Copyright © 2020 NR. All rights reserved.
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and benefits
afforded under P.R. China and international copyright and patent laws in its products, including but
not limited to software, firmware and documentation. NR Engineering Co., Ltd. is licensed to use
this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd,
including but not limited to copyright, rights in inventions, patents, know-how, trade secrets,
trademarks and trade names, service marks, design rights, database rights and rights in data, utility
models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered sufficiently
for your purposes, please do not hesitate to contact us.
Preface
Preface
About This Manual
This manual describes the configuration scheme in multiple application scenarios for PCS-978S
Transformer Relay, including how to connect the device to a computer and to configure functions,
such as control, protection, measurement and supervision in using of configuration tool.
To start using this manual for application configuration, user should know the basic operations of
the configuration tool PCS-Studio.
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for personal
safety, as well as to avoid material damage. Information is highlighted and illustrated as follows
according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage.
Indicates that property damage can result if the measures specified are
not taken.
Important information about the device, product handling or a certain
section of the documentation which must be given particular attention.
Instructions and Warnings
The following hazard statements apply to this device.
Disconnect or de-energize all external connections BEFORE opening this
device. Contact with hazardous voltages and currents inside this device can
cause electrical shock resulting in injury or death.
PCS-978S Transformer Relay
I
Date: January 15, 2020
Preface
Contact with instrument terminals can cause electrical shock that can result
in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not qualified
to service this equipment, you can injure yourself or others, or cause
equipment damage.
This device is shipped with default passwords. Default passwords should
be changed to private passwords at installation. Failure to change each
default password to a private password may allow unauthorized access. NR
shall not be responsible for any damage resulting from unauthorized access.
DO NOT look into the fiber (laser) ports/connectors.
DO NOT look into the end of an optical cable connected to an optical output.
DO NOT perform any procedures or adjustments that this instruction
manual does not describe.
During installation, maintenance, or testing of the optical ports, ONLY use
the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
PCS-978S Transformer Relay
II
Date: January 15, 2020
Preface
are NOT user serviceable. Return units to NR for repair or replacement.
Equipment components are SENSITIVE to electrostatic discharge (ESD).
Undetectable permanent damage can result if you do not use proper ESD
procedures. Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment. If your facility is not
equipped to work with these components, contact NR about returning this
device and related NR equipment for service.
Insufficiently rated insulation can deteriorate under abnormal operating
conditions and cause equipment damage. For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions.
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables. Please use
the wiring method recommended in the manual for communication terminals.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage can
result otherwise.
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure.
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.
PCS-978S Transformer Relay
III
Date: January 15, 2020
Preface
Menu path is connected with the arrow "→" and bold.
For example: the access path of protection settings is: MainMenu→Settings→Protection
Settings.
Settings not in t.he table should be placed in brackets.
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
For example: press the button "ENT".
Symbols
AND Gate
&
&
&
>=1
>=1
OR Gate
>=1
Comparator
Binary signal Input
BI
Signal input
SIG
xxx
xxx
Setting input
SET
xxx
PCS-978S Transformer Relay
IV
Date: January 15, 2020
Preface
Enable input
EN
xxx
Timer
Optional definite-time or inverse-time characteristic
Timer
t
t
Timer
Fixed delay pickup (10ms), fixed delay dropout (2ms)
10ms
2ms
Timer
Settable delay pickup, fixed delay dropout
[Tset1]
0ms
Timer
Fixed delay pickup, settable delay dropout
0ms
[Tset2]
Timer
Settable delay pickup, settable delay dropout
[Tset1]
[Tset2]
Generator
G
Transformer
PCS-978S Transformer Relay
V
Date: January 15, 2020
Preface
Reactor
Motor
M
Capacitor
C
Busbar
Circuit breaker
52
Current transformer
3CT
*
Voltage transformer
3VT
Disconnector
Earth
PCS-978S Transformer Relay
VI
Date: January 15, 2020
Preface
Three-phase Corresponding Relationship
Basic
A, B, C
L1, L2, L3
R, Y, B
AN, BN, CN
L1N, L2N, L3N
RN,YN, BN
ABC
L123
RYB
U (voltage)
V
U
Example
Ia, Ib, Ic, I0
IL1, IL2, IL3, IN
IR, IY, IB, IN
Ua, Ub, Uc
VL1, VL2, VL3
UR, UY, UB
Uab, Ubc, Uca
VL12, VL23, VL31
URY, UYB, UBR
U0, U1, U2
VN, V1, V2
UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This manual is a comprehensive work covering all aspects of relay application and use. Read the
sections that pertain to your application to gain valuable information about using the PCS-978S. To
concentrate on the target sections of this manual as your job needs and responsibilities dictate. An
overview of each manual section and section topics follows.
1 Functions and Applications
Introduces of device functions and typical application scenarios.
2 Connection to the Configuration Tool
Introduction of the PCS-Studio configuration tool with the connection method.
3 Basic Function
Basic functions configuration methods, including functions selection through MOT, diagram drawing
of LCD display, communication protocol selection and setting, user authority management,
configuration of binary inputs and outputs, programmable logic, etc.
4 Measurement
Measurement analogue input channels configuration methods which are specified for different
application scenarios.
5 Protection
Protection functions configuration methods, including function activation method and specific
configuration method of each protection element.
PCS-978S Transformer Relay
VII
Date: January 15, 2020
Preface
6 Control
Control function configuration methods, including switchgear control, direct control, synchronism
check, voltage selection and tap changer control.
7 Supervision
Supervision functions configuration functions, including circuit supervision of VT.
Appendix A Glossary
List of abbreviations adopted in this manual.
Document Revision History
PN: ZL_PCS-978S_X_Application Manual_EN_Overseas General_X
Current version: R1.00
Corresponding Version
Date
Document
Software
R1.00
R1.20
2020-01-15
Description of change
Form the original manual.
PCS-978S Transformer Relay
VIII
Date: January 15, 2020
1 Functions and Application
1 Functions and Application
1
Table of Contents
1.1 Functions ......................................................................................................... 1-1
1.1.1 Protection Function .............................................................................................................1-1
1.1.2 Control Functions ...............................................................................................................1-3
1.1.3 Measurement and Metering Functions ...............................................................................1-3
1.1.4 Supervision Functions ........................................................................................................1-3
1.1.5 Communication Functions ..................................................................................................1-4
1.1.6 User Interfaces ...................................................................................................................1-4
1.1.7 Additional Functions............................................................................................................1-4
1.2 Typical Applications ........................................................................................ 1-5
1.2.1 Two-Winding Transformer ...................................................................................................1-5
1.2.2 Three-Winding Transformer ................................................................................................1-6
1.2.3 Auto-Transformer ................................................................................................................1-7
List of Figures
Figure 1.2-3 Typical application of a 2-winding transformer .............................................. 1-5
Figure 1.2-3 Typical application of a 3-winding transformer .............................................. 1-6
Figure 1.2-3 Typical application of a auto-transformer ....................................................... 1-7
PCS-978S Transformer Relay
1-a
Date: January 15, 2020
1 Functions and Application
1
PCS-978S Transformer Relay
1-b
Date: January 15, 2020
1 Functions and Application
1.1 Functions
PCS-978S transformer relay provides fast and selective protection, control and monitoring for twowinding transformers, three-winding transformers and auto-transformers in any voltage level. All
the important auxiliary functions that are necessary today for safe network operation are integrated
in the IED, and the modular structure permits the device always to be adapted flexibly to the
individual requirements.
The PCS-978S is applicable not only to conventional substations, but also to digital substations. It
supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high
real-time performance. The process level network supports peer-to-peer (P2P) mode and
networking mode, including single network mode and dual network mode. The station level network
could also receive and send MMS messages (such as interlocking signals) or process level
GOOSE messages (such as trip signals).
1.1.1 Protection Function
ANSI
Protection Functions
Remark
Biased differential protection with three slopes
Biased DPFC differential protection
Unrestrained instantaneous differential protection
Optional
inrush
current
distinguished
principles:
harmonic criterion or waveform distortion
87T
Transformer differential protection
Optional harmonic blocking modes: self-adaptive
1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode
Overexcitation detection: fifth harmonic or third
harmonic criterion
64REF
Restricted earth-fault protection
Optional transfer methods: △→Y or Y→△
Independent CT saturation criterion
Differential CT circuit failure supervision
Optional direction element
CT transient characteristic detection
CT saturation detection based on 2nd and 3rd
harmonics
87W
Winding differential protection
CT transient characteristic detection
CT saturation detection based on 2nd and 3rd
harmonics
Two stages definite-time overexcitation protection
Stage 1 of definite-time overexcitation protection for trip
purpose
24
Overexcitation protection
Stage 2 of definite-time overexcitation protection for
alarm purpose
One stage inverse-time overexcitation protection for
both alarm purpose and trip purpose
PCS-978S Transformer Relay
1-1
Date: January 15, 2020
1
1 Functions and Application
1
67P
50/51P
67G
50/51G
Phase overcurrent protection
6 stages with independent logic by default
Voltage control element for each stage
Optional direction element for each stage
Optional definite-time characteristic and inverse-time
characteristic for each stage
Trip purpose or alarm purpose for each stage
Harmonic control element for each stage
4 stages with independent logic by default
Optional direction element for each stage
Optional
measured
zero-sequence
current
or
calculated zero-sequence current
Earth fault protection
Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each
stage
67Q
50/51Q
Negative-sequence
overcurrent
protection
Harmonic control element for each stage
Up to 2 stages with independent logic
Optional direction element for each stage
Optional definite-time characteristic and inverse-time
characteristic for each stage
49
50BF
Thermal overload protection
Two stages thermal overload protection, and one stage
for alarm purpose and the other stage for trip purpose
Up to 6 circuit breakers are supported
Phase-segregated re-trip and three-phases re-trip
Optional current criterion (phase overcurrent element,
Breaker failure protection
zero-sequence
overcurrent
element,
negative-
sequence overcurrent element)
Optional circuit breaker position check
Two time delays
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time
characteristic for each stage
59P
Overvoltage protection
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Selectable trip purpose or alarm purpose for each
stage
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time
characteristic for each stage
27P
Undervoltage protection
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Blocked by instantaneous VT circuit failure
Selectable trip purpose or alarm purpose for each
stage
PCS-978S Transformer Relay
1-2
Date: January 15, 2020
1 Functions and Application
Up to 2 stages with independent logic
Optional
measured
zero-sequence
voltage
or
calculated zero-sequence voltage
59G
Residual overvoltage protection
Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each
stage
81O
Overfrequency protection
81U
Underfrequency protection
Up to 2 stages with independent logic
Voltage control element
Up to 4 stages with independent logic
Voltage control element
1.1.2 Control Functions
Switchgear control
Double point status synthesis
Remote/Local control mode switch
Interlocking logic for control
Direct control
Closing synchronism check with voltage selection
Switchgear trip counter
Tap position indicator and control
1.1.3 Measurement and Metering Functions
U, I, P, Q, S, Cos, f
Positive, negative and zero sequences
Max.15th harmonics
DC analog inputs (0~±20mA, 0~±10Vdc, RTD: Pt10, Pt100, Pt1000, Cu50, Cu100)
1.1.4 Supervision Functions
CT circuit failure supervision (CTS)
VT circuit failure supervision (VTS)
Self diagnostic
Powerful faults recording (max. buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
Disturbance recorder including 64 disturbance records with waveforms (The file format of
PCS-978S Transformer Relay
1-3
Date: January 15, 2020
1
1 Functions and Application
disturbance recorder is compatible with international COMTRADE file.)
1
Single line diagram representation in display
1.1.5 Communication Functions
Support of various protocols
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server,
IEC 61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol,
IEC 62439 HSR Ring Redundancy Protocol.
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to two 100Base-FX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL serial port for clock synchronization
Two RJ45 debugging ports (front and rear)
1.1.6 User Interfaces
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment
Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-232 or RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
1.1.7 Additional Functions
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
PCS-978S Transformer Relay
1-4
Date: January 15, 2020
1 Functions and Application
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,
Modbus protocol and DNP3.0 protocol
Cyber security
NERC CIP
IEC 62351
IEC 62443
IEEE 1686
1.2 Typical Applications
There are three kinds of typical application scenarios, as
Two-winding transformer, single circuit breaker arrangement
Three-winding transformer, single circuit breaker arrangement
Auto-winding transformer, singe circuit breaker arrangement
1.2.1 Two-Winding Transformer
HVS
1VT
52
*
3CT
3VT
51P
Alm
87T
64
REF
67G
50BF
67P
50/
51P
*
MR
84
CSWI
25
1CT
50/
51G
67Q
50/
51Q
59P
59G
27P
24
81O
81U
3CT
*
52
3VT
LVS
Figure 1.2-1 Typical application of a 2-winding transformer
This configuration is used in the application scenario of a 2-winding transformer with a single circuit
breaker on both sides. The three-phase VT, three-phase CT and the neutral-point CT are used for
PCS-978S Transformer Relay
1-5
Date: January 15, 2020
1
1 Functions and Application
protection functions calculation and single-phase busbar VT is used for synchronism check.
1
The current differential protection is as the main protection, it provides fast and secure tripping for
internal faults. Restricted earth fault protection, overexctiation protection, phase overcurrent
protection, earth fault protection, phase overvoltage protection, residual overvoltage protection and
breaker failure protection are configured as backup protection. Negative-sequence overcurrent
protection, phase undervoltage protection and frequency protection are also optional for some
specific requirements.
High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the
relevant disconnector switches and earthing switches and the tap position could be controlled by
the device. Supervision functions of analog input channels, binary input channels, CT secondary
circuits, VT secondary circuits, switchgear tripping counter, etc. are equipped for the operating
reliability and safety of the device. Moreover, measurement function including U, I, P, Q, S, Cos, f
are available in local HMI and remote representation.
1.2.2 Three-Winding Transformer
HVS
1VT
52
3CT
*
51P
Alm
87T
64
REF
67G
50BF
67P
3VT
50/
51P
MVS
*
MR
52
84
25
CSWI
1CT
*
50/
51G
67Q
3CT
50/
51Q
3VT
59P
59G
27P
24
81O
81U
3CT
*
52
3VT
LVS
Figure 1.2-2 Typical application of a 3-winding transformer
This configuration is used in the application scenario of a 3-winding transformer with a single circuit
breaker on both sides. The three-phase VT, three-phase CT and the neutral-point CT are used for
protection functions calculation and single-phase busbar VT is used for synchronism check.
The current differential protection is as the main protection, it provides fast and secure tripping for
internal faults. Restricted earth fault protection, overexctiation protection, phase overcurrent
protection, earth fault protection, phase overvoltage protection, residual overvoltage protection and
breaker failure protection are configured as backup protection. Negative-sequence overcurrent
PCS-978S Transformer Relay
1-6
Date: January 15, 2020
1 Functions and Application
protection, phase undervoltage protection and frequency protection are also optional for some
specific requirements.
High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the
relevant disconnector switches and earthing switches and the tap position could be controlled by
the device. Supervision functions of analog input channels, binary input channels, CT secondary
circuits, VT secondary circuits, switchgear tripping counter, etc. are equipped for the operating
reliability and safety of the device. Moreover, measurement function including U, I, P, Q, S, Cos, f
are available in local HMI and remote representation.
1.2.3 Auto-Transformer
HVS
1VT
52
*
3CT
87T
51P
Alm
87W
64
REF
67G
50BF
67P
3VT
MVS
52
50/
51P
*
1CT
*
*
*
MR
3CT
84
25
CSWI
1CT
1CT
50/
51G
67Q
*
50/
51Q
1CT
3VTs
59P
59G
27P
24
81O
81U
3CT
*
52
3VT
LVS
Figure 1.2-3 Typical application of a auto-transformer
This configuration is used in the application scenario of an auto-winding transformer with a single
circuit breaker on both sides. The three-phase VT, three-phase CT and the neutral-point CT are
used for protection functions calculation and single-phase busbar VT is used for synchronism check.
The current differential protection is as the main protection, it provides fast and secure tripping for
internal faults. Winding differential, restricted earth fault protection, overexctiation protection, phase
overcurrent protection, earth fault protection, phase overvoltage protection, residual overvoltage
protection and breaker failure protection are configured as backup protection. Negative-sequence
overcurrent protection, phase undervoltage protection and frequency protection are also optional
for some specific requirements.
High voltage circuit breaker synchronism check function is equipped, the circuit breaker, the
relevant disconnector switches and earthing switches and the tap position could be controlled by
the device. Supervision functions of analog input channels, binary input channels, CT secondary
PCS-978S Transformer Relay
1-7
Date: January 15, 2020
1
1 Functions and Application
1
circuits, VT secondary circuits, switchgear tripping counter, etc. are equipped for the operating
reliability and safety of the device. Moreover, measurement function including U, I, P, Q, S, Cos, f
are available in local HMI and remote representation.
PCS-978S Transformer Relay
1-8
Date: January 15, 2020
2 Connecting to the Configuration Tool
2 Connecting to the Configuration Tool
Table of Contents
2.1 Brief Introduction of PCS-Studio ................................................................... 2-1
2.2 Establishing Connection................................................................................. 2-1
2.2.1 Via Front RJ45 Port ............................................................................................................2-1
2.2.2 Via Ethernet Interface on CPU Module ...............................................................................2-2
2.3 Validation of Configuration ............................................................................. 2-2
PCS-978S Transformer Relay
2-a
Date: January 15, 2020
2
2 Connecting to the Configuration Tool
2.1 Brief Introduction of PCS-Studio
The PCS-Studio is the configuration and debugging software of PCS S series devices. It provides
the following configuration functions:
Device information configuration
Viewing and editing project name, user configuration file version, file modification time, etc.
Global function configuration
MOT selection, system configuration, function object activation/deactivation, etc.
Human-machine interface configuration
Single Line Diagram (SLD) drawing for LCD display, definition of LED indicators, shortcut keys,
user-level waveform recording, etc.
Communication configuration
Support of multiple communication protocols, including IEC 61850 (Edition 1 & Edition 2), IEC
60870-5-103, DNP3.0, Modbus, etc.
IO signal configuration
Binary inputs, binary outputs, AC and DC analogue inputs, etc.
User-defined logic programming
Complete and rich symbol library for user-defined logic programming.
Parameter setting
Setting, import and export of device parameters.
Online debugging
Debugging through visual pages and virtual LCD screen.
2.2 Establishing Connection
On the front panel of the device, there is a multiplex RJ45 port which is the debugging port for
connection to a portable computer. Meanwhile, the CPU plug-in module is equipped with several
Ethernet interfaces which may also be used to communicate with debugging computer.
2.2.1 Via Front RJ45 Port
By default, the IP address of front debugging port is “100.100.100.100” with the subnet mask
“255.255.255.000”. If this address conflicts with any other Ethernet port on CPU module. Through
the device front human-machine interface, please call up the modification menu by pressing the
key combination "◄ + ◄ - ENT" under the default LCD display screen and change the default
address.
PCS-978S Transformer Relay
2-1
Date: January 15, 2020
2