ENGLISH
MITSUBISHI Low-Voltage Air Circuit Breakers series
World Super AE
CHINESE
三菱低圧気中遮断器 World Super AE
JAPANESE
Type AE-SW
INSTRUCTION MANUAL
取扱説明書
Types covered in this manual
対象機種
AE630-SW AE1000-SW AE1250-SW AE1600-SW
AE2000-SWA
AE2000-SW AE2500-SW AE3200-SW
AE4000-SWA
AE4000-SW AE5000-SW AE6300-SW
IMPORTANT NOTE: Before using these Series AE breakers, please read these
instructions carefully, and make sure that all actual users also read them.
ご使用の前に必ずこの取扱説明書をお読みください。
この説明書は、最終ユーザまでお届けください。
07A
Safety precautions
¡Before using this device, make sure to read this Instruction manual thoroughly. The cautionary items noted herein are of
the utmost importance for the safe use of this device, and should always be strictly followed.
¡Please make sure that the final user receives this Instruction manual.
¡This Instruction manual is prepared for an electrical expert.
The following symbols have been used:
DANGER
Failure to follow these instructions may result in dangerous conditions, which in
turn could lead to severe
personal injury or even
death.
CAUTION
Failure to follow these instructions may result in dangerous
conditions, which could result
in moderate to slight personal
injury or damage to equipments and facilities.
Warning for possible electrification under
certain conditions.
This means prohibition. Never ignore this
instruction.
Warning for possible outbreak of a fire
under certain conditions.
Be sure to follow these instructions without fail.
DANGER
¡Do not use this device on the conditions over ratings. Otherwise, ground-fault or short circuit fault could occur due to
dielectric breakdown. Or explosion could occur due to a short circuit protection failure.
¡Do not touch the terminals. There is a risk of electrical shock.
CAUTION
¡A qualified electrician should install this equipment.
¡Inspection and maintenance should be performed by a qualified electrician and only after shutting off the electric power
and verifying that there is no voltage present. Failure to do so could result in an electrical shock.
¡Make sure to tighten the terminal screws to the torque specified in the instruction manual. Failure to do so could result
in fire.
¡Do not install in areas subject to high temperatures, high humidity, dust, corrosive gas, vibrations, or shocks, etc. To do
so could result in malfunction or fire.
¡Install so that trash, concrete dust, iron filings or rainwater cannot get into the circuit breaker unit interior. Failure to do
so could result in malfunction or fire.
¡When the circuit breaker trips automatically, always clear the source of the malfunction before closing the circuit
breaker. Failure to do so could result in fire.
¡Terminal screws should be tightened periodically. Failure to do so could result in fire.
¡Use the breaker in 50/60 Hz. Failure to do so could result in malfunction or fire.
¡Dispose of this product as industrial waste.
E− 2
¡Safety precautions ................................................. 2
¡External view .......................................................... 3
¡Internal construction ............................................... 4
¡Outline dimensions and weight .............................. 4
¡Unpacking .............................................................. 5
¡Storage ................................................................... 5
¡Handling ................................................................. 6
¡Installation .............................................................. 7
¡Mount of drawout handle ........................................ 8
¡Attach the Inter-phase Barrier ................................ 8
¡Connection ............................................................. 9
¡Insert operation .................................................... 11
¡Drawout operation ................................................ 13
¡Charging operation ............................................... 15
¡Opening/Closing operation .................................. 16
¡Door interlock (DI) ................................................ 18
¡Cylinder lock (CYL) and castell lock (CAL) .......... 18
¡Shutter lock (SST-LOCK) ..................................... 18
¡Functions of electronic trip relay parts ................. 20
¡Characteristics setting of type WS relay .............. 22
¡Characteristics setting of type WM relay ............. 23
¡Characteristics setting of type WB relay .............. 24
¡Characteristic setting of optional setting module ... 25
¡Setting the operation characteristics .................... 27
¡Wiring diagram ..................................................... 29
¡Technical note (Arc space, reverse connection) ... 30
¡Technical note (Performance of withstand voltage) ... 30
¡Technical note (Service conditions) ..................... 31
¡Guarantee ............................................................ 31
¡Inspection and maintenance ................................ 32
¡Service network .................................................... 39
External view
< Fixed type >
< Drawout type >
Control circuit terminal box
Electronic trip relay
Control circuit connector
Control circuit terminal box
Arc-extinguish chamber
Cradle
OFF button
Charging
handle
ON buttons
Charging handle
Extension rail
Pad lock hook
Charging
indicator
ON/OFF
indicator
Rated name
plate
Drawout position indicator
Drawout handle aperture
Manual reset button
(option)
Drawout handle
Drawout state
Note: The fixed type is provided with lifting hooks (HP).
Fig. 3-1
Fig. 3-2
< Drawout type >
AE4000-SW∼
AE6300-SW 3P
Fix bolt
Fig. 3-3
E− 3
ENGLISH
Table of contents
Internal construction
1Control circuit terminal block
2Control circuit connector
3Auxiliary switch
4Shunt trip device, closing coil
5Electronic trip relay
6Front cover
7Tripping mechanism
8Closing mechanism
9Charging mechanism
AClosing spring
BDrawout mechanism
CIntermediate base
DArc-extinguishing chamber
EMovable contact
FFixed contact
GConductor on the breaker
HConductor on the cradle
IMain circuit junction
JBase
KContact spring
LConductor on the breaker
MConductor on the cradle
NPower supply CT
OCurrent sensor coil
PCradle
QCradle name plate
AE-SW
Fig. 4-1
Outline dimensions and Weight
Table 4-1
Type
Drawout
type
Fixed
type
Weight
(kg)
Drawout
type
Cradle
only
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
AE630-SW AE1000-SW AE1250-SW AE1600-SW
340 ✕ 410 ✕ 290 ✕ 40
425 ✕ 410 ✕ 290 ✕ 40
300 ✕ 430 ✕ 368 ✕ 61
385 ✕ 430 ✕ 368 ✕ 61
41
42
40
51
52
50
64
65
63
78
79
77
26
30
AE2000-SWA
340 ✕ 410 ✕ 290 ✕ 108
425 ✕ 410 ✕ 290 ✕ 108
300 ✕ 430 ✕ 368 ✕ 104
385 ✕ 430 ✕ 368 ✕ 104
47
57
70
84
31
35
Type
Fixed
type
Drawout
type
Fixed
type
Weight
(kg)
b
a
Drawout
type
Cradle
only
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
AE2000-SW
AE2500-SW
AE3200-SW
475 ✕ 410 ✕ 290 ✕ 40
605 ✕ 410 ✕ 290 ✕ 40
435 ✕ 430 ✕ 368 ✕ 61
565 ✕ 430 ✕ 368 ✕ 61
63
61
60
75
73
72
95
93
92
116
114
113
35
36
43
44
AE4000-SWA
475 ✕ 410 ✕ 290 ✕ 117
605 ✕ 410 ✕ 290 ✕ 117
439 ✕ 430 ✕ 368 ✕ 109
569 ✕ 430 ✕ 368 ✕ 109
81
99
108
136
49
61
43
a (MAX)
c
Drawout handle aperture
Fig. 4-3
Drawout
type
Drawout
type
Cradle
only
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
AE5000-SW
874 ✕ 414 ✕ 290 ✕ 136
1004 (1134) ✕ 414 ✕ 290 ✕ 136
875 ✕ 480 ✕ 368 ✕ 123
1005 (1135) ✕ 480 ✕ 368 ✕ 123
160
180 (200)
233
256 (279)
118
133 (148)
AE6300-SW
Max.173
Fixed
type
Fixed
type
240
263 (286)
125
140 (155)
( ) shows the value for 4P FN type, Neutral pole current capacity is 100% of the rated current.
E− 4
15
Cover position
200
AE4000-SW
(kg)
d
b
Drawout handle
Type
Weight
c
Fig. 4-2
Table 4-3
Dimension
a✕b✕c✕d
(mm)
11
¡Drawout type
Table 4-2
Dimension
a✕b✕c✕d
(mm)
¡Fixed type
40
Dimension
a✕b✕c✕d
(mm)
Fixed
type
169
200
Fig. 4-4
d
ENGLISH
Unpacking
1 Make sure that the packing case is free from any abnormality such as
breaking and/or wetting.
2 Referring to the rating nameplate, make sure that the delivered breaker
is in conformity with your order. Serial No. is indicated on the rated
name plate and the cradle name plate (Fig. 4-1Q).
Fixed type
Drawout type
Accessories
nameplate
ETR accessories
Nameplate
CT rated
name plate
Not attached
Fig. 5-1
Fig. 5-2
Fig. 5-3
Rated
name plate
Fig. 5-4
Storage
✽ When you start using the breaker after storage and if its storage period is over 6 years, use it after lubrication as stated in
“Grease lubricating procedure” for the maintenance manual.
+60°C
–20°C
Average temperature for 24 hours,
however, shall not be higher than 35°C.
Fig. 5-5
Avoid humid air.
Relative humidity : 85% max.
Fig. 5-6
Fig. 5-7
H2 S
SO2
NH3
0.01ppm
0.05ppm
0.25ppm
Fig. 5-10
OFF
Fig. 5-8
Fig. 5-9
Fig. 5-11
E− 5
Handling
Fig. 6-1
Fig. 6-2
Never drop the breaker when Never roll the breaker
handling.
when handling.
Wire length: 1 m or more
Wire length: 1 m or more
Lifting hooks (HP)
CONNECT position
Fig. 6-5
Fixed type
Drawout type
Fig. 6-4
Fig. 6-3
When the drawout breaker is
lifted with the cradle, lift it
when it is the “CONNECT”
position.
length
1m
Fig. 6-6
To lift the breaker types AE4000-SW,
AE5000-SW and AE6300-SW, be sure to
use four ropes with a length of 1 m or
more, or use the lifting truck, apply for
further detail.
E− 6
When lifting and placing, be careful neither to drop nor to impact the breaker and
the terminals for the center of gravity is
by the terminal.
ENGLISH
Installation
< Drawout type >
AE630-SW∼AE4000-SWA
1 mm
1 mm or less
Tolerance on support flatness
M12
M8
Earthing terminal
Fig. 7-1
Fig. 7-2
In the case of AE4000 ~ 6300-SW, insert four M12 bolts from the bottom and two M12 bolts from the back to mount the
cradle as shown in Fig. 7-3. In the case of 4P FN type, insert six M12 bolts from the bottom and two M12 bolts from the
back to mount the cradle as shown in Fig. 7-4.
AE4000 ~ 6300-SW 3P & 4P (HN)
Cradle
AE4000 ~ 6300-SW 4P (FN)
Mounting angle (Non-magnetic)
Mounting angle (Non-magnetic)
2-M12
2-M12
6-M12
4-M12
Fig. 7-3
Fig. 7-4
Operate the drawout operation (CONNECT position to DRAWOUT position) according to instructions of drawout
operation. (Refer to P.13 and 14.)
Lifting by lifting truck or lifting hooks
CAUTION
CAUTION
Lifting
Support
Falling
Fig. 7-5
When the main body is drawn out,
the center of gravity shifts to the
front. If the cradle is not secured,
take measures against overturning
and dropping.
Fig. 7-6
< Fixed type >
On AE4000-SWA,AE4000-SW ~
AE6300-SW, the center of gravity of the
cradle is located at the terminal position. When the main body is removed
from the cradle, the cradle may turn over
backward. Take measures against
overturning.
Fig. 7-7
M12
M8
Earthing
terminal
Fig. 7-8
E− 7
Mount of drawout handle
The drawout handle can be mounted on any of the left and right sides of the cradle.
¡Mounting on the left side
¡Mounting on the right side
Drawout handle
Handle holder
Note: The drawout handle cannot be mounted
on the left side of the cradle when the
cradle is provided with a mechanical
inter lock (MI) or a door inter lock (DI).
Mount the handle at an appropriate
position in the panel.
Mechanical interlock (MI)
or
door interlock (DI)
Cradle
Nut M5
Fig. 8-1
Fig. 8-2
Mtg. Screw M5 ✕ 12
2.8 ~ 3.6 N·m
Fig. 8-3
Attach the Inter-phase Barrier
Insert in the slot on the breaker.
<Fixed type>
<Drawout type>
Fig. 8-4
E− 8
Fig. 8-5
ENGLISH
Connection
■Main circuit
CAUTION
CAUTION
25mm
M12
40 ~ 50N·m
Conductor
Use small washers to connect that
the washers do not overlap with
each other.
Fig. 9-1
Fig. 9-2
ACB terminal (silverplated)
CAUTION
Max. 200 mm
Fig. 9-3
Fixing support
Fig. 9-4
■Control circuit
¡Crimp-type terminal size
Recommended crimp-type terminals
Ex.1.25 mm2 ~ 2.0 mm2 wires
N2-M3(RAP2-3.5) (JST)
FN2-M3(RBP2-3.5) (JST)
N2-YS3A(JST)
If the screw is tightened with excessive torque, the terminal and the
screw may be damaged. Tighten
the screw to the specified torque.
Screwdrivers should be used whose
diameters are of size suited to the
diameters of the cruciform grooves.
Size of toolhead : PH2
Passage wiring
M3.5 ✕ 10
Torque: 0.8 ~ 1.2N・m
Max. 7.2 mm
Fig. 9-5
Fig. 9-6
Fig. 9-7
E− 9
Table 10-1 Electromagnetic force in N per 1 m conductor (3-phase short circulation)
Type
Conductor distance (mm)
Prospective fault current
kA (pf)
30 (0.2)
42 (0.2)
50 (0.2)
65 (0.2)
75 (0.2)
85 (0.2)
100 (0.2)
130 (0.2)
AE630-SW
~
AE1600-SW
85
7,700
15,100
21,400
36,100
—
—
—
—
AE2000-SWA
3P
115
5,700
11,200
15,800
26,700
—
—
—
—
4P
105
6,300
12,200
17,300
29,300
—
—
—
—
AE2000-SW
~
AE3200-SW
130
5,100
9,900
14,000
23,600
31,500
40,400
—
—
AE4000-SWA
Drawout type
3P
4P
190
170
3,500
3,900
6,800
7,600
10,700
9,600
18,100
16,200
24,100
21,500
30,900
27,600
—
—
—
—
Fixed type
3P
4P
152
145
4,300
4,500
8,500
8,900
12,000
12,600
20,200
21,200
26,900
28,200
34,500
36,200
—
—
—
—
(N)
AE4000-SW
~
AE6300-SW
262
2,500
5,000
7,000
11,800
15,800
20,000
27,800
47,000
Table 10-2
Rated current max. (A)
4000
630
1000
1250
1600
2000
2500
3200
AE4000-SWA
Fixed type
4000
Conductor size (IEC60947-1)
(40°C ambient temperature, open air)
Connecting conductors (Copper bus bar)
Arrangement
Quantity
Conductor size (mm)
40 ✕ 5
2
Vertical
60 ✕ 5
2
Vertical
80 ✕ 5
2
Vertical
2
Vertical
100 ✕ 5
3
Vertical
4
Vertical
3
100 ✕ 10
Vertical
AE4000-SWA
Drawout type
Vertical
4
4
4
2m
4
Vertical
Vertical
Vertical
3m
3
4000 (AE4000-SW)
5000
6300
E − 10
Vertical
Note: Table 10-2 shows conductor size based
on IEC 60947-1 in ambient temperature
40°C and open air. And the examination
circuit is as Fig. 10-1
150 ✕ 10
100 ✕ 10
150 ✕ 10
200 ✕ 10
Fig. 10-1
■DISCONNECT
ENGLISH
Insert operation
CONNECT position
1 Release the lock levers, and pull the extension rails for-
ward.
2 Place the breaker on the extension rails, using a lifter or
ropes. Mount the concave of the breaker in the rail protruding portion. (Fig. 11-5)
1
2
Using a lifter or ropes
Extension rails
Lock levers
Fig. 11-1
3 Slowly push the breaker in unit it does not move.
To insert the breaker, push each side equally.
Otherwise (in the case of inserting slantwise) the breaker
can not move smoothly.
When ACB is installed at a high position, please do the
Drawout / Insert operation by two people.
Fig. 11-2
CAUTION
Concave of the breaker
3
Falling
Click!
Fig. 11-3
Projection of the rail
If the breaker main body is put
on the rails with the cradle unsecured, the center of gravity
shifts to the front. Take measures against overturning.
Fig. 11-5
Fig. 11-4
4 Keeping the OFF button pushed, insert the drawout handle.
Make sure that the drawout position indicator shows “DISCONNECT” (Fig. 11-7).
4
CAUTION
Take care not to shut finger between extension rails and switch
board when the breaker is insert.
OFF button
Shut finger
Push
DISCONNECT position
Drawout handle
Insert
Fig. 11-6
Fig. 11-7
(Prohibition)
Do not insert the drawout handle unless the OFF button is pushed.
There is a possibility of damaging.
E − 11
5 Push the lock plate in fully until it is latched to release
6 After releasing the lock plate, turn the drawout handle
the lock.
(Note:)
(a) If the lock plate is not fully released, turn the
drawout handle to right and left a little.
(b) Be sure to push the lock plate in fully to release
position, otherwise the drawout position indicator
may not function collectoly.
clockwise. Operating torque is less than 30 N·m.
(Note:)
(a) Do not try to pull the unit out while inserting it as
doing so may not accurately display the position. If the unit is pulled out in the middle of the
inserting process, pull it out to the circuit disconnecting position and then insert it again.
5
Lock plate
6
Lock position
Push
Cover
Latch
30N・m
Release
position
Fig. 12-1
Fig. 12-2
7 When the breaker is inserted to the test position, the
8 Then, push the lock plate to turn the handle clockwise.
drawout position indicator shows TEST position, and the
lock plate automatically protrudes to lock the drawout
handle.
When the breaker is inserted to the connect position,
the lock plate automatically protrudes to indicate that
the breaker has been inserted completely. The drawout
position indicator shows CONNECT position.
7
CAUTION
Insert the breaker until the lock plate protrudes. If it does
not protruding, the breaker may not be connected completely.
(Note:)
(a) After insertion is completed, do not turn the
drawout handle further.
(b) The drawout position indicator shows the position
(CONNECT or TEST) of the breaker at the time
when the lock plate protrudes. When the lock
plate is in the released state, the indicator shows
the reference position.
(c) It is impossible to close the breaker when inserting the drawout handle.
TEST position
8
Fig. 12-3
9 For the AE4000 ~ 6300-SW series (See Fig. 12-5), shall
be sure to tighten the screws on both sides to secure
the breaker.
Check 1
The lock plate is jutted
out.
9
Automatic
Check 2
CONNECT (Connection)
position
Fig. 12-4
Fig. 12-5
E − 12
■CONNECT
DISCONNECT position
ENGLISH
Drawout operation
1
1 Remove two fixing bolts (M12) for the types AE4000 ~
6300-SW. (See Fig. 13-1)
Fig. 13-1
2 Keeping the OFF button pushed, insert the drawout
handle.
2
OFF button
CONNECT position
Push
Fig. 13-2
(Prohibition)
Do not insert the drawout handle unless the OFF
button is pushed.
Drawout handle
Fig. 13-3
3 Push the lock plate in fully until it is latched to release
the lock.
3
Lock plate
(Note:)
(a) If the lock plate is not fully released, turn the
drawout handle to right and left a little.
(b) Be sure to push the lock plate in fully to the release position, otherwise the drawout position indicator may not function correctly.
Lock position
Push
Cover
Latch
Release
position
Fig. 13-4
4 After releasing the lock plate, turn the drawout handle
counterclockwise. Operating torque is less than 30 N·m.
4
(Note:)
(a) In the middle of drawout operation, do not turn
the drawout handle insert operation. The drawout
position indicator may not function correctly.
30N・m
Fig. 13-5
E − 13
5 When the breaker is drawn out to the test position, the
drawout position indicator shows TEST position, and the
lock plate automatically protrudes to lock the drawout
handle.
5
Automatic
TEST position
Fig. 14-1
6 Then, push in the lock plate, turn the drawout handle
counterclockwise to change the displayed extraction
position to the DISCONNECT position until the drawout
position indicator shows disconnect position. The handle
operation is completed. The breaker can be drawn out
by hand.
6
(Note:)
(a) The lock plate may project before the breaker
moves to the DISCONNECT position. Push the
lock plate in and continue to operate the handle.
(b) If the lock plate is not fully released, turn the
drawout handle to right and left a little.
DISCONNECT
position
Fig. 14-2
7 To remove the breaker main body from the cradle, pull
the lock levers toward you to unlock the main body, pull
the rails toward you, and draw out the breaker.
CAUTION
7
CAUTION
Lock lever
Shut finger
Take care not to shut finger between extension rails and switch
board when the breaker is
drawn out.
Falling
When the main body is drawn
out, the center of gravity shifts
to the front. If the cradle is not
secured, take measures against
overturning and falling.
Fig. 14-3
E − 14
Click!
Fig. 14-4
Otherwise (in the case of drawing slantwise) the breaker
can not move smoothly.
When ACB is installed at a high position, please do the
Drawout / Insert operation by two people.
8
ENGLISH
8 To drawout the breaker, pull each side equally.
(Note:)
Since the center of gravity is by the terminal, the
Cradle support is required to prevent from falling.
(See Fig. 15-1)
Cradle support
Fig. 15-1
Charging operation
< Manual charging >
Press the charging handle down at full stroke 7 or 8 times
until a click sounds. (It is completion when a charging handle
becomes light.) Then, the closing spring will be fully charged.
The charging indicator will show CHARGED.
The operating load is 30 N·m or less.
Charge operation: 7 to 8 times
Fig. 15-2
< Motor charging >
The closing spring is electrically charged.
This is an “ON charge method”, in which the spring is automatically charged when the breaker is closed.
¡Manual charging operation is also possible using the charging handle.
¡Pumping prevention is assured both electrically and mechanically.
¡Although the charging motor has a short time rating it can
be continuously operated for up to ten times.
¡Since the charging complete switch is separate from the
motor charging circuit, the sequence can be arranged as
required.
Table 15-1 Motor charging rating
Rated
voltage
(V)
Applicable Applied
voltage
voltage
range (V)
(V)
24 DC
48 DC
100-125
AC/DC
200-250
AC/DC
18-26.4
36-52.8
85-137.5
170-275
24
48
100
125
200
250
Inrush
Steady
current
current
(peak) (A)
(A)
22
14
10 (10)
12 (12)
5 (7)
6 (8)
6
3
3 (4)
3 (4)
1 (2)
1 (2)
Criterion for
power
Charging
requirement
time
(VA)
500
5 sec or
less
700
1000
700
1000
Note: Contents in parentheses show the case of AE4000-SWA 4-pole,
AE4000-SW, AE5000-SW and AE6300-SW.
24 V DC and 48 V DC products of AE4000-SWA 4-pole, AE4000-SW,
AE5000-SW and AE6300-SW cannot be manufactured.
MD circuit diagram
Charging completion switch
Charging
completion 413
Switch output 414
Charging limit
switch
Control
supply
U1
M
U2
Motor
Control
relay
Breaker
Motor charging
circuit
Apply for further of 24 V DC and 48 V DC.
Fig. 15-3
E − 15
Opening/Closing operation
< Conditions of ON operation >
ON operation will be possible, when all the following conditions have fulfilled.
¡The breaker is OFF condition.
¡The closing spring is charged.
The charging indicator shows “CHARGED”.
¡The state without OFF operations.
•Without SHT operation
•Without mechanical lock (Padlock, Cylinder lock, Mechanical in-
non-OFF instructions
terlock etc.)
OFF
•UVT controller power is supplied and no operation with trip terminals.
Fig. 16-1
Manual operation
< Closing >
Push the ON button, the breaker will close. The ON/OFF
indicator will show “ON”, and the charging indicator will show
“DISCHARGED”. Operating force is less than 50N.
(Note:)
When the OFF lock device (Padlock, cylinder lock,
castell lock etc.) is used, the closing operation should
be made after the lock is released.
Opening and closing of the drawout type breaker
must be carried out in either the CONNECT or the
TEST position.
If an under voltage trip device (UVT) is provided, its
rated voltage should be applied before attempting to
close and open the breaker.
ON
ON
Fig. 16-2
< Opening >
Push the OFF button, the breaker will be opened and the
ON/OFF indicator will show “OFF”. Operating force is less
than 50N.
OFF
OFF
Fig. 16-3
E − 16
Electrical operation
ENGLISH
Control supply
< Closing >
Remote closing can be made by emerging the closing coil (CC).
Apply the rated voltage to the control terminals A1 , A2 , and
the breaker closes.
The unit comprises an unti-pumping circuit which allows only
one action without first de-energizing then re-energizing.
To re-close the breaker, once turn off power (between A1 and
A2 ) to the closing coil, and re-apply the rated voltage to them.
When the breaker has an under-voltage trip device (UVT), the
breaker cannot be closed if power is not applied. (After power is
applied to the UVT, it takes a waiting time of 1.5 sec until the
breaker can be closed.)
Air circuit breaker
CC Unit
Min. 80ms
A1
CC
Power supply
One pulse
circuit
A2
Note: 24 to 48 V DC does not have rectifier circuit.
Fig. 17-1
< Opening >
The use of a shunt trip device (SHT) or an under-voltage trip
device (UVT) enables to electrically trip the breaker.
When an SHT is used, apply the rated voltage to C1 and C2 on
the control circuit terminal block.
When a UVT is used, open the trip terminals DT1 and DT2 on
the control circuit terminal block. (A short-circuiting bar has been
fitted before shipment. Remove the bar before using the terminals.)
Or turn off an applied voltage to D1 and D2 .
SHT circuit diagram
Air circuit breaker
Min. 40ms
Cut-off
switch
SHT unit
C1
Power supply
C2
SHT
Note: 24 to 48 V DC does not have rectifier
circuit.
Fig. 17-2
UVT circuit diagram (for 100-120 V AC, 200-240 V AC or
DC voltage)
UVT circuit diagram (for 380-460 V AC)
IN1
D1
UVT
controller
D2
Max. 2m
OUT3
D1
OUT4
D2
UVT
controller
UVT
coil
UVT
coil
DT1
Push button
for tripping
Min 0.2s
IN2
External
unit
DT1
Push button
for tripping
Min 0.2s
DT2
Max. 2m
DT2
Air circuit breaker
Note: Use a pushbutton for tripping having power ratings of
150 V DC and 0.5 A or more.
Fig. 17-3
Air circuit breaker
Note: Use a pushbutton for tripping having power ratings of
150 V DC and 0.5 A or more.
The external transformer dedicated for AE-SW is used.
Only one UVT controller can be connected to one
external unit.
Fig. 17-4
E − 17
Door interlock (DI)
< Procedures for releasing door interlock >
1 Even when the breaker is on, the interlock can be manually released.
For this purpose, make a hole 7 or more in diameter in the panel door. (See the following figure.)
(mm)
Door
Door hook
Direction A
Release
20
5
Hole for releasing 7 or
more in diameter
(5)
40
When the breaker is on
View A
Fig. 18-1
Cylinder lock (CYL) and Castell Lock (CAL)
< Procedures for locking in off state >
< Releasing procedures >
1 Press the OFF button to turn off the ACB.
1 Insert the key, and turn the key to the releasing side.
2 Hold down the OFF button and turn the key to the locking
If the key cannot be turned smoothly, hold down the OFF
button and turn the key to the releasing side.
side. Then, the key can be removed, and the breaker will
be locked in the off state.
OFF
Fig. 18-2
OFF
OFF
Lock
Fig. 18-3
Fig. 18-4
Release
E − 18
The safety shutter can be locked at the closing position so that
the live parts are not touched.
Prepare a pad lock (5 in diameter) by yourself.
ENGLISH
Shutter lock (SST-LOCK)
Pad lock (f5)
Shutter lock
Fig. 19-1
E − 19
Functions of electronic trip relay (ETR) parts
5 TAL LED and contact output Option
The ETR temperature detector is made functional by fitting a TAL sensor.
When the power type is P3 to P5, output is given between
513 and 564 on the control circuit terminal block. When
the temperature drops, the output will be reset. To retain
the output, take measures with an external sequence.
< Functions >
1 ERR. LED, Contact alarm output
When any abnormality or setting failure is found in ETR,
the LED alerts the operators to the abnormal status. When
the power type is P3 to P5, contact output is given between 513 and 574 on the control circuit terminal block.
•ETR function (Microprocessor, H/W)
•Mis-setting of INST. /MCR dial (P.27)
•Internal wiring of breaker related to ETR
6 MCR (Making current release) Option
Only when the breaker is turned on (from the off state), it
has the INST function. After it is turned on, the INST function will be disabled. If you specify the use of MCR when
placing an order, the MCR switch will be incorporated in
the main body. MCR will be functional by setting the INST
setting dial of ETR to the MCR side. (Refer to Fig. 20-2)
2 RUN LED (ETR)
This LED indicates that ETR is functional. When control
power is applied or approx. 10% of current flows into the
main circuit, the internal circuit will start, and the LED will
light.
3 RUN LED (Optional setting module)
This LED indicates that the optional setting module is functional.
When the control power is applied or approx. 10% of the
main circuit current flows, the LED will light.
7 Reset button
The trip indicator (LED and contact alarm output) can be
reset by pressing the “RESET” button on the front panel
of ETR or short-circuiting RS1 and RS2 on the control circuit terminal block.
(P1 and P2 types are not provided with the function to
reset the indication from the control circuit terminal block.)
A function is provided to temporarily lock LTD and STD
when the INST function is tested with the field test device.
(See the breaker tester instruction manual.)
4 Trip indicator (LED and contact alarm output)
The LED indicates the tripping or pre-alarm status. When
the power supply type is P3 to P5, contact output is given
between 513 (common) and 524 , 534 , 544 and 554 on
the control circuit terminal block.
When the current exceeds pre-alarm current setting (Ip),
the PAL LED will blink. When the LTD time (1/2 of TL) is
passed, the PAL LED will light and output the contact.
6MCR
2RUN LED
(ETR)
Do not
set
1ERR. LED
4LED indicating
cause of tripping
5TAL LED
Fig. 20-2
3RUN LED
(GFR)
4LED indicating
cause of tripping
7RESET
button
Fig. 20-1
As for the display and interface unit, see the separate instruction manual.
E − 20
< Pre-alarm function >
The current value which is used as the reference of the load
current indication LED, varies depending on the ETR types
and characteristics setting.
When the current exceeds pre-alarm current setting (lp), the
PAL LED will blink. When the LTD time (1/2 of TL) is passed,
the PAL LED will light and output the contact.
Table 21-1
Current
Base current
of LED indication
Usage
ETR type
General use
WS
WS1
WS2
WS3
Iu
Uninterrupted
current
WM
WM1
WM2
WM3
Load current
LED indication
IL
LTD pick-up
current
Ip
Current
Lighting
PAL LED
OVER
Blink
100
ON
PAL OUT
80
(contact output)
60
%Iu
1/2 TL
OFF
time (t)
100
Generator
protection use
80
60
40
%IL
OVER
Special purpose
use
WB
WB1
WB2
WB3
100
Ir
Rated current
80
60
%Ir
Note: When the “OVER” of WS type and the “100%” of LED are lighting, the
current value is over LTD pick-up current.
The breaker carries out trip operation after specified time.
< Power supply >
Power supply is required for the trip indicator (LED, alarm contact output), the measurement extension module, the display
(LCD), etc. Over-current tripping, function when there is no control power supply, it operates with the energy of internal CT.
Table 21-2 Ratings of the power supply and output contacts
Type code
P1
P2
P3
P4
P5
Rated voltage
100-240V AC·DC
24-60V DC
100-240V AC
100-125V DC
24-60V DC
100-240V DC
Criterion for power requirement Alarm output contacts
15VA
10VA
15VA
6-contacts
10VA
15VA
6-contacts
6-contacts (SSR)
Table 21-5 Resetting of the output contact
3
G1/E1/AP
Refer to
Self-holding Self-holding
under table
1
LTD
2
STD/INST
4
PAL
Automatic
reset
E1
AP
ETR dial set
G1
TRIP side Self-holding Self-holding
−
Automatic Automatic Automatic
ALARM side
reset
reset
reset
5
TAL
Automatic
reset
6
ERR.
Automatic
reset
Table 21-3 Alarm contact capacity (Type code P3 and P4)
Voltage (V)
240
AC
120
125
DC
30
Resistive load cos f=1.0 Inductive load cos f=0.4 L/R=0.7
0.5A
1A
1A
1A
0.05A
0.1A
1A
1A
Table 21-4 Current capacity (Type code P5)
Voltage (V)
240
AC
120
240
DC
30
Current
0.1A
0.1A
0.1A
0.1A
Peak current
0.3A
0.3A
0.3A
0.3A
max. ON resistance
5
5
5
5
Self-holding :
The output is maintained until it
resets.
Automatic reset :
The output will be reset if it back
to normal condition.
CAUTION
In case of power type P3 or P4, the alarm contact output relay is high sensitive relay. Therefore may occur a chattering noise
(approximately 1 ms) by ON/OFF operation of the breaker. Please adopt a time constant filter of several ms, or sampling
double reading, or the like.
E − 21
ENGLISH
< Load current LED >
Characteristics setting of type WS relay
7Pre-alarm
current: Ip
2Uninterrupted
current: Iu
3LTD time: TL
8Pre-alarm
1
6
2
Operation time (s)
time: Tp
4STD pick-up
current: Isd
3
With MCR
5STD time: Tsd
5
4
7
I2t ON
I2t OFF
6INST Pick-up
current: Ii
Note: The figure includes the optional G1
setting module, display and MCR.
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
Current (%)
Table 22
No.
Setting item
Mark
Adjustable setting range
Accuracy
Factory default
value
1
Current setting
Ir
0.5 ~ 1.0 (0.05step) ✕ In (CT rating)
—
1.0
Uninterrupted
Iu
current
LTD time
TL
3
4 STD pick-up current Isd
2
5
6
STD time
12-25-50-100-150s at Iu ✕ 2
1.5-2-2.5-3-4-5-6-7-8-9-10 ✕ Ir
0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s
(I2t ON)
(I2t OFF)
Tsd
INST/MCR
pick-up current
Ii
7 Pre-alarm current Ip
Tp
8 Pre-alarm time
1.05 ✕ Iu···Non pick-up
1.25 ✕ Iu···Pick-up
±20%
±15%
±20%
0.8 ~ 1.0 ✕ Ir (0.02step), Pick-up current : 1.15 ✕ Iu
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW, AE4000-SW
AE2000-SWA, AE4000-SWA
AE5000-SW
It operates in the range
between 0.04 and 0.08s
at Isd ✕ 1.5 when the time set at 0.06s.
16-12-10-8-6-4-2-2-4-6-8-10-12-16 ✕ Ir
(INST)
(MCR)
WS1
12-10-8-6-4-2-2-4-6-8-10-12 ✕ Ir
(INST)
(MCR)
WS2
10-8-6-4-2-2-4-6-8-10 ✕ Ir
AE6300-SW
(INST)
(MCR)
WS3
Iu ✕ 0.68 ~ 1.0 (0.04step)-OVER
1/2 TL at Iu ✕ 2 (after 1/2TL, PAL contact output turns on.)
1.0
150
10
0.5 (I2t ON)
WS1···16 (INST)
±15%
WS2···12 (INST)
WS3···10 (INST)
±10%
±20%
The table shows data obtained on the breakers provided with MCR (optional). For breakers without MCR, the setting position for MCR is not provided.
Relation of setting dial
In (CT rating)
E − 22
Ir
Iu
Isd
Ii
Ig (Page 25)
Ip
Ip2 (Page 26)
Load current LED (60, 80, 100, OVER)
OVER
—
ENGLISH
Characteristics setting of type WM relay
7Pre-alarm
current: Ip
2LTD pick-up
current: IL
3LTD time: TL
8Pre-alarm
1
6
2
Operation time (s)
time: Tp
4STD pick-up
current: Isd
3
5STD time: Tsd
With MCR
5
4
7
I2t ON
I2t OFF
6INST Pick-up
current: Ii
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
Current (%)
Note: The figure includes the optional G1 setting
module, display and MCR.
Table 23
No.
Setting item
Mark
Adjustable setting range
Accuracy
1
Current setting
Ir
0.63 ~ 1.0 ✕ In (Adjust by factory : Fixed)
—
1.0-1.05-1.1-1.15-1.2 ✕ Ir
15-20-25-30-40-60s at IL ✕ 1.2
1.5-2-2.5-3-3.5-4-4.5-5 ✕ Ir
±5%
±20%
±15%
±20%
2 LTD pick-up current IL
LTD time
TL
3
4 STD pick-up current Isd
5
6
STD time
INST/MCR
pick-up current
0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s
(I2t OFF)
(I2t ON)
Tsd
Ii
7 Pre-alarm current Ip
Tp
8 Pre-alarm time
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW, AE4000-SW
AE2000-SWA, AE4000-SWA
AE5000-SW
It operates in the range
between 0.04 and 0.08s
at Isd ✕ 1.5 when the time set at 0.06s.
16-12-10-8-6-4-2-2-4-6-8-10-12-16 ✕ Ir
(INST)
(MCR)
WM1
12-10-8-6-4-2-2-4-6-8-10-12 ✕ Ir
(INST)
(MCR)
WM2
10-8-6-4-2-2-4-6-8-10 ✕ Ir
AE6300-SW
(INST)
(MCR)
WM3
IL ✕ 0.68 ~ 1.0 (0.04step)-OVER
1/2 TL at IL ✕ 1.2 (after 1/2TL, PAL contact output turns on.)
Factory default
value
Comply with
ordering sheet
1.15
20
5
0.5 (I2t ON)
WM1···16 (INST)
±15%
WM2···12 (INST)
WM3···10 (INST)
±5%
±20%
OVER
—
The table shows data obtained on the breakers provided with MCR (optional). For breakers without MCR, the setting position for MCR is not provided.
When the WM relay is used, the pre-alarm current at the setting, OVER, is the same as that at 1.0.
Relation of setting dial
In (CT rating)
Ir (Fixed)
Ig(Page 25)
IL
Isd
Ii
Ip
Ip2 (Page 26)
Load current LED (40, 60, 80, 100)
E − 23
Characteristics setting of type WB relay
7Pre-alarm
current: Ip
Max. setting of
let-through current
8Pre-alarm
time: Tp
1
Operation time (s)
Max. setting of
external OCR
6
6INST pick-up
current: Ii
Up to Icw
Up to Icw
7
Max. breaking time
(In case of AE4000-SW~
6300-SW, it is 0.05s)
Current (%)
Note: The figure include MCR function.
Table 24
No.
Setting item
1
Current setting
Adjustable setting range
Ir
6
INST/MCR
pick-up current
Ii
Factory default
value
—
1.0
AE630-SW~AE1600-SW
AE2000-SW~AE3200-SW, AE4000-SW
AE2000-SWA, AE4000-SWA
AE5000-SW
AE6300-SW
7 Pre-alarm current Ip
Tp
8 Pre-alarm time
Accuracy
0.5 ~ 1.0 (0.05step) ✕ In (CT rating)
Mark
16-12-10-8-6-4-2-2-4-6-8-10-12-16 ✕ Ir
(INST)
(MCR)
WB1
12-10-8-6-4-2-2-4-6-8-10-12 ✕ Ir
(INST)
(MCR)
WB2
10-8-6-4-2-2-4-6-8-10 ✕ Ir
(INST)
(MCR)
WB3
Ir ✕ 0.68 ~ 1.0 (0.04step)-OVER
75s at Ir ✕ 2 (after 75s, PAL contact output turns on.)
WB1···16 (INST)
±15%
WB2···12 (INST)
WB3···10 (INST)
±10%
±20%
The table shows data obtained on the breakers provided with MCR (optional). For breakers without MCR, the setting position for MCR is not provided.
Relation of setting dial
In (CT rating)
E − 24
Ir
Ii
Ip
Ip2 (Page 26)
Load current LED (60, 80, 100, OVER)
Ig (Page 25)
OVER
—
ENGLISH
Characteristic setting of optional setting module
< Characteristics setting of G1 module >
1
1Pick-up current: Ig
0.1
1.0
2
¡When the 3pole breaker is used on a 3phase-4wires system, the
neutral CT (NCT) is required for ground fault protection. As for the
NCT installation, refer to instruction manual (included in the product).
¡In the case of ✽low-rating of AE630-SW, power supply is necessary
for ground fault protection.
Ground fault protection does not operate correctly without power
supply.
Operation time (s)
3.0±20%
2Operating time: Tg
0.15±20%
Ͻ0.1
(0.04 to 0.1s)
✽ AE630-SW low rating type: 500A, 315A and 250A
Table 25-1
Adjustable setting range
0.1 to 1.0✕In (0.1 steps)
±20%
2
Ground fault
Tg
time
1.0
3.0-1.5-0.8-0.5-0.3-0.15-Ͻ0.1 - Ͻ0.1-0.15-0.3-0.5-0.8-1.5-3.0 s
(TRIP)
(ALARM)
(at 1.5 × Ig)
±20%
Ground fault current (% of CT rating In)
Accuracy Setting for shipment
3s(TRIP)
No. Setting item Mark
Ground fault
Ig
1
pick-up current
Note: If the ground fault current setting is 0.2 or more, the
module except low rating of AE630-SW operates even
when control power is not applied.
< Characteristic setting of E1 module >
1
By combining the ETR with Earth leakage protection(ER) and
External ZCT, earth leakage protection is possible. Control
supply is necessary for this function.
ZCT for load circuit
ZCT types
ZCT163
ACB types, poles
AE630-SW ~ AE1600-SW 3P
AE630-SW ~ AE1600-SW 4P
AE2000-SW ~ AE3200-SW 3P
AE2000-SW ~ AE3200-SW 4P
ZCT323
ZCT324
2
As for outline dimensions, refer to AE-SW catalogue,
and make your choice in reference to the BUSBAR size.
1Pick-up current: I∆n
ZCT with primary conductors
ZCT types
ZTA1200A
ZTA2000A
ACB types, poles
AE630-SW ~ AE1600-SW 3P
AE1250-SW ~ AE1600-SW, AE2000-SWA 3P
1A
10A
3.0s±20%
ZT15B
ZT30B
ZCT types
ZT40B
ZT60B
ZT80B
Operation time (s)
ZCT for ground wire of transformer types
ZT100B
¡Be sure to combine with ZCT of our products.
¡As for the ZCT installation, reter to instruction manual (included in
the product).
Table 25-2
ER time
0.15s±20%
Ͻ0.1s
(0.04 ~ 0.1s)
No. Setting item Mark
ER pick-up
I∆n
q
current
w
2Operation time: Te
Te
Adjustable setting range
1A-2A-3A-5A-10A
Accuracy Setting for shipment
0%
10A
–30%
3-1.5-0.8-0.5-0.3-0.15-Ͻ0.1s - Ͻ0.1-0.15-0.3-0.5-0.8-1.5-3 s
±20%
(TRIP)
(ALARM)
(at 1.5 × I∆n)
3s(TRIP)
Earth leakage current (A)
E − 25