Structured Cabling
Standard Updates
By Anton Indrawata
Regional Trainer
Structured Cabling
Structured Cabling
Standard Updates
Standard Updates
By Anton
By Anton
Indrawata
Indrawata
Regional Trainer
Regional Trainer
23
Standards Framework

Mandatory
z Local Authority Technical Standards:
z Cable and cabling components (Permit or CCL required)
z Wiring Practices (particularly separations/segregation's)

Industry Recommendations
z ISO/IEC 11801 & EIA/TIA 568 B : Structured Cabling Design,
dimensions, component specification, installation practices, compliance
testing, Class D or Cat.5E bandwidth up to100MHz, Class E or Cat. 6
bandwidth up to 250 MHz parameters.
z EIA/TIA 569A: Design and installation practices of cabling pathways,
spaces, support structures, termination, cross connect enclosures and
cable entrance facilities.


z EIA/TIA 606: Administration of communications cabling systems includes
plant symbols, cable records and component labeling.
23
Cabling Standardisation history
TIA
568
+
TSB
36
+
TSB
40A
=
TIA
568A
+
TSB
67,72,75
+
TIA568A
Add 1-5
=
TIA 568-B
1,2,3
ISO
11801
ISO
11801
Add 1-2
EN

50173
EN
50173
Add 1
Cat3
Cat4
Cat 5
Class D
Cat 5E Cat 6, 7
New Class D
1991 1995 1999 2001
TIA
568B.2-1
TIA/
EIA
ISO
CENELEC
Class E, F
ISO
11801
Ed.2
2002
EN
50173
Ed.2
2000
23
ISO/IEC 11801 Standards history

The first and most important document in this series is ISO/IEC 11801


ISO/IEC 11801 – 1995: Generic Cabling for Customer Premises
z Defines performance of Category 5 / Class D of Basic and Channel Link
z Superseded by ISO/IEC 11801 2
nd
edition 2002

ISO/IEC 11801 AMENDMENT2- 1999
z Major update to ISO/IEC 11801 – 1995
z Adds requirements for new measurements, defines Permanent Link and
Channel
z Harmonized with EIA/TIA 568B Cat 5E

ISO/IEC 11801 2
nd
edition – 2002
z The 2
nd
edition incorporate specifications for Category 6 / Class E and
Category 7 / Class F cabling components
23
CENELEC Standards history

EN 50173 - 1995: Generic Cabling Standard for Customer Premises
z Specifies generic cabling for use within commercial premises
z Very similar to ISO 11801
z Amendment 1999 add permanent link and channel definitions as well as
new measurement parameters

EN 50173 – 2000 2

nd
edition
z To harmonize with ISO 11801 2
nd
edition and include specifications of
Category 6 / Class E and Category 7 / Class F cabling components

EN 50174-1-1999: Administration, documentation, records
z Describes requirements for administration system, documentation of
pathway, spaces, cables, terminations, grounding in accordance with EN
50173
23
North American Standards history

EIA/TIA 568A - 1995: Commercial Building Telecommunications Wiring
Standard
z Establishes technical and performance criteria for cabling system
configuration, interfacing and connecting hardware

EIA/TIA 568A-A1 – 1998: Delay & Delay Skew
z Defines and specifies requirement s for propagation delay and delay
skew in cables, components, basic link and channels
z Replaced by EIA/TIA 568B

TIA 568A-A2 – 1998: Miscellaneous Changes
z Requirement for testing connecting hardware with both common and
differential mode terminations
z Replaced by EIA/TIA 568B
23
North American Standards history


EIA/TIA 568A-A3 – 1998: Bundled and Hybrid Cables
z Defines and specifies requirement for testing of bundled and hybrid
cables
z Replaced by EIA/TIA 568B

EIA/TIA 568A-A4 – 1999: Patch Cords
z Defines and specifies NEXT and RL for patch cables
z Replaced by EIA/TIA 568B

EIA/TIA 568A-A5 – 1999: Additional Transmission Performance
Specifications for Enhanced Category 5 Cabling
z Provides performance requirements for Enhanced Category 5
components, cables and links; includes all the measurements in
TSB67 and TSB95, Replaced by EIA/TIA 568B
23
North American Standards history

EIA/TIA 568B.1 – 2000: Commercial Building Telecommunications
Wiring Standard
z This is a major standard release that updates and replaces: TSB67,
TSB72, TSB75, TSB95, TIA 568A and its addendum’s 1,2,3,4,5 and
TIA ScTP.
z Include Category 5E performance levels, 50/125um fiber
z Category 5E becomes the minimum accepted performance level

EIA/TIA 568-B.2: 100 Ohm Twisted Pair Cabling Standard
z Technical content 0n 100 Ohm twisted pair cabling referenced by
TIA 568-B.1


EIA/TIA 568 – B.2-1: Category 6
z This Cat.6 standard has been ratified on June 20,2002, the
most complete document providing Category 6 performance
specifications
23
North American Standards history

EIA/TIA 568-B.3: Optical Fibre Cabling Standard
z Technical content on optical fibre cabling that is referenced by EIA/TIA
568-B.1

EIA/TIA 568-B.4: Shielded Twisted Pair Cabling Standard
z Technical content on shielded twisted pair cabling that is referenced by
EIA/TIA 568-B.1

EIA/TIA 569A – 1995: Commercial Building Standard for
Telecommunications Pathways and Spaces
z Specifies design and construction of pathways and spaces, installation
practices for telecommunications services within and between
commercial buildings

EIA/TIA 570A – 1998: Residential and Light Commercial
Telecommunications Wiring Standard
z Specifies residential cabling systems, requirements and structure
23
North American Standards history

EIA/TIA 606 – 1994: Administration Standard for the
Telecommunications Infrastructure of Commercial Buildings
z Specifies administration of communications wiring and connecting

hardware, building distribution systems, grounding and bonding.
z Standardized labeling and documentation requirements for generic
cabling in commercial buildings

EIA/TIA TSB67 – 1995: Transmission Performance Specifications for
Field Testing of UTP Cabling Systems
z Defines the basic link and channel
z Specifies performance requirements for the basicl link and channel, wire
map, length, attenuation, NEXT.
z Defines field measurement procedures and test instruments
requirements; replaced by EIA/TIA 568B.
23
North American Standards history

EIA/TIA TSB72 – 1995: Centralized Optical Fiber Cabling Guidelines
z Replaced by EIA/TIA 568B

EIA/TIA TSB75 – 1996: Additional Horizontal Cabling Practices for
Open Offices ( Consolidation Points & MUTOA )
z Replaced by EIA/TIA 568B.

EIA/TIA TSB95 – 1999: Additional Transmission Performance
Specification for UTP
z For Gigabit Ethernet: defines minimum test requirements for RL,
ELFEXT, Powersum ELFEXT, propagation delay and delay skew
z Replaced by EIA/TIA 568B
23
ANSI EIA/TIA 568-A Revision to 568-B
568-B.1
Main document :


Installation

Link requirements

Testing
568-B.2
100 ohm
UTP/FTP
568-B.3
FIBER
568-B.4
STP-A
Document :
•Cable

Connector

Link

Model
568-A
+
TSB-67
TSB-72
TSB-75
TSB-95
TSB: Telecommunications System Bulletin
23
Amendment of EIA/TIA 568A, Summary


Recognition of 100 Ohm ScTP ( FTP) cabling

Deletion of 150 ohm STP cabling as recognized cable for new
installation

Recognition of 50/12 5µm multimode fibre cabling for both horizontal
and backbone applications

Removal of Category 4 specifications

Deletion of Category 5 cabling as recognized cable for new installation

A min. of Category 5E recommended at the first telecommunications
outlet and a min. of Cat5E required for the second TO or 50/125 µm or
62/125 µm multimode optical cable.
23
CENELEC Standards history

EN 50173 - 1995: Generic Cabling Standard for Customer Premises
z Specifies generic cabling for use within commercial premises
z Very similar to ISO 11801
z Amendment 1999 add permanent link and channel definitions as well as
new measurement parameters

EN 50173 – 2000 2
nd
edition
z To harmonize with ISO 11801 2
nd

edition and include specifications of
Category 6 / Class E and Category 7 / Class F cabling components

EN 50174-1-1999: Administration, documentation, records
z Describes requirements for administration system, documentation of
pathway, spaces, cables, terminations, grounding in accordance with EN
50173
23
CENELEC Standards history

EN 50174-2-2000: Planning and installation practises
z Specifies requirements for planning, specification, quality, assurance
and installation of new balanced copper and optical fibre

EN 50174-3-1999: Installation, Planning and Practises External to
Buildings
z Details requirements and guidance for installation, planning and
practises for balanced copper and optical fibre external to buildings

EN 50346-2000: Procedure for Testing Premise Cabling
z Specifies procedures for testing the transmission performance of
installed cabling inpremises
z To be used for acceptance testing, verification, and trouble shooting of
faults
23
CENELEC Standards history

EN 50173 - 1995: Generic Cabling Standard for Customer Premises
z Specifies generic cabling for use within commercial premises
z Very similar to ISO 11801

z Amendment 1999 add permanent link and channel definitions as well as
new measurement parameters

EN 50173 – 2000 2
nd
edition
z To harmonize with ISO 11801 2
nd
edition and include specifications of
Category 6 / Class E and Category 7 / Class F cabling components

EN 50174-1-1999: Administration, documentation, records
z Describes requirements for administration system, documentation of
pathway, spaces, cables, terminations, grounding in accordance with EN
50173
23
Comparison between EIA/TIA, ISO & CENELEC
23
Comparison between EIA/TIA, ISO & CENELEC
23
Comparison between EIA/TIA, ISO & CENELEC
23
Comparison between EIA/TIA, ISO & CENELEC
Notes:
23
ISO 11801, General Purposes

Structured Cabling Elements:
z Campus Distributor (CD) - previously campus MDF
z Campus Backbone cabling

z Building Distributor (BD) - previously building MDF
z Building backbone cabling
z Floor Distributor (FD) - previously floor IDC or TC
z Horizontal (floor) cabling
z Transition Point (TP) - optional and should be avoided
z Telecommunications Outlet (TO)
z Consolidation Point (CP)
z MUTO - Multi User Telecommunications Outlet
23
Campus Application of
Generic Cabling System
FLOOR DISTRIBUTOR equipped with:
FD
Campus cabling
Incoming services
PSTN, ISDN etc.
Cross connect
Active and Passive components
Optical-electrical converters
LAN Hubs, Bridges, Routers etc.
Building entry facilitiesEquipment room
PABX, Data switch etc.
FD = Floor Distributor
BD = Building Distributor
CD = Campus distributor
TO = Telecom. Outlet (RJ-45)
Fibre-optic or copper cabling
Copper cabling
TO
Backbone cabling

Horizontal cabling
CP
FD
TO
TO
TO
TO
TO
TO
TO
TO
FD
TO
TO
FD
BD CD
23
Multi Campus Buildings
FD
TO
CP
FD
TO
TO
TO
TO
TO
TO
TO
TO

FD
TO
TO
FD
BD CD
TO
FD
BD/FD
TO
TO
TO
TO
FD
BD
TO
TO
TO
Campus
cabling
PSTN
Building entry facilities
Equipment room
PABX, Data switch etc.
23
ISO 11801: Cabling Sub-Systems
Universal Cabling System
Campus cable
Building
Backbone
Cable

Workplace
Cable
Horizontal Cable
Cross connect - Jumper or Patchcord
FDBDCD
TOCP
23
ISO 11801 - Maximum Cabling Lengths
Campus
Cable
ABCD
ASE ASE ASE
GF E
C + D ≤ 20 m; F + G ≤ 30 m; A + B + E = 10 m max.
ASE
= Application-specific equipment
2000 m
500 m 90 m
Backbone
Cable
Horizontal
Cable
1,500 m
FDBDCD
TOCP