Operation Current 4A
220 x 4 x 0.5 = 440VA, TR capacity of more than 440 VA is
recommended.
Selection of Control Relay
The capacity of UVR, Operating Relay and Timer contactor
should be higher than ATS operating current.
Note : If the control power source is not stable, it is
recommended to use Automatic Voltage Regulator.
24 I Automatic Transfer Switches
Automatic Transfer Switches I