PCS 9611s x application manual EN overseas general x r1 00

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (6.17 MB, 223 trang )



Copyright © 2019 NR. All rights reserved.
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.



Preface

Preface
About This Manual
This manual describes the configuration scheme in multiple application scenarios for PCS-9611S


Feeder Relay, including how to connect the device to a computer and to configure functions, such
as protection, control, measurement and supervision in using of configuration tool.
To start using this manual for application configuration, user should know the basic operations of
the configuration tool PCS-Studio.

Safety Information
This manual is not a complete index of all safety measures required for operation of the
equipment (module or device). However, it comprises important information that must be followed
for personal safety, as well as to avoid material damage. Information is highlighted and illustrated
as follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage.
Indicates that property damage can result if the measures specified are
not taken.
Important information about the device, product handling or a certain
section of the documentation which must be given particular attention.

Instructions and Warnings
The following hazard statements apply to this device.

Disconnect or de-energize all external connections BEFORE opening this
device. Contact with hazardous voltages and currents inside this device
can cause electrical shock resulting in injury or death.
PCS-9611S Feeder Relay
Date: 2019-12-29


I


Preface

Contact with instrument terminals can cause electrical shock that can
result in injury or death.

Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.

Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.

This device is shipped with default passwords. Default passwords should
be changed to private passwords at installation. Failure to change each
default password to a private password may allow unauthorized access.
NR shall not be responsible for any damage resulting from unauthorized
access.

DO NOT look into the fiber (laser) ports/connectors.

DO NOT look into the end of an optical cable connected to an optical
output.

DO NOT perform any procedures or adjustments that this instruction
manual does not describe.

During installation, maintenance, or testing of the optical ports, ONLY use

the test equipment qualified for Class 1 laser products!

II

PCS-9611S Feeder Relay
Date: 2019-12-29


Preface

Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable. Return units to NR for repair or replacement.

Equipment components are SENSITIVE to electrostatic discharge (ESD).
Undetectable permanent damage can result if you do not use proper ESD
procedures. Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment. If your facility is not
equipped to work with these components, contact NR about returning this
device and related NR equipment for service.

Insufficiently rated insulation can deteriorate under abnormal operating
conditions and cause equipment damage. For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions.

SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables. Please
use the wiring method recommended in the manual for communication
terminals.


DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage
can result otherwise.

Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure.

The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.

Document Conventions
PCS-9611S Feeder Relay
Date: 2019-12-29

III


Preface



The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.



Menu path is connected with the arrow "→" and bold.
For example: the access path of protection settings is: MainMenu→Settings→Protection
Settings




Settings not in the table should be placed in brackets.
For example: the system setting [Opt_SysFreq]



Cross-references are presented in italics.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1



Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
For example: press the button "ENT".

Symbols


AND Gate

&



&

&


>=1

>=1

OR Gate

>=1



Comparator



Signal input
SIG



Setting input
SET


IV

xxx

xxx

Enable input

PCS-9611S Feeder Relay
Date: 2019-12-29


Preface
EN



xxx

Timer
Optional definite-time or inverse-time characteristics
Timer
t
t



Timer
Fixed delay pickup (10ms), fixed delay dropout (2ms)
10ms



2ms

Timer
Settable delay pickup, fixed delay dropout
[Tset1]




0ms

Timer
Fixed delay pickup, settable delay dropout
0ms



[Tset2]

Timer
Settable delay pickup, settable delay dropout
[Tset1]



[Tset2]

Generator

G



Transformer




Reactor

PCS-9611S Feeder Relay
Date: 2019-12-29

V


Preface



Motor

M


Capacitor

C


Busbar



Circuit breaker
52




Current transformer
3CT

*



Voltage transformer

3VT



Disconnector



Earth

Three-phase Corresponding Relationship
VI

PCS-9611S Feeder Relay
Date: 2019-12-29


Preface
Basic

A, B, C

L1, L2, L3

R, Y, B

AN, BN, CN

L1N, L2N, L3N

RN,YN, BN

ABC

L123

RYB

U (voltage)

V

U
Example

Ia, Ib, Ic, I0

IL1, IL2, IL3, IN

IR, IY, IB, IN


Ua, Ub, Uc

VL1, VL2, VL3

UR, UY, UB

Uab, Ubc, Uca

VL12, VL23, VL31

URY, UYB, UBR

U0, U1, U2

VN, V1, V2

UN, U1, U2

Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.

Document Structure
This manual is a comprehensive work covering all aspects of relay application and use. Read the
sections that pertain to your application to gain valuable information about using the PCS-9611S.
To concentrate on the target sections of this manual as your job needs and responsibilities dictate.
An overview of each manual section and section topics follows.

1 Functions and Application

Introduces summarizes functions and typical applications of the device.

2 Configuration Tool
Introduces the communication interface of the device and the corresponding software and
hardware settings by which PCS-Studio connects with the device.

3 Basic Function Configuration
Introduces how to configure the basic function of the device, such as, enabling/disabling functions,
setting HMI (human machine interface), setting communication protocol and network structure,
binary inputs, binary outputs, user-defined logic, authority management, etc.

4 Protection Function Configuration
Introduces how to configure protection functions, including enabling/disabling functions,
configuration methods and corresponding settings.

5 Control Function Configuration
Introduces the configuration method of control functions, such as, switchgear control,
synchronism check and voltage selection.

6 Measurement Function Configuration
PCS-9611S Feeder Relay
Date: 2019-12-29

VII


Preface

Introduces the configuration method of the sampling channel for different typical application
scenarios.


7 Supervision Function Configuration
Introduces the configuration method of supervision functions, such as, secondary circuit
supervision, tripping statistic, etc.

Appendix A Glossary
Describes the abbreviations adopted in this manual.

Document Revision History
PN: ZL_PCS-9611S_X_Application Manual_EN_Overseas General_X
Current version: R1.00
Corresponding Version
Date
Document

Software

R1.00

R1.13

VIII

2019-12-29

Description of change



Form the original manual.


PCS-9611S Feeder Relay
Date: 2019-12-29


1 Functions and Application

1 Functions and Application

1

Table of Contents
1.1 Functions ......................................................................................................... 1-1
1.2 Typical Application .......................................................................................... 1-7
1.2.1 Feeder Protection Application .............................................................................................. 1-7
1.2.2 Transformer Backup Protection Application ......................................................................... 1-8
1.2.3 Double-star Connection Capacitor Bank Protection Application.......................................... 1-9
1.2.4 Single-star Connection Capacitor Bank Protection Application ......................................... 1-10

List of Figures
Figure 1.1-1 Functional diagram of PCS-9611S ....................................................................... 1-1
Figure 1.2-1 Feeder protection typical application .................................................................. 1-7
Figure 1.2-2 Transformer backup protection typical application ........................................... 1-8
Figure 1.2-3 Double-star connection capacitor bank protection typical application .......... 1-9
Figure 1.2-4 Single-star connection capacitor bank protection typical application .......... 1-10

PCS-9611S Feeder Relay
Date: 2019-12-29

1-a



1 Functions and Application

1

1-b

PCS-9611S Feeder Relay
Date: 2019-12-29


1 Functions and Application

1.1 Functions
The PCS-9611S relay is a protection, control and monitoring unit for various primary equipment
(such as overhead line, underground cable and transformer etc.) on solidly grounded, impedance
grounded, Peterson coil grounded and ungrounded system. This relay is suitable for wall surface
mounted indoors or outdoors or flush mounted into a control panel.
The functional overview of this relay is shown as below.
Busbar
3VTs

52

27P

59P

59Q


VTS

59G

1VT

67P

*

*

81U

81O

81R

50BF

51Q

46BC

25

79

32R


3CTs

50P

51P

50G

51G

49

CTS

50L/NL

1CT

*

SOTF

67G

37

1CT

51SEF


60/59

60/50

67SEF

FR

1VT

Load
Figure 1.1-1 Functional diagram of PCS-9611S

The PCS-9611S is widely adopted not only for conventional substations, but also for digital
substations. It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network
interfaces with high real-time performance. The process level network supports peer-to-peer (P2P)
mode and networking mode, including single network mode and dual network mode. The station
level network can also receive and send MMS messages (such as interlocking signals) or process
level GOOSE messages (such as circuit breakers or disconnectors positions and trip signals).
1

Protection functions

PCS-9611S Feeder Relay
Date: 2019-12-29

1-1

1



1 Functions and Application
ANSI

Protection Functions

Remark

1
67P
50/51P



Up to 6 stages with independent logic



Voltage control element for each stage



Optional direction element for each stage, including
forward direction, reverse direction and non-direction

Phase overcurrent protection




Optional definite-time characteristic and inverse-time
characteristic for each stage



Selectable trip purpose or alarm purpose for each
stage



Harmonic control element for each stage



Up to 6 stages with independent logic



Optional direction element for each stage, including
forward direction, reverse direction and non-direction


67G
50/51G

Optional

measured

zero-sequence


current

or

calculated zero-sequence current

Earth fault protection



Optional definite-time characteristic and inverse-time
characteristic for each stage



Selectable trip purpose or alarm purpose for each
stage

A.67G
A.50/51G

Another group of earth fault



Harmonic control element for each stage




Only measured zero-sequence current is supported



Up to 6 stages with independent logic



Optional definite-time characteristic and inverse-time

overcurrent protection

characteristic for each stage


Selectable trip purpose or alarm purpose for each
stage

50/51Q

Negative-sequence
overcurrent protection



Up to 2 stages with independent logic



Optional direction element for each stage, including

forward direction, reverse direction and non-direction



Optional definite-time characteristic and inverse-time
characteristic for each stage



Selectable trip purpose or alarm purpose for each
stage


46BC

Broken conductor protection

Adopt the ratio of negative-sequence current to
positive-sequence current (Ι2/Ι1) to detect the broken
conductor.

1-2

PCS-9611S Feeder Relay
Date: 2019-12-29


1 Functions and Application



The measured

zero-sequence current from the

high-precision CT is adopted

50/51SEF

Sensitive

earth

fault

protection



Up to 6 stages with independent logic



Optional direction element for each stage, including
forward direction, reverse direction and non-direction



Optional definite-time characteristic and inverse-time
characteristic for each stage




Selectable trip purpose or alarm purpose for each
stage

50/51R



Up to 2 stages with independent logic



Full-current RMS value includes 2nd~11th harmonic

RMS overcurrent protection

components


Selectable trip purpose or alarm purpose for each
stage


37

Undercurrent protection

Optional blocking condition, including circuit breaker
position and current criterion




Selectable trip purpose or alarm purpose for each
stage



Breaker failure protection and re-trip function



Optional current criterion (phase overcurrent element,
zero-sequence

50BF

Breaker failure protection

overcurrent

element,

negative-sequence overcurrent element)


It can be initiated by current, circuit breaker position or
external binary input

50PSOTF

50GSOTF

Switch-on-to-fault protection



Two time delays



One stage of phase overcurrent SOTF protection



One stage of earth fault overcurrent SOTF protection



Harmonic control element



Voltage control element for phase overcurrent SOTF
protection



Up to 2 stages with independent logic




Optional definite-time characteristic and inverse-time
characteristic for each stage

59P

Overvoltage protection



Optional phase voltage or phase-to-phase voltage



Optional “1-out-of-3” logic or “3-out-of-3” logic



Selectable trip purpose or alarm purpose for each
stage

PCS-9611S Feeder Relay
Date: 2019-12-29

1-3

1


1 Functions and Application


1



Up to 2 stages with independent logic



Optional definite-time characteristic and inverse-time
characteristic for each stage

27P

Undervoltage protection



Optional phase voltage or phase-to-phase voltage



Optional “1-out-of-3” logic or “3-out-of-3” logic



Check mode using circuit breaker position and current
criterion




Blocked by instantaneous VT circuit failure



Selectable trip purpose or alarm purpose for each
stage

59Q

59Pos

59G

Negative-sequence
overvoltage protection



Up to 2 stages with independent logic



Selectable trip purpose or alarm purpose for each
stage

Positive-sequence




One stage of positive-sequence overvoltage protection

overvoltage protection



Selectable trip purpose or alarm purpose



Up to 2 stages with independent logic



Optional

Residual

overvoltage

protection

measured

zero-sequence

voltage

or


calculated zero-sequence voltage


Selectable trip purpose or alarm purpose for each
stage

81O

Overfrequency protection

81U

Underfrequency protection

81R

32R

Frequency

rate-of-change

protection
Reverse power protection



Up to 6 stages with independent logic




Voltage control element



Up to 6 stages with independent logic



Voltage control element



Up to 6 stages with independent logic



Voltage control element



Up to 2 stages with independent logic



Selectable trip purpose or alarm purpose for each
stage

60/50


Current unbalance protection



Up to 2 stages with independent logic



Selectable trip purpose or alarm purpose for each
stage

60/59

Voltage unbalance protection



Up to 2 stages with independent logic



Selectable trip purpose or alarm purpose for each
stage


CLP

25

Synchro-check


49

Thermal overload protection

50L/NL

1-4

Cold load pickup

Arc flash protection

It can be triggered by on-load signal or circuit breaker
position



Short resetting is supported



Independent logic for auto-reclosing and manually
closing



Two stages of thermal overload protection, one stage
for alarm purpose and the other stage for trip purpose




The arc flash signal is acquired by an arc sensor



It is combined with the auxiliary fault current criterion
PCS-9611S Feeder Relay

Date: 2019-12-29


1 Functions and Application

79

Auto-reclosing



One shot or multi-shot



3-pole AR



It can be triggered by protection operation signal or
external binary input signal



CTS
VTS
TCS

2

3

4

5

Current

Supports synchronism check or dead charge check

transformer

supervision
Voltage

transformer

supervision
Tripping circuit supervision

Control functions



Circuit breaker & disconnector control (Remote/Local)



Synchronism check for remote and manual closing

Measurement functions


Energy metering (active and reactive energy are calculated in import and export direction
respectively)



Power (Apparent/Active/Reactive)



Power factor



Frequency



Event recorder including 1024 disturbance items, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.




Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)

Supervision functions


VT circuit supervision



CT circuit supervision



Trip/Close coil supervision



Self-diagnostic



DC power supply supervision



System frequency supervision


Communication functions


Up to four 10Base-T/100Base-TX copper Ethernet ports using IEC 61850, DNP3.0 or
IEC 60870-5-103 over TCP/IP



Up to four 100Base-FX optical Ethernet ports using IEC 61850, DNP3.0 or IEC

PCS-9611S Feeder Relay
Date: 2019-12-29

1-5

1


1 Functions and Application

60870-5-103 over TCP/IP

1

6

7

8


1-6



Two RS-485 serial ports using IEC 60870-5-103 or Modbus



One RS-485 serial port for clock synchronization



Support GOOSE communication module using IEC 61850-8-1 GOOSE



Full compatibility between IEC 61850 Editions 1 and 2



Redundancy protocols PRP and HSR



One front RJ45 port for debugging

Digital interface


Support IEC 61850 MMS Server via extendable electrical or optical Ethernet port




Support IEC 61850-8-1 GOOSE via extendable electrical or optical Ethernet port



Support IEC 61850-9-2LE SV via extendable electrical or optical Ethernet port

User Interfaces


Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment



Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management



4 programmable operator pushbuttons with user-configurable labels



Up to 18 (6U, 1/2 × 19")/15 (6U, 1/3 × 19") programmable target LEDs with
user-configurable labels




1 RS-232 or RS-485 rear ports for printer



Language switchover—English + selected language



Configuration tool—PCS-Studio

Additional functions


User programmable logic



Fault location



Fault phase selection



System phase sequences rotation function (ABC or ACB)




Clock synchronization


IRIG-B: IRIG-B via RS-485 differential level or TTL level



PPS: Pulse per second (PPS) via RS-485 differential level or binary input



PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
PCS-9611S Feeder Relay
Date: 2019-12-29


1 Functions and Application





IEEE1588: Clock message based on IEEE1588 via optical fiber interface



SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network




SNTP (BC): Broadcast SNTP mode via Ethernet network



Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,
Modbus protocol and DNP3.0 protocol

1

Cyber security


NERC CIP



IEC 62351



IEC 62443



IEEE 1686

1.2 Typical Application
The PCS-9611S can be used for several applications, including feeder protection, transformer
backup protection, and capacitor protection etc. In addition, many auxiliary functions such as fault
diagnosis, fault recording, event recording, and communication functions etc. are also integrated

into the device. The device supports up to 13 analog inputs.

1.2.1 Feeder Protection Application
Busbar
3VTs

52

27P

VTS

81U

1VT

81O

25

81R

79

67P

*

*


3CTs

50P

51P

50G

51G

50SEF

51SEF

CTS

50BF

1CT

*

SOTF

67G

1CT

67SEF


FR

Load
Figure 1.2-1 Feeder protection typical application
PCS-9611S Feeder Relay
Date: 2019-12-29

1-7


1 Functions and Application

For the large-resistance grounding system, when an earth fault occurs, the zero-sequence current
sensitivity is insufficient, and the earth fault overcurrent protection may not operate. In this case,
sensitive earth fault protection (67/50/51SEF) can be configured.
For double busbars arrangement, the voltages of the two busbars can be connected to the
external voltage selection device firstly, and then the selected voltage is connected to the device;
the voltages of the two busbars can also be connected to the device directly and the voltage
selection function can be accomplished by the internal software.
In addition, the device provides some control functions such as synchronism check and
switchgear control etc., it also supports the measurement of apparent power (S), active power (P),
reactive power (Q), current (I), voltage (U), power factor (Cos), frequency (f) and others.

1.2.2 Transformer Backup Protection Application
HVS
3VT

52

FR


VTS

3CT

*
50/
51P

50/
51G

67P

50B
F

67G

CTS

*

1

The application scenario corresponding to this configuration is feeder protection. The device
provides phase overcurrent protection (67/50/51P), earth fault overcurrent protection (67/50/51G),
undervoltage protection (27P), switch-on-to fault protection (SOTF), underfrequency protection
(81U), overfrequency protection (81O) ), frequency rate-of-change protection (81R), breaker
failure protection (50BF), automatic reclosure (79) and other protection functions.


1CT
A.50
/51G

*

1CT

59G

52

LVS

Figure 1.2-2 Transformer backup protection typical application

The application scenario corresponding to this configuration is transformer backup protection, a
set of transformer backup protection is required for each side of the transformer. The device
provides phase overcurrent protection (67/50/51P), earth fault overcurrent protection (67/50/51G),
another group of earth fault overcurrent protection (A.50/51G), residual overvoltage protection
(59G), breaker failure protection (50BF) and other protection functions.
1-8

PCS-9611S Feeder Relay
Date: 2019-12-29


1 Functions and Application


In addition, the device supports the measurement of apparent power (S), active power (P),
reactive power (Q), current (I), voltage (U), power factor (Cos), frequency (f) and others.

1

1.2.3 Double-star Connection Capacitor Bank Protection Application
Busbar
3VT

52

*

*

27P

59P

50P

51P

50G

51G

VTS

3CTs


50BF

CTS

37

1CT

FR

1CT

60/50

*

Figure 1.2-3 Double-star connection capacitor bank protection typical application

The application scenario corresponding to this configuration is double-star connection capacitor
bank protection. The device provides phase overcurrent protection (50/51P), earth fault
overcurrent protection (50/51G), undervoltage protection (27P), phase overvoltage protection
(59P), undercurrent protection (37), current unbalance protection (60/50), breaker failure
protection (50BF) and other protection functions.
In addition, the device provides the switchgear control function, it also supports the measurement
of apparent power (S), active power (P), reactive power (Q), current (I), voltage (U), power factor
(Cos), frequency (f) and others.

PCS-9611S Feeder Relay
Date: 2019-12-29


1-9


1 Functions and Application

1.2.4 Single-star Connection Capacitor Bank Protection Application

1

Busbar
3VT

52

*

*

27P

59P

50P

51P

50G

51G


VTS

3CTs

50BF

CTS

37

1CT

FR
60/59

1VT

Figure 1.2-4 Single-star connection capacitor bank protection typical application

The application scenario corresponding to this configuration is neutral point ungrounded
single-star capacitor bank protection. The device provides phase overcurrent protection (50/51P),
earth fault overcurrent protection (50/51G), undervoltage protection (27P), phase overvoltage
protection (59P), undercurrent protection (37), voltage unbalance protection (60/59), breaker
failure protection (50BF) and other protection functions.
In addition, the device provides the switchgear control function, it also supports the measurement
of apparent power (S), active power (P), reactive power (Q), current (I), voltage (U), power factor
(Cos), frequency (f) and others.

1-10


PCS-9611S Feeder Relay
Date: 2019-12-29


2 Configuration Tool

2 Configuration Tool
Table of Contents
2.1 Brief Introduction to PCS-Studio.................................................................... 2-1
2.2 Connection to Debugging Computer ............................................................. 2-1
2.2.1 Via Front RJ45 Port .............................................................................................................. 2-1
2.2.2 Via Ethernet Interface on CPU Module ................................................................................ 2-2

2.3 Validation of Configuration ............................................................................. 2-2

PCS-9611S Feeder Relay
Date: 2019-12-29

2-a