Copyright © 2020 NR. All rights reserved.
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface
About This Manual
The manual describes the protection, control, measurement and supervision functions with the
information of relevant hardware for PCS-978S Transformer Relay.
Safety Information
This manual is not a complete index of all safety measures required for operation of the
equipment (module or device). However, it comprises important information that must be followed
for personal safety, as well as to avoid material damage. Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage.
Indicates that property damage can result if the measures specified are
not taken.
Important information about the device, product handling or a certain
section of the documentation which must be given particular attention.
Instructions and Warnings
The following hazard statements apply to this device.
Disconnect or de-energize all external connections BEFORE opening this
device. Contact with hazardous voltages and currents inside this device
can cause electrical shock resulting in injury or death.
PCS-978S Transformer Relay
I
Date: 2020-03-05
Preface
Contact with instrument terminals can cause electrical shock that can
result in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
This device is shipped with default passwords. Default passwords should
be changed to private passwords at installation. Failure to change each
default password to a private password may allow unauthorized access.
NR shall not be responsible for any damage resulting from unauthorized
access.
DO NOT look into the fiber (laser) ports/connectors.
DO NOT look into the end of an optical cable connected to an optical
output.
DO NOT perform any procedures or adjustments that this instruction
manual does not describe.
During installation, maintenance, or testing of the optical ports, ONLY use
the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
PCS-978S Transformer Relay
II
Date: 2020-03-05
Preface
are NOT user serviceable. Return units to NR for repair or replacement.
Equipment components are SENSITIVE to electrostatic discharge (ESD).
Undetectable permanent damage can result if you do not use proper ESD
procedures. Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment. If your facility is not
equipped to work with these components, contact NR about returning this
device and related NR equipment for service.
Insufficiently rated insulation can deteriorate under abnormal operating
conditions and cause equipment damage. For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions.
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables. Please
use the wiring method recommended in the manual for communication
terminals.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage
can result otherwise.
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure.
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
PCS-978S Transformer Relay
III
Date: 2020-03-05
Preface
Glossary also contains definitions of important terms.
Menu path is connected with the arrow "→" and bold.
For example: the access path of protection settings is: MainMenu→Settings→Protection
Settings
Settings not in the table should be placed in brackets.
For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
For example: press the button "ENT".
Symbols
AND Gate
&
&
&
>=1
>=1
OR Gate
>=1
Comparator
Binary signal Input
BI
Signal input
SIG
xxx
xxx
Setting input
PCS-978S Transformer Relay
IV
Date: 2020-03-05
Preface
SET
Enable input
EN
xxx
xxx
Timer
Optional definite-time or inverse-time characteristic
Timer
t
t
Timer
Fixed delay pickup (10ms), fixed delay dropout (2ms)
10ms
2ms
Timer
Settable delay pickup, fixed delay dropout
[Tset1]
0ms
Timer
Fixed delay pickup, settable delay dropout
0ms
[Tset2]
Timer
Settable delay pickup, settable delay dropout
[Tset1]
[Tset2]
Generator
G
Transformer
PCS-978S Transformer Relay
V
Date: 2020-03-05
Preface
Reactor
Motor
M
Capacitor
C
Busbar
Circuit breaker
52
Current transformer
3CT
*
Voltage transformer
3VT
Disconnector
PCS-978S Transformer Relay
VI
Date: 2020-03-05
Preface
Earth
Three-phase Corresponding Relationship
Basic
A, B, C
L1, L2, L3
R, Y, B
AN, BN, CN
L1N, L2N, L3N
RN,YN, BN
ABC
L123
RYB
U (voltage)
V
U
Example
Ia, Ib, Ic, I0
IL1, IL2, IL3, IN
IR, IY, IB, IN
Ua, Ub, Uc
VL1, VL2, VL3
UR, UY, UB
Uab, Ubc, Uca
VL12, VL23, VL31
URY, UYB, UBR
U0, U1, U2
VN, V1, V2
UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This manual is a comprehensive work covering the theories of protection, control, supervision,
measurement, etc. and the structure & technical data of relevant hardware. Read the sections that
pertain to your application to gain valuable information about using the PCS-978S. To concentrate
on the target sections of this manual as your job needs and responsibilities dictate. An overview of
each manual section and section topics follows.
1 Introduction
Introduces PCS-978S features, summarizes functions and applications of the device.
2 Technical Data
Lists device specifications, type tests, and ratings.
3 Protection Functions
Describes the function of various protection elements, gives detailed specifics on protection
scheme logic, and provides the relevant logic diagrams.
PCS-978S Transformer Relay
VII
Date: 2020-03-05
Preface
4 Control Functions
Describes the logic for the control of disconnectors and circuit breakers.
5 Measurement
Provides information on viewing fundamental and rms metering quantities for voltages and
currents, as well as power and energy metering data.
6 Supervision
Describes self-supervision technique to help diagnose potential difficulties should these occur and
includes the list of status notification messages. Provides a troubleshooting chart for common
device operation problems.
7 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating
with the device, switching active setting group, checking relay status, reading event reports and
SER (Sequential Events Recorder) records.
8 Hardware
Describes the hardware of the PCS series device family and provides general information on the
product structure and the modules technical data.
9 Settings
Provides a list of all settings and their ranges, unit, steps, defaults. The organization of the
settings is similar to the settings organization in the device and in the PCS-Studio software.
Appendix A Glossary
Describes the abbreviations adopted in this manual.
Document Revision History
PN: ZL_PCS-978S_X_Technical Manual_EN_Overseas General_X
Current version: R1.20
Corresponding Version
Date
Document
Software
R1.00
R1.00
2019-01-31
Description of change
Form the original manual.
PCS-978S Transformer Relay
VIII
Date: 2020-03-05
Preface
R1.10
R1.20
2019-12-09
Modification of voltage selection diagram.
Update of switchgear control function.
Update of VT circuit supervision.
Update of technical data.
Add switchgear position verification
Add the description about digital substation application
Add the description about digital interface
Add technical data of GOOSE and SV
Add certifications of IEC 61850, DNP, PRP, HSR, IEEE
1588
Add alarm signals of GOOSE and SV
Add NET-DSP plug-in module (NR6112B)
Add SV communication settings
Add GOOSE send links and receiving links
Add SV links
Add reactor protection application scenario
Update of technical data
Add reactor current differential protection function 87R
and inter-turn fault protection function 21IT
R1.20
R1.30
2020-03-05
Add binary input and binary output module NR6661
Add mechanical relay input and output module NR6662
Replace the NET-DSP module NR6112B with NR6113
Deletion of the DC analogue input module NR6631B
PCS-978S Transformer Relay
IX
Date: 2020-03-05
1 Introduction
1 Introduction
1
Table of Contents
1.1 Application ....................................................................................................... 1-1
1.2 Protection Functions ....................................................................................... 1-4
1.3 Control Functions ............................................................................................ 1-6
1.4 Measurement and Metering Functions .......................................................... 1-6
1.5 Supervision Functions .................................................................................... 1-7
1.6 Communication Functions ............................................................................. 1-7
1.7 User Interfaces ................................................................................................. 1-7
1.8 Additional Functions ....................................................................................... 1-8
1.9 Features ............................................................................................................ 1-8
List of Figures
Figure 1.1-1 Two-winding transformer .................................................................................... 1-1
Figure 1.1-2 Three-winding transformer ................................................................................. 1-1
Figure 1.1-3 Auto-transformer with two sides ........................................................................ 1-2
Figure 1.1-4 Auto-transformer with three sides ..................................................................... 1-2
Figure 1.1-5 Typical application of an auto-transformer ....................................................... 1-3
Figure 1.1-6 Typical application of a shunt reactor ............................................................... 1-3
PCS-978S Transformer Relay
1-a
Date: 2020-03-05
1 Introduction
1
PCS-978S Transformer Relay
1-b
Date: 2020-03-05
1 Introduction
1.1 Application
PCS-978S transformer relay provides fast and selective protection, control and monitoring for
two-winding transformers, three-winding transformers, auto-transformers, as well as shunt
reactors. The full transformer protections are configurable by user. Ancillary functions of fault
diagnostic, disturbance records, event records and communication function are integrated in the
device.
PCS-978S is adaptive to the following 2/3-windings transformers or auto-transformer.
Figure 1.1-1 Two-winding transformer
Figure 1.1-2 Three-winding transformer
PCS-978S Transformer Relay
1-1
Date: 2020-03-05
1
1 Introduction
1
Figure 1.1-3 Auto-transformer with two sides
Figure 1.1-4 Auto-transformer with three sides
The function diagrams for protecting an auto-transformer and a reactor are respectively shown
below.
PCS-978S Transformer Relay
1-2
Date: 2020-03-05
1 Introduction
HVS
3 VT
52
3 CT
1
*
87T
MVS
87W
64
REF
51P
Alm
50BF
67G
*
*
*
3 CT
50/
51G
1 CT
1 CT
67P
50/
51P
*
1 CT
52
49
67Q
*
50/
51Q
1 CT
3 VT
59P
59G
27P
24
81U
81O
3 CT
*
52
3 VT
LVS
Figure 1.1-5 Typical application of an auto-transformer
Bus1
52
Line
1 VT
52
50/
51P
3 CT
21IT
49
87R
*
50/
51G
Shunt reactor
3 CT
52
*
Bus2
1 CT
*
Neutral earthing reactor
Figure 1.1-6 Typical application of a shunt reactor
PCS-978S Transformer Relay
1-3
Date: 2020-03-05
1 Introduction
1
The PCS-978S is applicable not only to conventional substations, but also to digital substations. It
supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network interfaces with high
real-time performance. The process level network supports peer-to-peer (P2P) mode and
networking mode, including single network mode and dual network mode. The station level
network could also receive and send MMS messages (such as interlocking signals) or process
level GOOSE messages (such as trip signals).
1.2 Protection Functions
ANSI
Protection Functions
Remark
Biased differential protection with three slopes
Biased DPFC differential protection
Unrestrained instantaneous differential protection
Optional
inrush
current
distinguished
principles:
harmonic criterion or waveform distortion
87T
Transformer differential protection
Optional harmonic blocking modes: self-adaptive
1Pblk1P mode, 2PBlk3P mode, 1Pblk3P mode
Overexcitation detection: fifth harmonic or third
harmonic criterion
64REF
Restricted earth-fault protection
Optional transfer methods: △→Y or Y→△
Independent CT saturation criterion
Differential CT circuit failure supervision
Optional direction element
CT transient characteristic difference detection
CT saturation detection based on 2nd and 3rd
harmonics
87W
Winding differential protection
CT transient characteristic difference detection
CT saturation detection based on 2nd and 3rd
harmonics
87R
21IT
Reactor differential protection
Biased DPFC differential protection
Biased current differential protection
Independent CT saturation criterion
Harmonic blocking criterion
Differential CT circuit failure supervision
Zero-sequence
Inter-turn fault protection
power
directional
element
and
zero-sequence impedance element
CT and VT circuit failure blocking
Two stages definite-time overexcitation protection
Stage 1 of definite-time overexcitation protection for
trip purpose
24
Overexcitation protection
Stage 2 of definite-time overexcitation protection for
alarm purpose
One stage inverse-time overexcitation protection for
both alarm purpose and trip purpose
PCS-978S Transformer Relay
1-4
Date: 2020-03-05
1 Introduction
ANSI
67P
50/51P
67G
50/51G
Protection Functions
Phase overcurrent protection
Remark
6 stages with independent logic by default
Voltage control element for each stage
Optional direction element for each stage
Optional definite-time characteristic and inverse-time
1
characteristic for each stage
Trip purpose or alarm purpose for each stage
Harmonic control element for each stage
4 stages with independent logic by default
Optional direction element for each stage
Optional
measured
zero-sequence
current
or
calculated zero-sequence current
Earth fault protection
Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each
stage
67Q
50/51Q
Negative-sequence
overcurrent
protection
Harmonic control element for each stage
Up to 2 stages with independent logic
Optional direction element for each stage
Optional definite-time characteristic and inverse-time
characteristic for each stage
49
Thermal overload protection
Two stages thermal overload protection, and one
stage for alarm purpose and the other stage for trip
purpose
50BF
Up to 6 circuit breakers are supported
Phase-segregated re-trip and three-phases re-trip
Optional current criterion (phase overcurrent element,
Breaker failure protection
zero-sequence
overcurrent
element,
negative-sequence overcurrent element)
Optional circuit breaker position check
Two time delays
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time
characteristic for each stage
59P
Overvoltage protection
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Selectable trip purpose or alarm purpose for each
stage
PCS-978S Transformer Relay
1-5
Date: 2020-03-05
1 Introduction
ANSI
Protection Functions
1
Remark
Up to 2 stages with independent logic
Optional definite-time characteristic and inverse-time
characteristic for each stage
27P
Undervoltage protection
Optional phase voltage or phase-to-phase voltage
Optional “1-out-of-3” logic or “3-out-of-3” logic
Blocked by instantaneous VT circuit failure
Selectable trip purpose or alarm purpose for each
stage
Up to 2 stages with independent logic
Optional
measured
zero-sequence
voltage
or
calculated zero-sequence voltage
59G
Residual overvoltage protection
Optional definite-time characteristic and inverse-time
characteristic for each stage
Selectable trip purpose or alarm purpose for each
stage
81O
Overfrequency protection
81U
Underfrequency protection
Up to 2 stages with independent logic
Voltage control element
Up to 4 stages with independent logic
Voltage control element
1.3 Control Functions
Switchgear control
Double point status synthesis
Remote/Local control mode switch
Interlocking logic for control
Direct control
Closing synchronism check with voltage selection
Switchgear trip counter
Tap position indicator and control
1.4 Measurement and Metering Functions
U, I, P, Q, S, Cos, f
Positive, negative and zero sequences
Max.15th harmonics
DC analog inputs (0~±20mA, 0~±10Vdc)
PCS-978S Transformer Relay
1-6
Date: 2020-03-05
1 Introduction
1.5 Supervision Functions
CT circuit failure supervision (CTS)
VT circuit failure supervision (VTS)
Self diagnostic
Powerful faults recording (max. buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Single line diagram representation in display
1
1.6 Communication Functions
Support of various protocols
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server, IEC
61850-8-1 GOOSE, IEC 61850-9-2LE SV, IEC 62439 Parallel Redundancy Protocol, IEC
62439 HSR Ring Redundancy Protocol.
Up to four 10Base-T/100Base-TX copper Ethernet ports
Up to fourteen 100Base-FX optical Ethernet ports
Up to four 1000Base-SX optical Ethernet ports
Two RS-485 serial ports for communication or printer
One RS-485/TTL serial port for clock synchronization
Two RJ45 debugging ports (front and rear)
1.7 User Interfaces
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment
Push buttons for open/close, switch for selection between local and remote control, and user's
login and logout authority management
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-232 or RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
PCS-978S Transformer Relay
1-7
Date: 2020-03-05
1 Introduction
1.8 Additional Functions
1
User programmable logic
Switching system phase sequences function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE 1588: Clock message based on IEEE 1588 via optical fibre interface
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus
protocol and DNP3.0 protocol
Cyber security
NERC CIP
IEC 62351
IEC 62443
IEEE 1686
1.9 Features
High degree of functional integration and flexible configuration modes, transformer main
protection and back-up protection can be integrated in one device, or be separated in two
devices.
Up to 36 analog inputs can be provided and configured flexibly.
The tripping output contacts can be configured by tripping matrix, which is flexible, convenient
and suitable to any mode of tripping.
The relay supports at most 6 branches differential protection. The transformer angle can be
adjusted flexibly, and any transformer angle compensation mode is supported and any side
can be chosen as the reference side of differential protection.
Reliable differential CT circuit failure supervision. The relay can detect multi-phase CT
wire-break, multi-side CT wire-break, short-circuit, and other complex situation. The
corresponding logic setting can be used to select blocking differential protection or not, in case
of CT circuit failure.
Multiple inrush current blocking options are provided. Self-adaptive inrush current blocking
PCS-978S Transformer Relay
1-8
Date: 2020-03-05
1 Introduction
criterion can ensure the relay fast operation for transformer energized on to a slight fault,
meanwhile it will avoid the unwanted operation in the case of the energization inrush current
caused by energizing transformer with no load, the recovery inrush current caused by cutting
off the transformer external fault, and the sympathetic inrush current.
Biased DPFC differential protection is regardless of load current and is sensitive to small
internal fault current within the transformer. Its anti CT saturation performance is also strong.
PCS-978S Transformer Relay
1-9
Date: 2020-03-05
1