Tải bản đầy đủ (.pdf) (40 trang)

Developments in Heat Transfer Part 17 pot

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (3.7 MB, 40 trang )

Heat Transfer in the Environment:
Development and Use of Fiber-Optic Distributed Temperature Sensing

629
known-temperature sections should bracket the expected observations in the corresponding
environment. If possible, the fiber-optic cable should have a loop to return the cable to the
instrument (see Suárez et al. (2011) for more details about calibration procedures). This
permits the DTS instrument to interrogate the fiber-optic from each end, i.e., allowing
single- or double-ended measurements. Single-ended measurements refer to temperatures
estimated from light transmission in only one direction along the optical fiber. These
measurements assume a uniform rate of differential attenuation (Δα) over the entire fiber,
and provide greater precision near the instrument, degrading with distance because of the
energy loss along the fiber length. Double-ended measurements refer to temperatures
estimated from light transmission in both directions along the optical fiber. In these
measurements, the temperature is estimated using single-ended measurements made from
each end of the fiber, and can account for spatial variation in the differential attenuation of
the anti-Stokes and Stokes backscattered signals, which typically occurs in strained fibers.
Double-ended measurement results in a signal noise more evenly distributed across the
entire length of the optical fiber, but uniformly greater than that obtained in a single-ended
measurement (Tyler et al., 2009b; Suárez et al., 2011). Single-ended calibrations are
encouraged for short cables (i.e., smaller than 1 or 2 km) since they provide more precision
near the instrument. However, sometimes strains or sharp bends in the deployed fiber-optic
cable yields large localized losses in the Stokes and anti-Stokes signals, which decrease the
magnitude of the signals and add noise to the temperature data. Because these localized
losses cannot be handled adequately by a single uniform value of the differential
attenuation, further calibration is sometimes required to translate the scattered Raman
signals into usable temperature data. In these cases, double-ended measurements are
recommended because they allow the calculation of the differential attenuation along the
entire length of the cable, and are much better able to handle the step losses introduced by
strains and bends.
4.4 Operating conditions


An issue that has been observed in DTS installations is drift of the instrument. This drift
typically occurs because of large variations in the instrument’s temperature, particularly
when the DTS instrument is subject to large daily temperature fluctuations in the field. The
best solution to minimize this drift is to put the instrument in a controlled environment if
possible. Other solution to minimize drift is to calibrate the DTS instrument at every
measurement (sometimes referred to as dynamic calibration).
4.5 Current and future trends
As previously described, the ability to precisely measure temperature at thousands of
locations is the main thrust of DTS systems. This capability has opened a new window for
observation of environmental processes. Typical DTS instruments currently used in
environmental applications can achieve temperature resolutions as small as ±0.01 °C, and
spatial and temporal resolutions of 1-2 m and 10-60 s, respectively. At present, there are
ongoing efforts to improve both spatial and temporal resolution of DTS systems. A high-
resolution DTS instrument (Ultima, Silixa, Hertfordshire, UK) with temporal and spatial
resolutions of 1 Hz and 12.5 cm, respectively, was recently commercialized and is under
testing in environmental applications. This instrument simultaneously improved temporal
precision by a factor of ten and spatial precision by a factor of four over previously available
units. It was first deployed for observation of turbulent and stable atmospheric processes

Developments in Heat Transfer

630
( and it has also
been utilized during a borehole heat tracer experiment designed to identify zones of high
horizontal hydraulic conductivity and borehole through-flow. While this new DTS instrument
has opened many possibilities, observation of atmospheric processes, for example, still
needs improvement of temporal resolution to monitor turbulent processes. Instruments with
this improved resolution are expected to be available in the near future and definitively will
open new opportunities for observation of environmental processes.
5. Conclusion

In the environment, heat transfer mechanisms are combined in a variety of ways and span
spatial scales that range from millimeters to kilometers. This extremely wide spatial scaling
has been a barrier that limits observation, description, and modeling of environmental
processes. The introduction of fiber-optic DTS has contributed to fill the gap between these
two disparate scales. Fiber-optic DTS has proven effective to precisely observe temperatures
at thousands of locations at the same time, with no issues of bias, and avoiding variability
due to use of different sensors.
In this work, we have shown some of the environmental applications that have benefited
from DTS methods. For instance, using fiber-optic DTS provides the first and only reliable
method in which the spatial variability of snowpack temperatures can easily and remotely
be measured. Measurement of both vertical and horizontal gradients and their spatial
variability may provide important insights into snowpack dynamics, melting and avalanche
susceptibility. DTS methods also have improved thermal measurements in natural and
managed aquatic systems. For example, the hydrodynamic regimes in Devils Hole were
observed at resolutions smaller than 0.1 °C, allowing observation of temperature gradients
as small as 0.003 °C m
-1
. This resolution allowed the examination of seasonal oxygen and
nutrient distribution in the water column. In salt-gradient solar ponds, this temperature
resolution allowed observation of both mixing and stratification, which is important for
pond efficiency. In both Devils Hole and the solar pond, fiber-optic DTS provided high-
resolution thermal measurements without disturbance of the water column. DTS methods
also have been successfully utilized in other environments such as in atmosphere, streams,
boreholes, and in many applications to understand the interdependence between
groundwater and surface water. Novel extensions of DTS methods include spatially
distributed soil moisture estimation, detection of illicit connections in storm water sewers,
and there are many more to come in the near future, especially because the technology is
growing and improving the spatial and temporal resolutions of DTS instruments, which will
open new opportunities for environmental observations.
6. Acknowledgement

This work was funded by the National Science Foundation by Award NSF-EAR-0929638.
7. References
Alfe, D., Gillan, M.J., Vocadlo, L., Brodholt, J. & Price, G.D. (2002). The ab initio simulation
of the earth’s core. Philosophical Transaction of the Royal Society of London A, Vol.360,
No.1795, (June 2002), pp. 1227-1244, ISSN 1364–503X
Heat Transfer in the Environment:
Development and Use of Fiber-Optic Distributed Temperature Sensing

631
Alpers, M., Eixmann, R., Fricke-Begemann, C., Gerding, M. & Höffner, J. (2004).
Temperature lidar measurements from 1 to 105 km altitude using resonance,
Rayleigh, and Rotational Raman scattering. Atmospheric Chemistry and Physics,
Vol.4, No.3, (2004), pp. 793-800, ISSN 1680-7316
Andersen, M.E & Deacon, J.E. (2001). Population size of Devils Hole pupfish (Cyprindon
diabolis) correlates with water level. Copeia, Vol.2001, No.1, ( February 2001), pp.
224-228, ISSN 0045-8511
Bales, R.C., Molotch, N.P, Painter, T.H, Dettinger, M.D., Rice, R. & Dozier, J. (2006).
Mountain hydrology of the western United States. Water Resources Research, Vol.42,
No.W08432, (2006), 13 pp., ISSN 0043-1397
Bense, V.F. & Kooi, H. (2004). Temporal and spatial variations of shallow subsurface
temperature as a record of lateral variations in groundwater flow. Journal of
Geophysical Research, Vol.109, No. B04103, (2004), 13 pp., ISSN 0148-0227
Branco, B.F. & Torgersen, T. (2009). Predicting the onset of thermal stratification in shallow
inland waterbodies. Aquatic Sciences, Vol.71, No.1, (March 2009), pp. 65-79, ISSN
1015-1621
Brown, J.H. & Feldmeth, C.R. (1971). Evolution in constant and fluctuating environments:
thermal tolerances of desert pupfish (Cyprinodon). Evolution, Vol.25, No.2, (June
1971), pp. 390-398, ISSN 0014-3820
Brutsaert, W. (1982). Evaporation into the atmosphere: theory, history and applications (1st
Edition), Springer, ISBN 9789027712479, London, England

Builtjes, P.J.H. (2001). Major twentieth century milestones in air pollution modelling and its
Applications, In: Air Pollution Modeling and its Applications XIV, Gryning, S.E. &
Schiermeier (eds.), Springer, pp.3-16, Kluwer Academic/Plenum Publishers, ISBN
0306465345, New York
Campbell, G.S. (1985). Soil physics with BASIC: transport models for soil-plant systems (3rd
Edition), Elsevier, ISBN 9780444425577, New York, USA
Dakin, J.P., Pratt, D.J., Bibby, G.W. & Ross, J.N. (1985). Distributed optical fiber Raman
temperature sensor using a semiconductor light-source and detector. Electronics
Letters, Vol.21, No.13, (1985), pp. 569-570, ISSN 0013-5194
Dürrenmatt, D.J. & Wanner, O. (2008). Simulation of the wastewater temperature in sewers
with TEMPTEST. Water Science and Technology, Vol.57, No.11, (2008), pp.1809-1815,
ISSN 0273-1223
Eichinger, W.E., Cooper, D.I., Parlange, M. & Katul, G. (1993). The Application of a
Scanning, Water Raman-Lidar as a Probe of the Atmospheric Boundary Layer. IEEE
Transactions on Geoscience and Remote Sensing, Vol.31, No.1, (January 1993), pp.70-79,
ISSN 0196-2892
Farahani, M.A. & Gogolla, T. (1999). Spontaneous Raman Scattering in Optical Fibers with
Modulated Probe Light for Distributed Temperature Raman Remote Sensing.
Journal of Lightwave Technology, Vol.17, No.8, (August 1999), pp.1379-1391, ISSN
0733-8724
Förster, A., Schrötter, J., Merriam, D.F. & Blackwell, D. (1997). Application of optical-fiber
temperature logging—An example in a sedimentary environment. Geophysics,
Vol.62, No.4, (July-August 1997), pp.1107-1113, ISSN 0016-8033
Fridleifsson, I.B., Bertani, R., Huenges, E., Lund, J.W., Ragnarsson, A. & Rybach, L. (2008).
The possible role and contribution of geothermal energy to the mitigation of

Developments in Heat Transfer

632
climate change, In: O. Hohmeyer and T. Trittin (Eds.) IPCC Scoping Meeting on

Renewable Energy Sources, Proceedings, pp. 20-25, Luebek, Germany, January 20-25,
2008
Freifeld, B.M., Finsterle, S., Onstott, T.C., Toole P. & Pratt, L.M. (2008). Ground surface
temperature reconstructions: using in situ estimates for thermal conductivity
acquired with a fiber-optic distributed thermal perturbation sensor. Geophysical
Research Letters, Vol.35, No.L14309, (2008), 5 pp., ISSN 0094-8276
Hausner, M.B. (2010). Estimating in situ integrated soil moisture content using fiber-optic
distributed temperature sensing (DTS) measurements in the field. M. Sc. Thesis,
University of Nevada, Reno, 124 pp.
Hausner, M.B., Tyler, S.W., Wilson, K.P., Gaines, D.B. & Selker, J.S. (2010). Devils Hole: a
window into the carbonate aquifer of the Death Valley regional flow system.
Abstract H31A-0977 presented at 2010 Fall Meeting, American Geophysical Union, San
Francisco, California, USA, December 2010
Henderson, R.D., Day-Lewis, F.D. & Harvey, C.F. (2009). Investigation of aquifer-estuary
interaction using wavelet analysis of fiber-optic temperature data. Geophysical
Research Letters, Vol.36, No.L06403, (2009), 6 pp., ISSN 0094-8276
Henderson-Sellers, B. (1984). Engineering Limnology (1st Edition), Pitman Published Limited,
ISBN 0273085395, London, England
Hoes, O.A.C, Schilperoort, R.P.S., Luxemburg, W.M.J., Clemens, F.H.L.R. & van de Giesen,
N.C. (2009a). Locating illicit connections in storm water sewers using fiber-optic
distributed temperature sensing. Water Research, Vol.43, No.20, (December 2009),
pp. 5187-5197, ISSN 0043-1354
Hoes, O.A.C., Luxemburg, W.M.J., Westhoff, M.C., van de Giesen, N.C. & Selker, J.S.
(2009b). Identifying seepage in ditches and canals in polders in the Netherlands by
distributed temperature sensing. Lowland Technology International, Vol.11, No.2,
(December 2009), pp. 21-26, ISSN 1344-9656
Hurtig, E., S. Großwig, S., Jobmann, M., Kühn, K. & Marschall, P. (1994). Fibre-optic
temperature measurements in shallow boreholes: experimental application for fluid
logging. Geotermics, Vol.23, No.4, (August 1994), pp. 355-364, ISSN 0375-6505
Kelley, D.E., Fernando, H.J.S., Gargett, A.E., Tanny, J. & Özsoye, E. (2003). The diffusive

regime of double-diffusive convection. Progress in Oceanography, Vol.86, No.3-4,
(March 2003), pp. 461-481, ISSN 0079-6611
Keller, C.A., Huwald, H., Vollmer, M.K., Wenger, A., Hill, M., Parlange, M.B. & Reimann, S.
(2011). Fiber optic distributed temperature sensing for the determination of the
nocturnal atmospheric boundary layer height. Atmospheric Measurement Techniques,
Vol.4, No.2, (2011), pp. 143-149, ISSN 1867-1381
Kersey, A.D. (2000). Optical fiber sensors for permanent downwell monitoring applications
in the oil and gas industry. IEICE Transactions on Electronics, Vol.E83c, No.3, (March
2000), pp. 400-404, ISSN 0916-8524
Kumar, A. & Kishore, V. (1999). Construction and operational experience of a 6000 m2 solar
pond at Kutch, India. Solar Energy, Vol.65, No.4, (March 1999), pp. 237-249, ISSN
0038-092X
Kurashima, T., Horiguchi, T. & Tateda, M. (1990). Distributed-temperature sensing using
stimulated Brillouin scattering in optical silica fibers. Optics Letters, Vol.15, No.18,
(1990), pp. 1038-1040, ISSN 0146-9592
Heat Transfer in the Environment:
Development and Use of Fiber-Optic Distributed Temperature Sensing

633
Lachenbruch, A.H. (1959). Periodic heat flow in a stratified medium with applications to
permafrost problems. U.S. Geological Survey Bulletin, 1083-A, 36 pp.
Lean, J. & Rind, D. (1998). Climate Forcing by Changing Solar Radiation. Journal of Climate,
Vol.11, No.12, (December 1998), pp. 3069-3094, ISSN 0894-8755
Lee, K.K.M., Steinle-Neumann, G. & Akber-Knutson, S. (2009). Ab initio predictions of
potassium partitioning between Fe and Al-bearing MgSiO
3
perovskite and post-
perovskite. Physics of the Earth and Planetary Interiors, Vol.174, No.1-4, (May 2009),
pp. 247-253, ISSN 0031-9201
Lema, S.C. & Nevitt, G.A. (2006). Testing an ecophysiological mechanism of morphological

plasticity in pupfish and its relevance to conservation efforts for endangered Devils
Hole pupfish. The Journal of Experimental Biology, Vol.209, No.18, (September 2006),
pp. 3499-3509, ISSN 0022-0949
Lowry, C.S., Walker, J.F., Hunt, J.H. & Anderson, M.P. (2007). Identifying spatial variability
of groundwater discharge in a wetland stream using a distributed temperature
sensor. Water Resources Research, Vol.43, No.W10408, (2007), 9 pp., ISSN 0043-1397
Lu, H. , Walton, J. & Swift, A. (2001). Desalination coupled with salinity-gradient solar
ponds. Desalination, Vol.136, No.1-3, (May 2001), pp. 13-23, ISSN 0011-9164
Lundquist, J.D. & Lott, F. (2008). Using inexpensive temperature sensors to monitor the
duration and heterogeneity of snow-covered areas. Water Resources Research, Vol.44,
No.W00D16, (2008), 6 pp., ISSN 0043-1397
Miller, R.R. (1950). Speciation in fishes of the genera Cyprinodon and Empetrichthys
inhabiting the Death Valley region. Evolution, Vol.4, No.2, (June 1950), pp. 155-163,
ISSN 0014-3820
Minckley, C.O & Deacon, J.E. (1973). Observations on the reproductive cycle of Cyprinodon
diabolis. Copeia, Vol.1973, No.3, (August 1973), pp. 610-613, ISSN 0045-8511
Moffett, K.B., Tyler, S.W., Torgersen, T., Menon, M., Selker, J.S. & Gorelick, S.M. (2008).
Processes controlling the thermal regime of saltmarsh channel beds. Environmental
Science and Technology, Vol.42, No.3, (January 2008), pp. 671-676, ISSN 0013-936X
Moya-Laraño, J. (2010). Can Temperature and Water Availability Contribute to the
Maintenance of Latitudinal Diversity by Increasing the Rate of Biotic Interactions?
The Open Ecology Journal, Vol.3, No.1, (2010), pp. 1-13, ISSN 1874-2130
Moyle, P.B. (2002). Inland Fishes of California: Revised and Expanded (1st edition), University of
California Press, ISBN 9780520227545, Berkeley, California, USA
Neilson, B.T., Hatch, C.E., Ban, H. & Tyler, S.W. (2010). Solar radiative heating of fiber-optic
cables used to monitor temperatures in water. Water Resources Research, Vol.46,
No.W08540, (2010), 17 pp., ISSN 0043-1397
Norand, C.W.B. (1920). Effect of High Temperature, Humidity, and Wind on the Human
Body. Quarterly Journal of the Royal Meteorological Society, Vol.46, No.193, (January
1920), pp. 1-14, ISSN 0035-9009

Otto, R.G. & Gerking, S.D. (1973). Heat tolerance of a Death Valley pupfish (genus
Cyprinodon). Physiological Zoology, Vol.46, No.1, (January 1973), pp. 43-49, ISSN
0031-935X
Painter, T.H., Donahue, D., Dozier, J., Li, W., Kattelmann, R., Dawson, D., Davis, R.E., Fiori,
J., Harrington, B. & Pugner, P. (2000). The Mammoth Mountain cooperative snow
study site: data acquisition, management, and dissemination. Proceedings of the

Developments in Heat Transfer

634
International Snow Science Workshop, Vol. ISSW2000, pp. 447-451, Big Sky, Montana,
USA, October 2000
Rabl, A. & Nielsen, C. (1975). Solar ponds for space heating. Solar Energy, Vol.17, No.1,
(April 1975), pp. 1-12, ISSN 0038-092X
Riggs, A. & Deacon, J.E. (2002). Connectivity in Desert Aquatic Ecosystems: The Devils Hole
Story, Proceedings of Spring-fed wetlands: important scientific and cultural resources of
the intermountain region, DHS Publication No. 41210, Las Vegas, Nevada, USA, May
2002, available from:
Robinson, D.A., Campbell, C.S., Hopmans, J.W., Hornbuckle, B.K., Jones, S.B., Knight, R.,
Ogden, F., Selker, J.S. & Wendroth, O. (2008). Soil moisture measurement for
ecological and hydrological watershed-scale observatories: a review. Vadose Zone
Journal. Vol.7, No.1, (February 2008), pp. 358-389, ISSN 1539-1663
Rogers, A. (1999). Distributed optical-fibre sensing. Measurement Science and Technology,
Vol.10, No.8, (August 1999), pp. R75-R99, ISSN 0957-0233
Roth, T.R., Westhoff, M.C., Huwald, H., Huff, J.A., Rubin, J.F.,Barrenetxea, G., Vetterli, M.,
Parriaux, A., Selker, J.S. & Parlange, M.B. (2010). Stream Temperature Response to
Three Riparian Vegetation Scenarios by Use of a Distributed Temperature
Validated Model. Environmental Science and Technology, Vol.44, No.6, (February
2010), pp. 2072–2078, ISSN 0013-936X
Sayde, C., Gregory, C., Gil-Rodriguez, M., Tufillaro, N., Tyler, S.W., van de Diesen, N.C.,

English, M., Cuenca, R. & Selker, J.S. (2010). Feasibility of soil moisture monitoring
with heated fiber optics. Water Resources Research, Vol.46, No.W06201, (2010), 8 pp.,
ISSN 0043-1397
Sclater, J.G, Parsons, B. & Jaupart, C. (1981). Oceans and Continents: Similarities and
Differences in the Mechanisms of Heat Loss. Journal of Geophysical Research, Vol.86,
No.B12, (1981), pp. 11535-11552, ISSN 0148-0227
Selker, J.S., Thevenaz, L., Huwald, H., Mallet, A., Luxemburg, W., van de Giesen, N.C.,
Stejskal, M., Zeman, J., Westhoff, M. & Parlange, M.B. (2006a). Distributed fiber-
optic temperature sensing for hydrologic systems. Water Resources Research, Vol.42,
No.W12202, (2006a), 8 pp., ISSN 0043-1397
Selker, J.S., van de Giesen, N.C., Westhoff, M., Luxemburg, W. & Parlange, M.B. (2006b).
Fiber optics opens window on stream dynamics. Geophysical Research Letters, Vol.33,
No.L24401, (2006), 4 pp., ISSN 0094-8276
Shrode, J.B. & Gerking, S.D. (1977). Effects of constant and fluctuating temperatures on
reproductive performance of a desert pupfish, Cyprinodon n. nevadensis.
Physiological Zoology, Vol.50, No.1, (January 1977), pp. 1-10, ISSN 0031-935X
Slater, L.D., Ntarlagiannis, D., Day-Lewis, F.D., Mwakanyamale, K., Versteeg, R.J., Ward, A.,
Strickland, C., Johnson, C.D. & Lane, J.W. (2010). Use of electrical imaging and
distributed temperature sensing methods to characterize surface water–
groundwater exchange regulating uranium transport at the Hanford 300 Area,
Washington. Water Resources Research, Vol.46, No.W10533, (2010), 13 pp., ISSN
0043-1397
Smith, E. & Dent, G. (2005). Modern Raman spectroscopy: a practical approach (1st Edition), John
Wiley and Sons, ISBN 978-0471497943, Sussex, England
Steele-Dunne, S.C., Rutten, M.M., Krzeminska, D.M., Hausner, M.B., Tyler, S.W., Selker, J.S.,
Bogaard, T.A. & van de Giesen, N.C. (2010). Feasibility of Soil Moisture Estimation
Heat Transfer in the Environment:
Development and Use of Fiber-Optic Distributed Temperature Sensing

635

using Passive Distributed Temperature Sensing. Water Resources Research, Vol.42,
No.W03534, (2010), 12 pp., ISSN 0043-1397
Suárez, F. (2010). Salt-gradient solar ponds for renewable energy, desalination and reclamation of
terminal lakes. Ph. D. Thesis, University of Nevada, Reno, 195 pp.
Suárez, F., Childress, A.E. & Tyler, S.W. (2010a). Temperature evolution of an experimental
salt-gradient solar pond. Journal of Water and Climate Change, Vol.1, No.4, (2010), pp.
246-250, ISSN 2040-2244.
Suárez, F., Tyler, S.W. & Childress, A.E. (2010b). A fully coupled transient double-diffusive
convective model for salt-gradient solar ponds. International Journal of Heat and Mass
Transfer, Vol.53, No.9-10, (April 2010), pp. 1718-1730, ISSN 0017-9310.
Suárez, F., Tyler, S.W. & Childress, A.E. (2010c). A theoretical study of a direct contact
membrane distillation system coupled to a salt-gradient solar pond for terminal
lakes reclamation. Water Research, Vol.44, No.15, (August 2010), pp. 4601-4615, ISSN
0043-1354.
Suárez, F., Aravena, J.E., Hausner, M.B., Childress, A.E. & Tyler, S.W. (2011). Assessment of
a vertical high-resolution distributed-temperature-sensing system in a shallow
thermohaline environment. Hydrology and Earth System Sciences, Vol.15, No.3,
(March 2011), pp. 1081-1093, ISSN 1027-5606
Tyler, S.W., Burak, S.A., Mcnamara, J.P., Lamontagne, A., Selker, J.S. & Dozier, J. (2008).
Spatially distributed temperatures at the base of two mountain snowpacks
measured with fiber-optic sensors. Journal of Glaciology, Vol.54, No.187, (December
2008), pp. 673-679, ISSN 0022-1430
Tyler, S.W. & Selker, J.S. (2009). New user facility for environmental sensing, EOS,
Transactions, American Geophysical Union, Vol.90, No.50, (December 2009), pp. 483,
ISSN 0096-3941
Tyler, S.W., Hausner, M.B., Suárez, F. & Selker, J.S. (2009a). Closing the energy budget:
advances in assessing heat fluxes into shallow lakes and ponds, EOS, Transactions,
American Geophysical Union, Vol.90, No.52 (Fall Meet. Suppl.), ISSN 0096-3941, San
Francisco, California, USA, December 2009
Tyler, S.W., Selker, J.S., Hausner, M.B., Hatch, C.E., Torgersen, T., Thodal, C.E. & Schladow,

S.G. (2009b). Environmental temperature sensing using Raman spectra DTS fiber-
optic methods. Water Resources Research, Vol.45, No.W00D23, (2009), 11 pp., ISSN
0043-1397
Turner, J.S. (1974). Double-diffusive phenomena. Annual Review of Fluid Mechanics, Vol.6,
(January 1974), pp. 37-54, ISSN 0066-4189
Uchida, Y., Sakura, Y. & Taniguchi, M. (2003). Shallow subsurface thermal regimes in major
plains in Japan with reference to recent surface warming. Physics and Chemistry of
the Earth, Vol.28, No.9-11, (2003), pp. 457-466, ISSN 1474-7065
Vogt, T., Schneider, P., Hahn-Woernle, L. & Cirpka, O.A. (2010). Estimation of seepage rates
in a losing stream by means of fiber-optic high-resolution vertical temperature
profiling. Journal of Hydrology, Vol.380, No.1-2, (January 2010), pp. 154-164, ISSN
0022-1694
Westhoff, M.C., Savenije, H.H.G., Luxemburg, W.M.J., Stelling, G.S., van de Giesen, N.C.,
Selker, J.S., Pfister, L., Uhlenbrook, S. (2007). A distributed stream temperature
model using high resolution temperature observations. Hydrology and Earth System
Sciences, Vol.11, No.4, (2007), pp. 1469-1480, ISSN 1027-5606

Developments in Heat Transfer

636
Westhoff, M.C., Bogaard, T.A. & Savenije, H.H.G. (2010). Quantifying the effect of in-stream
rock clasts on the retardation of heat along a stream. Advances in Water Resources,
Vol.33, No.11, (November 2010), pp. 1417-1425, ISSN 0309-1708
Winograd, I.J., Landwehr, J.M., Coplen, T.B., Sharp, W.D., Riggs, A.C., Ludwig, K.R. &
Kolesar, P.T. (2006). Devils Hole, Nevada δ
18
O record extended to the mid-
Holocene. Quaternary Research, Vol.66, No.2, (September 2006), pp. 202-212, ISSN
0033-5894
Yilmaz, G. & Karlik, S.E. (2006). A distributed optical fiber sensor for temperature detection

in power cables. Sensors and Actuators A: Physical, Vol.125, No.2, (January 2006), pp.
148-155, ISSN 0924-4247
32
Prandtl Number Effect on Heat Transfer
Degradation in MHD Turbulent Shear
Flows by Means of High-Resolution DNS
Yoshinobu Yamamoto and Tomoaki Kunugi
Department of Nuclear Engineering, Kyoto University
Japan

1. Introduction
Estimation of the heat transfer degradation effected by Magneto-Hydro-Dynamics (MHD)
forces is one of the key issues of the fusion reactor designs utilized molten salt coolant.
FLiBe which is the molten salt mixture of LiF and BeF, is one of the coolant candidates in the
first wall and blanket of the fusion reactors, and has several advantages which are little
MHD pressure loss, good chemical stability, less solubility of tritium and so on. In contrast,
heat transfer degradation for the high Prandtl number, (Pr=
ν
/
α
, Prandtl number,
ν
is the
kinetic viscosity,
α
is the thermal diffusivity) characteristics caused by the low thermal
diffusivity and high viscosity (Sagara et al, 1995), was one of the issues of concern.
MHD turbulent wall-bounded flows have been investigated extensively by both
experimental and numerical studies (Blum, 1967, Reed & Lykoudis, 1978, Simomura, 1991,
Lee & Choi, 2001, Satake et al., 2006, Boeck et al, 2007, etc.) and much important information

such as the drag reduction, the turbulent modulation, similarity of velocity profile, and heat
transfer have been obtained.
On the other hands, MHD turbulent heat transfer in a high-Pr fluid has not been understood
well. The previous experimental and direct numerical simulation (DNS) studies still have
conducted for Prandtl number up to Pr=5.7. Therefore, the knowledge of the MHD heat
transfer on higher-Pr fluids such as FLiBe (Pr=20–40), is highly demanded to verify and
validate the MHD turbulent heat transfer models for the fusion reactor designs.
The objective of this study is to perform a direct numerical simulation of MHD turbulent
channel flow for Prandtl number up to Pr=25, where all essential scales of turbulence are
resolved. In this study, we report that the MHD turbulent heat transfer characteristics in
Pr=25 for the first time and discuss that the MHD pressure loss and heat transfer
degradation under the wide-range Pr conditions. The obtained database is of considerable
value for the quantitative and qualitative studies of the MHD turbulent heat transfer models
for the blanket design of a fusion reactor.
2. Target flow field and flow condition
The flow geometry and the coordinate system are shown in figure 1. The target flow fields
are the 2-D fully-developed turbulent channel flows imposed wall-normal magnetic field

Developments in Heat Transfer

638
and the streamwise and spanwise computational periods (L
x
and L
z
) are chosen to be 8h and
4h, where h (=L
y
/2) denotes channel half height.











L
z
=4h
L
y
=2h
Flow
L
x
=8h
Bottom wall
Top wall
x
y
z
θ
top

B
y



θ
bottom

Δ
θ
=
θ
top
-
θ
bottom
=1

Fig. 1. Flow geometry and coordinate system


Re
τ

Ha Pr
Grid number
N
x
,N
y
,N
z

(M

x
,N
y
,M
z
)
Resolution
Δ
x
+
,
Δ
y
+
,
Δ
z
+

(temperature)
CASE1
(Lithium)
0,8,10,12 0.025
CASE2
(KOH)
0,6,8,10,12 5.7
72,182,72 16,7,0.25-2.0,8.3
CASE2



(fine grid)
0 5.0 432,182,216 2.8,0.25-2.0,2.8
CASE3
(FLiBe)
0,8,10,12 25.0
72,370,72
(320,370,160)
16.7,0.05-1.0,8.3
(3.8,0.05-1.0,3.8)
CASE3

(fine grid)
150
0 25.0 648,370,324 1.9,0.05-1.0,1.9
Table 1. Numerical condition
Duo to the limitation of our utilizable computational resources, turbulent Reynolds number
(Re
τ
=u
τ
h/
ν
, u
τ
: friction velocity) was limited to 150, and three thermal properties of the
Lithium (Pr=0.025), KOH solution (Pr=5.7), and FLiBe (Pr=25) were covered. The KOH
solution was used as the FLiBe simulant fluid in the previous experimental study
(Yokomine et al., 2007) and the Lithium is a typical liquid metal coolant in a blanket of
fusion reactors. To maintain the fully-developed turbulent status, Hartman number
(Ha=B

y
2h(
σ
/
ρν
)
1/2
, B
y

: wall-normal magnetic flux density,
σ
: electrical conductivity,
ρ
:
density ) was also limited around 12 in Re
τ
=150 (Lee & Choi, 2001, Yamamoto et al., 2008).
Numerical conditions are tableted in Table 1. Here, N
x
(
Δ
x)

,N
y
(
Δ
y), and N
z

(
Δ
z) are the grid
numbers (resolutions) in the streamwise, vertical, and spanwise directions, respectively. The
super-script + denotes the nondimensional quantities normalized by the friction velocity,
friction temperature and the kinematic viscosity. M
x
and M
z
are also the grid numbers in a
horizontal direction temperature as mentioned 3.2, in case of adapting a different grid
resolution for the flow and for the temperature field. In a wall-normal direction, the grid
resolution resolved the Batchelor scale is ensured for all cases.
Prandtl Number Effect on Heat Transfer Degradation in
MHD Turbulent Shear Flows by Means of High-Resolution DNS

639
3. Numerical procedures
3.1 Governing equation and boundary condition
Governing equations of the present DNS are the continuity equation (1), the momentum
equations (2) with the electric field described using the electrical potential approach
(Simomura, 1991), Poisson equation (3) of the electrical potential, and the energy equation (4).

,0
*
=


i
i

x
u

(1)

**
**2**
*
1
,
ij
ii
i
ii
j
k
j
lm l m k
jijj j
uu
upu
F
BuBB
tx x xx x
ϕ
σ
δν ε
ρρ ρ
⎛⎞


⎛⎞
∂∂∂

⎜⎟
+=− + + −+
⎜⎟
⎜⎟
⎜⎟
∂∂ ∂ ∂∂ ∂
⎝⎠
⎝⎠
(2)

(
)
,
*
*2
kjijk
i
i
i
Bu
xxx
ε
φ


=
∂∂


(3)

**
*2*
.
j
jjj
u
tx xx
θ
θθ
α

∂∂
+=
∂∂ ∂∂
(4)
Here u
i
and x
i
are the streamwise (i=1), the vertical (i=2) and the spanwise (i=3) velocity and
direction, respectively. t is time, F
i
is the i-th competent mean pressure gradient, p is the
pressure,
φ
is the electric potential, B
i

=(0, B
y
,0) is the Magnetic flux density, and
θ
is the
temperature. Super script * denotes instantaneous value and
δ
ij
,
ε
ijk
(i,j,k=1-3) is the
Kronecker delta and the Levi-Civita symbol, respectively.
Non-slip and periodic conditions are imposed for the boundary conditions of velocities and
the constant temperature at top and bottom boundaries (
θ
top
>
θ
bottom
,
θ
top
: top wall
temperature,
θ
bottom
: bottom wall temperature), and the periodic conditions are imposed for
the temperature field. In this study, temperature transport is treated as a passive scalar.
The non-conducting conditions of the electric potential are applied to all walls and the

periodic condition imposed on the horizontal directions. Total electric current in the
spanwise flow domain is kept zero.
3.2 Numerical procedures
A hybrid Fourier spectral and the second-order central differencing method (Yamamoto et
al, 2009) is used for the computations. The spectral method is used to compute the spatial
discretization in the stream (x) and spanwise (z) directions. Nonlinear terms are computed
with 1.5 times finer grids in horizontal (x and z) directions to remove the aliasing errors
(Padding method). The derivative in the wall normal (y) direction is computed by a second-
order finite difference scheme at the staggered grid arrangement (Satake et al, 2006). Time
integration methods of the governing equations are the 3rd-order Runge-Kutta scheme for
the convection terms, the Crank-Nicolson scheme for the viscous terms and the Euler
Implicit scheme for the pressure terms, respectively. The Helmholtz equation for the viscous
(diffusion) terms and the Poisson equations of the pressure and the electrical potential are
solved by a Tri-Diagonal Matrix Algorithm, TDMA in Fourier space.
In DNS of the flow field, the Kolmogorov length scale has to be resolved. On the other
hands, the length scales of the high-Pr temperature field are smaller than the smallest length
scales of the velocity fields (Batchelor, 1959). To reduce the numerical costs in DNS of the

Developments in Heat Transfer

640
high-Pr fluids, a different number of grid resolutions in the horizontal direction for velocity
and temperature fields is adapted. In computing the temperature convection terms in (4)
pseudo-spectrally, the grid points of velocities were expanded to the same grid points of the
high-Pr temperature, as follow,

(,,) /, /
(,,) , / , /.
0otherwise
xzx xxz zz

xz x xxz zz
kyk k N L k N L
k
y
kkMLkML
ππ
ππ

Φ≤ ≤

Φ= ≤ ≤



(5)
Here,
Φ denotes the velocities in Fourier space, k
x
and k
z
are the wavenumbers in the
streamwise and spanwise directions, respectively. The phase-shift method (Patterson &
Orszag, 1971) is used to remove the aliasing errors derived from the temperature convection
terms. As a consequence, the grid size corresponded to the Batchelor length scale is retained
for Pr=25.
Present DNS were calculated by using the T2K Open Supercomputer at Kyoto University.
Elapsed time per one time step was about 1.2 [s] when using 8nodes (128cores) in CASE3.
4. Validation of present DNS
At the beginning of this study, we demonstrate the adequacy of the present DNS.


10
0
10
1
10
-6
10
-5
10
-4
10
-3
10
-2
10
-1
k
x
h
E
uu
+
y
+
=149
Ha= 0
Ha= 8
Ha=12
0
50 100 150

0
1
2
3
y
+
u
rms
+
Ha=0
Ha=8
Ha=12

(a) Streamwise turbulent intensity, (b) Streamwise energy spectra,
Fig. 2. MHD suppression effects on turbulence
Figures 2 shows the turbulent intensities and the streamwise energy spectra at the channel
center in Ha=0, 8, and 12. As well as the previous study (Lee & Choi, 2001), turbulent
intensity was suppressed with increase of Ha as shown in Fig. 2-(a). Figure 2-(b) gives
evidence that turbulent suppression effects can be remarkable in the high wave-numbers
turbulence. It is clear that the effects of the grid dependency would be the biggest in Ha=0.
Therefore, the convergences of the grid tendency were investigated in Ha=0, by using the
DNS data fully-resolved the Batchelor length scale for Pr=5 or 25 in Ha=0 as tabled CASE2’
and CASE3’ in Table 1.
4.1 Medium high-Pr case
According to Na & Hanratty, 2000, the use of a higher resolution in horizontal direction
does not produce significant changes to the first-order statistics from Pr=1 to 10. In this
Prandtl Number Effect on Heat Transfer Degradation in
MHD Turbulent Shear Flows by Means of High-Resolution DNS

641

study, we investigated the grid dependency effects on the higher-order statistics such as the
energy dissipation (=
ε) and temperature energy dissipation (=ε
θ
).

10
1
10
2
0
0.2
0.4
0.6
0.8
ε
θ
+
y
+
Δx
+
=2.8
Δx
+
=16.8
Δx
+
=20.0
Pr=5.0, Ha=0

10
1
10
2
0
0.1
0.2
ε
+
y
+
Δx
+
=2.8
Δx
+
=16.8
Δx
+
=20.0
Pr=5.0, Ha=0

(a)energy dissipation, (b) temperature energy dissipation,
Fig. 3. Grid dependency on high-order statistics in medium high-Pr fluid
Figures 3 show the energy dissipation and temperature energy dissipation for Pr=5 with
change of the horizontal resolutions. The required horizontal resolution for the reproductively
of the energy dissipation and temperature dissipation, was estimated as
Δ
x
+

=16.7, and
Δ
z
+
=8.3 in this medium high-Pr fluid.
4.2 High-Pr case
For Pr=25, DNS in Re
τ
=180 were conducted by means of a hierarchical algorithm in which
only the scalar fields were solved on the grid dictated by the Batchelor scale (Schwertfirm
&Manhart, 2007). However, the validation by using the different resolution for flow and
high-Pr temperature field has not been reviewed yet. In this study, the adequacy of DNS by
using a different resolution for flow and high-Pr temperature field is verified compared
with DNS data fully-resolved the Batchelor length scale in the same grid size for flow and
temperature.


(a) (b) (c)
Fig. 4. Flow visualization, CASE3, Ha=0, Pr=25, y
+
=149. (a) streamwise turbulent velocity,
-2 (black) < u
+
< 2.0 (white), (b) turbulent temperature (coarse grid), -0.15 (black) <
θ
/
Δθ
<0.15
(white) (c) turbulent temperature (fine grid), -0.15(black)<
θ

/
Δθ
<0.15 (white)
Figure 4 shows the flow visualization in results of Ha=0, Pr=25. In this case, 72x72 grids for
flow (in Fig.4-(a)), 72x72 grids for the temperature filed (in Fig.4-(b)) and 320x160 grids for
the temperature field (in Fig.4-(c)), were used in horizontal directions, respectively. Despites

Developments in Heat Transfer

642
of the high wave-number flow fluctuations, the high wave- number temperature fluctuation
can be computed as shown in Fig.4-(c).
Figure 5-(a) shows the temperature energy dissipation for Pr=25 with change of the
horizontal resolutions. The required horizontal resolution for the reproductively of the
temperature dissipation, was estimated as
Δ
x
+
=8.3, and
Δ
z
+
=4.2. This grid resolution is
equivalent to twice as high for Pr=5; it is proportional to square root of the Pr ratio
(=(25/5)
1/2
). The effects of using the different resolution for flow and temperature cannot be
found even in the temperature energy dissipation.
Figure 5-(b) shows the streamwise energy spectra near channel center for Pr=25. Compared
with CASE3 and CASE3’, there is ninefold grid resolution in flow, but the variance of the

spectra profile cannot be observed in this high-Pr temperature field. This indicates that the
high wave-number velocity fluctuations less than the Kolmogorov scale can be ignored in a
high-Pr passive scalar transport. As a consequence, we verify the adequacy of DNS by using
the different resolution for flow and high-Pr temperature field and numerical cost in DNS of
high-Pr fluids can be substantially reduced.

10
1
10
2
0
1
2
3
ε
θ
+
y
+
Δx
+
=1.9
Δx
+
=16.8 (temp. field Δx
+
=3.8)
Δx
+
=8.3

Δx
+
=16.8
Pr=25.0, Ha=0
10
0
10
1
10
2
10
-18
10
-13
10
-8
10
-3
k
x
h
E
uu
+
, E
θθ
/Δθ
2
E
uu

+
, CASE3'
E
θθ
/Δθ
2
, CASE3'
E
uu
+
, CASE3
E
θθ
/Δθ
2
, CASE3

(a) (b)
Fig. 5. Grid dependency and validation of different grid resolution for flow and high-Pr
temperature field. (a) Temperature dissipation, (b) Streamwise energy spectra, streamwise
velocity and temperature
5. MHD pressure loss and heat transfer
In this study, the friction drag confident (Cf) and Nusselt number (Nu) at the wall were
expressed by
Cf=2u
τ
2
/U
b
2

, (6)
Nu=2h(d
Θ/dy)
wall
/
Δθ
. (7)
Here, U
b
and (dΘ/dy)
wall
denotes the bulk mean velocity and mean temperature gradient at
the wall.
Figure 6-(a) shows the friction drag coefficient as a function of the interaction parameter N
(=Ha
2
/Re
b
, Re
b
: Bulk Reynolds number=U
b
2h/
ν
), where the friction drag coefficients were
normalized by that in Ha=0. The friction drag coefficients were monotonically decreased
Prandtl Number Effect on Heat Transfer Degradation in
MHD Turbulent Shear Flows by Means of High-Resolution DNS

643

with increase of Ha; MHD pressure loss is less than the turbulent drag reduction effected by
MHD. Therefore, all MHD cases of this study might be considered in a turbulent-laminar
transition status. We need the DNS data in more higher Re to discuss the general
relationships between MHD pressure loss and MHD turbulent drag reduction in turbulent
condition.
Figure 6-(b) shows the Nusselt number as a function of N, where the Nusselt number were
also normalized by that in Ha=0. Maximum heat transfer degradation in the low-Pr fluid
was no more than 5% of the non-MHD condition. The usability of a low-Pr fluid was no
doubt about heat transfer, however, Ha of Lithium was 700 times as large as one of FLiBe in
the same Reynolds number (Re) and magnetic flux density (B
y
) conditions.

0 0.01
0.02 0.03
0.9
0.95
1
1.05
N=Ha
2
/Re
b
Cf/Cf
Ha=0
0 0.01 0.02 0.03
0.5
0.6
0.7
0.8

0.9
1
N=Ha
2
/Re
b
Nu/Nu
Ha=0
Pr=5.7
Pr=25
Pr=0.025

(a) friction drag coefficient, (b) Nusselt number,
Fig. 6. Friction drag coefficient and Nusselt number as a function N
On the other hands, heat transfer degradation in the high-Pr fluids (Pr=5.7 and 25) reached
up to 30% without depending on Pr. This indicated that similarity of heat transfer
degradation in high-Pr MHD flows might be existed.

0 5 10 15
0.8
0.9
1
Ha
δ
Ha=0
/δ, Nu/Nu
Ha=0
δ
Ha=0
/δ, P r = 5 . 7

Nu/Nu
Ha=0
Pr=5.7
δ
Ha=0
/δ , P r = 2 5
Nu/Nu
Ha=0
Pr=25

Fig. 7. Thermal viscosity thickness and Nusselt number as a function N
Figure 7 shows the thermal viscosity thickness (
δ) and Nusselt number as a function of Ha in
the high-Pr fluids, where thermal viscosity thickness was defined as

Developments in Heat Transfer

644
δ=y
+
at Θ
+
=0.99Pry
+
. (8)
Thermal viscosity thickness was normalized by those in Ha=0. Heat transfer degradation
was strongly correlated with change of the thermal viscosity thickness without depending
on Pr.
6. Turbulence statistics
Figure 8 shows the profiles of temperature turbulent intensities for Pr=5.7 and 25. With

increase of Ha, the peak position of turbulent intensity was shifted to the channel center side
and the scale of it was decreased in both cases. In either case, the peak position was located
below the wall-normal height y
+
=15; thermal boundary layers for Pr=5.7 and 25 were
thinner than the velocity boundary layer in the present MHD conditions.

10
0
10
1
10
2
0
5
10
15
y
+
θ
rms
+
Pr=5.7
Ha=0
Ha=8.0
Ha=12.0
10
-1
10
0

10
1
10
2
0
10
20
30
40
y
+
θ
rms
+
Pr=25.0
Ha=0
Ha=8.0
Ha=12.0

(a) Pr=5.7, (b) Pr=25,
Fig. 8. Turbulent temperature profiles

10
0
10
1
10
2
-5
0

5
y
+
Loss Gain
Pr=25, Ha=0
10
0
10
1
10
2
-5
0
5
Production

ε
θ
Turbulent diff.
Viscous diff.
Residual
y
+
Loss Gain
Pr=25.0, Ha=12.0

(a) Ha=0, Pr=25, (b) Ha=12, Pr=25,
Fig. 9. Budget of turbulent temperature energy
Prandtl Number Effect on Heat Transfer Degradation in
MHD Turbulent Shear Flows by Means of High-Resolution DNS


645
10
0
10
1
10
2
-0.1
-0.05
0
0.05
0.1
Gain Loss
y
+
Production
TPG
Turbulent diff.
Viscous diff.
ε
θv
Residual
Budget of vθ
10
0
10
1
10
2

-0.1
-0.05
0
0.05
0.1
Gain Loss
y
+
Budget of vθ

(a) Ha=0, Pr=25, (b) Ha=12, Pr=25,
Fig. 10. Budget of wall-normal turbulent heat flux
Figures 9 and 10 show the budget of turbulent temperature energy (K
θ
) and wall-normal
turbulent heat flux(v
θ
) for Pr=25, Ha=0 and 12. Transport equations (9) and (10) of turbulent
temperature energy and wall-normal turbulent heat flux are expressed by

2
2
2
Production Turbulent diff.
Viscous diff.
Dissipation:
1
0
2
j

v
K
v
yy x
y
θ
θ
ε
θθ θ
θαα
⎛⎞
∂Θ ∂ ∂

⎜⎟
=− − + −
⎜⎟
∂∂ ∂

⎝⎠
 


 
, (9)

()
Production Turbulent diff. Temp.Press-Grad.
Viscous diff.
Dissipation
0

jj
vv p
vv
vv v p
y
yyyy yy xx
θθ
θθ θ
νθ α ν α
⎛⎞
∂∂

Θ∂∂∂∂ ∂∂
=− − + + + − − +
⎜⎟
⎜⎟

∂∂∂∂ ∂∂ ∂∂
⎝⎠
  



. (10)
Here, over bar denotes quantities estimated by ensemble average. In Fig. 9-(a), around the
thermal buffer region (y
+
=5), both diffusion terms of turbulent and viscous exceeded
dissipation (ε
θ

) term. Predominance of the diffusion terms in the high-Pr fluids (Pr>10) was
confirmed in the previous DNS (Schwertfirm &Manhart, 2007). In Ha=12, predominance of
diffusion terms was observed more clearly as shown in Fig. 9-(b). As well as turbulent
temperature energy, turbulent diffusion term in Fig. 10-(b) was dominant at y
+
=15-30 in
Ha=12, however, the predominance of viscous diffusion term was indistinct. Compared
with no-MHD case in Fig. 9-(a), the damping of turbulent diffusion term was small but the
others were suppressed by the MHD effects; effects of turbulent diffusion on the MHD heat
transfer were relatively larger with increase of Ha. These indicate that a sensitive model of
the turbulent diffusion would be required in the prediction of MHD heat transfer in high-Pr
fluids.
Figure 11 shows the turbulent Prandtl number (Pr
T
) profiles for Pr=5.7 and 25. Turbulent
Prandtl number was defined as

Pr /
T
uv v
θ
= . (11)

Developments in Heat Transfer

646
10
0
10
1

10
2
0.4
0.6
0.8
1
1.2
Pr=5.7
Ha= 0.0
Ha= 8.0
Ha=12.0
y
+
Pr
T
10
0
10
1
10
2
0.5
1
1.5
2
Pr=25.0
Ha= 0.0
Ha= 8.0
Ha=12.0
y

+
Pr
T

(a)Pr=5.7, (b) Pr=25,
Fig. 11. Turbulent Prandtl number profiles
Na & Hanratty, 2000 and Schwertfirm & Manhart, 2007 pointed out that turbulent Prandtl
number close to the wall increases with increase of Pr. The turbulent Prandtl number
profiles in the non-MHD case were good agreements with the results of Schwertfirm &
Manhart, 2007, however, profiles in MHD case was decreased close to the wall for Pr=5.7
and 25 with increase of Ha. In Ha=12, the values of the turbulent Prandtl number in the
vicinity of the wall fell into 1 for Pr=5.7 and 25. It was suggested that there was no MHD
terms in balance of the heat transfer equation; turbulent effect on heat transfer might exceed
that on momentum transfer as the limiting case of a turbulent-laminar transition status in
Ha=12.
Figure 12 shows the time scale ratio for Pr=5.7 and 25. In non-MHD flow, time scale ratio
had the weak peak at the buffer region for Pr=25 and 49 (Schwertfirm & Manhart, 2007
pointed out that). Time scale ratio profiles in MHD cases clearly had the peak in increase of
Ha for Pr=5.7 and 25. At the buffer region, MHD effects on heat transfer might to be
corresponded to the heat transfer in a higher-Pr fluid as shown in Figs. 9 and 12. However,
these close to the wall might act on like a lower-Pr fluid as shown in Fig. 11.


10
0
10
1
10
2
0

0.5
1
1.5
Pr=25.0
Ha= 0.0
Ha= 8.0
Ha=12.0
y
+
(K
θ

θ
)/(Pr*K/ε)
10
0
10
1
10
2
0
0.5
1
1.5
Ha= 0.0
Ha= 8.0
Ha=12.0
y
+
(K

θ

θ
)/(Pr*K/ε)

(a) Pr=5.7, (b) Pr=25,
Fig. 12. Time scale ratio profiles
Prandtl Number Effect on Heat Transfer Degradation in
MHD Turbulent Shear Flows by Means of High-Resolution DNS

647
Since both turbulent Prandtl number and time scale ratio were one of the dominant
parameters in turbulent heat transfer modeling, change of profiles in increase of Ha might
be caused the aggravation of the prediction accuracy.
7. Conclusion
In this study, direct numerical simulation of MHD turbulent channel flow for Prandtl
number up to Pr=25 were performed. The adequacy of the present DNS data was verified by
comparison with the DNS data fully-resolved the Batchelor length scale. As the results, the
MHD turbulent heat transfer characteristics in Pr=25 were reported for the first time.
Maximum heat transfer degradation in the low-Pr fluid was no more than 5% of the non-
MHD condition. On the other hands, heat transfer degradation in the high-Pr fluids (Pr=5.7
and 25) reached up to 30%. The similarity of heat transfer degradation in high-Pr MHD
flows seemed be existed.
On the MHD heat transfer in high-Pr fluids, effects of turbulent diffusion were relatively
larger. Turbulent Prandtl number and time scale ratio were considerably changed with
increase of Ha.
The scaling of MHD heat transfer in high-Pr fluids was not understood yet. For the high-Ha
and Re
τ
condition (Ha>5, Re

τ
>250), Boeck et al. 2007 reported the similarity of MHD mean
velocity profiles on the parameter R(: Hartmann Reynolds number). To discuss the scaling
of MHD heat transfer, we need DNS data of higher-Re and Ha conditions. In such cases,
present DNS procedure by using a different resolution for flow and high-Pr temperature
field will demonstrate a great advantage.
8. Acknowledgment
Present DNS were conducted by using the T2K open supercomputer at ACCMS and IIMC,
Kyoto University. This study was supported by the Global COE program “Energy Science in
the Age of Global Warming” and a Grant-in-aid for Young Scientists (B), KAKENHI
(21760156) MEXT, Japan.
9. References
Batchelor, G.K., (1959), Small-scale variation of convected quantities like temperature in
turbulent fluid. Part 1. General discussion and the case of small conductivity,
Journal of Fluid Mechanics, Vol.5, pp.113–133.
Blum, E.YA., (1967), Effect of a magnetic field on heat transfer in the turbulent flow of
conducting liquid, High Temperature,Vol. 5,pp. 68-74.
Boeck, T., Krasnov, D., and Zienicke, E., (2007), Numerical study of turbulent
magnetohydrodynamic channel flow, Journal of Fluid Mechanics, Vol.572, pp.179-
188.
Lee, D. & Choi, H., (2001), Magnetohydrodynamic turbulent flow in
a channel at low
magnetic Reynolds number, Journal of Fluid Mechanics, Vol.429, pp.367–394.
Na, Y. & T.J. Hanratty, T.J., (2000), Limiting behavior of turbulent scalar transport close to a
wall, International Journal of Heat and Mass Transfer, Vol.43 , pp.1749-1758.
Patterson, S. & Orszag, S.A., (1971), Spectral calculations of isotropic turbulence: Efficient
removal of aliasing interactions, Physics of Fluids, Vol.14, pp.2538-2541.

Developments in Heat Transfer


648
Reed, C.B. & Lykoudis, P.S., (1978), The effect of a transverse magnetic field on shear
turbulence Journal of Fluid Mechanics, Vol.89, pp.147-171.
Sagara. A., Motojima, O., Watanabe, K., Imagawa, S., Yamanishi, H., Mitarai, O., Sato, T.,
Chikaraishi, H. and FFHR Group, Design and development of the Flibe blanket for
helical-type fusion reactor FFHR, Fusion Engineering and Design, Vol.29, pp.51-56.
Satake, S., Kunugi, T., Takase, T., and Ose, Y., (2006), Direct numerical simulation of
turbulent channel flow under a uniform magnetic field for large-scale structures at
high Reynolds number, Physics of Fluids, Vol.18, 125106.
Schwertfirm, F. & Manhart, M., (2007), DNS of passive scalar transport in turbulent channel
flow
at high Schmidt numbers, International Journal of Heat and Fluid Flow, Vol.28,
pp. 1204–1214.
Simomura Y., (1991), Large eddy simulation of magnetohydrodynamic turbulent channel
flows under a uniform magnetic field, Physics of Fluids A 3, pp.3098-3106.
Yamamoto, Y.,Kunugi, T., Satake, S., and Smolentsev, S. (2008), DNS and k–ε model
simulation of MHD turbulent channel flows with heat transfer, Fusion Engineering
and Design, Vol.83, pp.1309-1312.
Yokomine, T., Takeuchi, J., Nakaharai, H., Satake, S., Kunugi, T., Morley, N.B., and M. A.
Abdou, M.A., (2007), Experimental investigation of turbulent heat transfer of high
Prandlt number fluid flow under strong magnetic field, Fusion Science and
Technology, Vol.52, pp.625-629.
33
Effective Method of
Microcapsules Production for Smart Fabrics
Luz Sánchez-Silva, Paula Sánchez and Juan F. Rodríguez
Department of Chemical Engineering/University of Castilla-La Mancha
Spain

1. Introduction

Nowadays, the attempts in the textile and clothing industry have moved towards more
innovative and high quality products in order to differentiate themselves and be more
competitive. The new demand for innovative textiles is increasingly oriented to match
material innovation, new technologies and fashion. The new products are not only different
for their lines, patterns and volumes but also for what they can do. Recently, microcapsules
have been applied to many functional and technical textiles. Examples of this include
fragrances, aromatic deodorants, cosmetics, insect repellents, antibiotics, polychromic, drug
delivery for medical textiles and thermo-regulating systems. This kind of fabrics, that
introduces new functionalities without affecting the look and feel of the textile, is commonly
denominated as smart textiles.
Microencapsulated phase change materials (PCM) can be incorporated into textile structures
to produce fabrics of enhanced thermal properties. A thermo-regulating fabric is an intelligent
textile that has the property of offering suitable response to changes in external temperature
changes or to external and environmental stimuli. The level of thermal comfort depends on
the heat exchange between the human body and the environment that surrounds it.
Microcapsule production may be achieved by means of physical and chemical techniques.
The use of some techniques has been limited to the high cost of processing, regulatory
affairs, and the use of organic solvents, which are concern for health and the environment.
In this way, a method based on a suspension like polymerization process for the encapsulation
of phase change materials has been selected. This PCM encapsulation method is simply,
inexpensive and technically easy.
Suspension like polymerization involves the dispersion of the monomer or monomers,
mainly as a liquid in small droplets, into an agitated stabilizing medium consisting of water
containing small amounts of suspension agents and without using aqueous phase inhibitors
of secondary nucleation or modifiers. The initiator is dissolved in the monomer-PCM
mixture and PCM material does not take part on the polymerization kinetic. In the proper
conditions the polymer reacts mainly in the interface of the drop forming a shell around the
PCM core since this interface is the only locus of polymerization. However, not all the
recipes and conditions for suspension polymerization favour the formation of the polymer
at the PCM/water interface all around the drop as desired and microparticles without

complete phase separation into capsules are obtained.

Developments in Heat Transfer

650
Well-known PCM are linear chain hydrocarbons known as paraffin waxes (or n-alkanes),
hydrated salts, polyethylene glycols (PEGs), fatty acids and mixture or eutectics of organic
and non-organic compounds. PCM materials absorb energy during the heating process as
phase change takes place and release energy to the environment in the phase change range
during a reverse cooling process.
The required properties for a phase change materials depend on their specific application in
textile fields. A wide spectrum of phase change materials are available with different heat
storage capacity and phase change temperature. Different types of commercial PCMs can be
encapsulated by means of suspension polymerization process. Rubitherm
®
RT20,
Rubitherm
®
RT27, Rubitherm
®
RT31, Petrepar
®
n-C14 and Petrepar
®
n-C-13 have
demonstrate their capability to be encapsulated and their thermal abilities to absorb and
release energy. Their physical and chemical properties make them very attractive for
thermal storage.
Thermal properties, air permeability, moisture vapour permeability and moisture regain of
materials also influence the heat balance of the body and, consequently, affect clothing

comfort (Ren & Ruckman, 2004). The incorporation of PCM microcapsules to textiles can
affect other comfort-related properties and hand of the materials adversely, especially when
the topical application of microcapsules results in drastic changes in the surface
characteristics of materials. The extent of change in these properties depends on the loading
amount of PCM microcapsules (Shin et al., 2005).
Several methods of incorporating PCM microcapsules into a fibrous structure have been
developed. The microcapsules can be applied by stamping works, exhaustion dyeing,
impregnation, spraying and coating or by direct incorporation in the fibre without highly
modifying its touch and colour (Monllor et al., 2009; Dixit & Goal, 2007; Rodrigues et al.,
2009). In previous applications of PCM technology in the textile industry, for garments and
home furnishing products, microencapsulated PCM were incorporated into acrylic fibers
(Bryant & Colvin, 1988) or polyurethane foams (Colvin & Bryant, 1996) or were embedded
into a coating compound and topically applied to a fabric (Bryant & Colvin, 1994). Shin et
al., (2005) incorporated melamine-formaldehyde microcapsules containing eicosane on
polyester knit fabrics by means of a pad dry cure method with a polyurethane binder.
Mengjin et al., (2008) developed a new kind of thermo-regulating fiber based on PVA and
paraffin. Furthermore, Onder et al., (2008) studied the microencapsulation of three types of
paraffin waxes by complex coacervation to improve thermal performances of woven fabrics.
Recently, Koo et al. (2009) have attempted to demonstrate the application of PCM
microcapsules on waterproof nylon fabrics and to enhance thermal insulation effect with
ceramic materials (SiC) by using a dual coating method.
Binders play a crucial role in microcapsule coating formulation for various textile materials,
as they are required to fix microcapsules on textile supports permanently. To a large extend,
binders determine the quality, durability and washability of textile materials with
microencapsulated ingredients. Some of the most frequently used binders in textile are
water-soluble polymers, such as starch and modified starches, carboxymethyl cellulose;
synthetic latexes, such as styrene-butadiene, polyvinylacetate or acrylate latexes; and
aminoaldehyde resins (Boh & Knez, 2006).
In our previous work, the fixation of PCM microcapsules containing paraffin with a melting
point around 40ºC, into a cotton textile substrate by means of a coating technique were

carried out. Furthermore, the influence of different coating formulations and mass ratio of
microcapsules to coating formulation were evaluated in order to obtain an adequate textile

Effective Method of Microcapsules Production for Smart Fabrics

651
with thermo-regulating properties (Sánchez et al., 2010). The coating fabric with 35 wt.% of
microcapsules added related to commercial coating binder (WST SUPERMOR
®
) showed a
energy storage capacity of 7.6 J g
−1
, a high durability and an adequate stability after
washing, rub fastness and ironing treatments. A difference of 8.8°C for 6 s was observed for
textiles with thermo-regulating properties in comparison with a coated one without
microcapsules. The different application areas of textiles with thermo-regulating properties
imply the fixation to very different substrates. In this sense, there are few references in the
literature studying the influence of the kind of textile on the fixation of microcapsules (Koo
et al., 2009). In addition, the PCM microcapsules incorporation could degrade the original
functionalities of the textile such as soft touch, vapor or moisture permeability and wearing
comfort.
The aim of this work was to investigate the production of textiles with thermo-regulating
properties by using PCM microcapsules and a coating technique. The influence of the type
of used PCM on the heat capacity of microcapsules, the particle size distribution (PSD) and
the microcapsules yield of each experiment was studied. On the other hand, different type of
textile substrates depending on the field of their textile applications (apparel, blankets,
insulation, protective clothing) were evaluated. Furthermore, a study of thermoregulatory
effect of the coating fabrics produced was carried out using an infrared thermography
camera. Thermal properties of textile samples were examined by Differential Scanning
Calorimetry (DSC). Furthermore, Environmental Scanning Electron Microscopy (ESEM) and

Optical Microscopy (OM) techniques were used to check the presence, surface distribution,
preferred join position and to analyse the structure of microcapsules into the textile.
2. Experimental
2.1. Microcapsules synthesis
Styrene (99 wt.%) of reagent grade (Merck Chemical) previously purified by washing with
sodium hydroxide and dried with calcium chloride was used as the monomer. Benzoyl
peroxide (97 wt.%) was used as initiator (Fluka Chemical). PRS
®
paraffin wax, Rubitherm
®

RT20, Rubitherm
®
RT27, Rubitherm
®
RT31, Petrepar
®
n-C14 and Petrepar
®
n-C-13 were
used as core materials. Polyvinylpyrrolidone (K30, Mw 40,000 gmol
-1
) of reagent grade
(Fluka Chemical) was used as stabilizer and methanol to pour the samples. All these
reagents were used as received. Water was purified by distillation followed by deionization
using ion-exchange resins. Nitrogen was of high-purity grade (99.999%).
A suspension like polymerization process was used for the microcapsules synthesis. A
tubular type Shirasu porous glass membrane was used for a better control of microparticle
size. Details of the synthesis process were previously described elsewhere (Sánchez et al.,
2008b).

2.2 Preparation of textiles with thermo-regulating properties
Microcapsules were fixed into seven fabrics by means of a coating technique, using a
motorized film applicator from Elcometer model 4340 according with ASTM D-823C (ASTM
D-823-C, 1997). WST SUPERMOR
®
(supplied by Minerva Color Ltd.) were used as
commercial coating binder. In a previous study (Sánchez et al., 2010), this binder was
selected due to allow an efficient fixation of the PCM microcapsules on the fabrics. Every
sample had 200 mm of wide and 290 mm of length due to requirements of the motorized
film applicator.

Developments in Heat Transfer

652
The coating formulation consisted of WST SUPERMOR
®
commercial binder and
Rubitherm
®
RT31 microcapsules (35 wt. % of the coating mixture).
The textile substrate was set on the motorized film applicator surface assuring the fabric
with clips. In this study, the thickness selection of the coating layer was 0.1 mm to obtain a
high thermal storage. The position of the motorized film applicator and the selection
thickness was carried out manually. A dragging speed of 5 mm s
-1
was chosen to allow a
homogeneous coating along the film applicator.
Finally, the coated fabric was cured at 95 ºC for 11 minutes.
2.3 Characterization
2.3.1 Differential Scanning Calorimetry (DSC)

Measurements of melting point and latent heat storage capacities of different materials were
performed in a differential scanning calorimetry model DSC Q100 of TA Instruments
equipped with a refrigerated cooling system and nitrogen as the purge gas. Measurements
were carried out in the temperature range from -30ºC to 80ºC with heating and cooling rate
of 10 ºCmin
-1
.
Various samples of each experiment were analyzed at least three times and the average
value was recorded. DSC analyses of coating textiles from random areas were done.
Furthermore, the encapsulation ratio of the different PCM in the microcapsule was
calculated with the following equation based on enthalpy values:

% PCM content by weight = (ΔHm / ΔHpcm) x 100% (1)

where ΔHm is the enthalpy for the analysed microcapsules (Jg
-1
) and ΔHpcm is the enthalpy
of pure PCM.
In order to determine the thermal stability of the reversible phenomena of phase change, the
coated textiles were subjected to repeated cycles of melting and crystallization.
2.3.2 Environmental scanning electron microscopy (ESEM)
ESEM was used to analyze the morphological structure of the microcapsules and the
fixation and integrity of PCM microcapsules into the coating textile substrates. Textile
samples were observed by using XL30 (LFD) ESEM with a wolfram filament operating at a
working potential of 20 kV.
2.3.3 Calculation of number-average diameter and volume-average diameter
Particle size and particle size distribution (PSD) of microcapsules were determined on a
Malvern Mastersizer Hydro 2000 SM light scattering apparatus with dilute dispersions of
the particles in methanol.
2.3.4 Infrared thermography

The temperature distributions of the coated textiles with thermo-regulating properties were
evaluated by means of an infrared and visible camera Fluke Ti25. This dispositive allows to
obtain thermal and visual images in the range of temperatures from -20ºC to 250ºC with a
precision of ±2 ºC. The screen was observed from a distance of 30 cm at 24ºC. Images were
downloaded using Fluke SmartViewTM software for analysis. The coated fabrics were pre-
heated at 60ºC, time considered as zero, and then cooled to room temperature.

Effective Method of Microcapsules Production for Smart Fabrics

653
Thermal human comfort in summer conditions was tested, recording images from 25ºC to
outside temperature (35ºC), comparing a reference textile with a prototype textile with
thermo-regulating properties in contact with the body (shoulders in this specific case).
3. Results
3.1 Microencapsulation of different type of phase change materials (PCM)
The required properties for a phase change materials depend on their specific application in
textile fields. A wide spectrum of phase change material is available with different heat
storage capacity and phase change temperature. In this study different type of commercial
PCM were assayed in order to know what PCM materials are suitable to be encapsulated by
means of suspension polymerization. Thus, Rubitherm
®
RT20, Rubitherm
®
RT27,
Rubitherm
®
RT31, Petrepar
®
n-C14 and Petrepar
®

n-C-13 were assayed due to their physical
and chemical properties are very attractive for thermal storage (Table 1). All of them are
saturated hydrocarbons

PCM
Molecular
weight
(gmol
-1
)
Latent heat
of fusion
(Jg
-1
)
Melting
temperature
(ºC)
Viscosity
(mm
2
s
-1
)
at 98ºC
PRS
®
paraffin wax 168-240 206.8 40-45 2.43
Rubitherm
®

RT31 268 199.3 31 2.07
Rubitherm
®
RT27 258 214.6 28 1.64
Rubitherm
®
RT20 244 177.7 22 1.52
Petrepar
®
n-C14 198.4 225.0 3-7 0.99
Petrepar
®
n-C13 184.4 134.4 (-7)-(-5) 0.88
Table 1. Properties of different types of PCMs investigated
Figure 1 shows the particle size distributions (PSDs) in volume (Figure 1a) and in number
(Figure 1b) of microcapsules obtained after the polymerization process using these PCM
materials. It can be seen from Figure 1a that Petrepar
®
n-C14 and n-C13 exhibit bimodal
PSDs with particles sizes smaller than 115 μm. However, PRS® paraffin wax, Rubitherm
®

RT31, RT27 and RT20 shows unimodal PSDs ranging in the interval between 149 to 251 μm.
In all experiments a big difference between the average particle size in volume and in
number was observed due to the heterogeneous sizes of obtained microcapsules. This
behaviour was reported in previous works (Sánchez et al., 2007; Sánchez et al., 2008a;
Sánchez et al., 2008b).
Table 2 reports average diameters (dp
0.5
) in volume and in number, storage energy

capacities and amount of PCM encapsulated of microcapsules produced using different
PCMs. The mean diameter in number of the microcapsules increases as described:
Rubitherm
®
RT27>PRS
®
paraffin wax>Rubitherm
®
RT31> Petrepar
®
C-14>Petrepar
®

C-13>Rubitherm® RT20. However, the average diameter in volume increases in the following
way: Rubitherm
®
RT27>Rubitherm
®
RT31>Rubitherm
®
RT20>PRS
®
paraffin wax>Petrepar
®

n-C14>Petrepar
®
n-C13. Therefore, the average diameter of the microcapsules depends on

×