Tải bản đầy đủ (.pdf) (10 trang)

Electric Machinery Fundamentals (Solutions Manual) Part 3 docx

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (78.55 KB, 10 trang )


121

(

)
3570 r/min

(
2
)

f

m
n

P
=

=

=

fl1

120

120

59.5 Hz





The

no-load

frequency

of generator 2 corresponds to

a

frequency of

(

)
1800 r/min

(
4
)

f



m
n


P
=

=

=

nl2


120

120

60.00 Hz



The full-load frequency of generator

2 corresponds

to a frequency of

(

)
1785 r/min


(
4

)

f



m
n

P
=

=

=

fl2


120

120

59.50 Hz




(a)

The

speed droop of generator

1 is

given by


n

n




SD
1



nl

fl

100%
=




3630 r/m
=

in

3570 r/min

100%

1.


68%
=


n
fl

3570 r/min


The speed droop of generator 2 is given by


n

n





DS

2



nl

fl

100%

18
=



00 r/m
=

in

1785

r/min


100%

0.


84%
=


n
fl

1785 r/min


(b)

The power supplied by generator 1

is given

by

(

)
=




1 1P
P

s

nl1
f


sys
f



and the power

supplied by generator

1 is given by

(

)
=



2 P 2
P


s

nl2
f


sys
f



The power curve’s

slope for generator 1 is


s



P




0.1
M
=

=




W


0.1 MW/
=

Hz

1
P






nl

fl

6
f

f

0.5 Hz


59.5

Hz


The power curve’s

slope for generator 1 is


s
P

2




P




0.07
=

=

5 MW



0.150 M
=

W/Hz





nl

fl

60
f

f

.00 Hz

59.50 Hz


The

no-load frequency of generator 1 is 60.5 Hz and the no-load frequency of generator 2 is 60 Hz.

The
total


power that

they must supply is

100

kW,

so the system frequency

can be

found

from the equations


=

+

LOAD 1 2
P

P

P



(

)
=



(
+

)


LOAD 1 nl1
P

s

sy
f

s
f

2 nl2
s

sy
f


sP P
f



(

)
(

)

(

)
(

)
=



+




100 kW

0.1 MW/Hz


60.5

Hz

sys

0.15 MW/Hz

60.0 Hz

sys
f

f


(

)

(

)

100 kW

6050 kW

0.10 MW

=



/Hz


(

)

sys

9000 kW
+

0.15 MW


/Hz

sys
f

f



0.25 MW/Hz


f
sys

6050 kW

9000 kW
=

+

100

kW




f
sys




14,

950 kW


59.8 Hz
=


=


0.25 MW/Hz


(c)

The power supplied by generator 1

is


122

(

)

(

)
=



=



(



)

=

1 1P
P

s

nl1
f


sys
f


0.1 MW/Hz

60.5 Hz

59.8

Hz

70 kW



The power supplied

by generator 2 is

(

)

(

)
=



=





(

)


=


2 2P
P

s

nl2
f


sys
f


0.15 MW/Hz

60.0 Hz

59.8

Hz

30 kW


(d)

If

the


terminal

voltage is

460

V, the operators of the generators must increase the field currents on
both generators simultaneously. That

action

will increase the

terminal

voltages

of

the

system

without
changing the power sharing between

the

generators.



5-9.

Three physically identical synchronous

generators are operating in parallel. They are all

rated

for

a

full
load

of 3 MW

at

0.8

PF

lagging.

The

no-load


frequency of generator A is 61 Hz, and

its speed

droop

is 3.4
percent. The no-load frequency of generator B

is 61.5 Hz, and

its speed droop is

3

percent.

The no-load
frequency of generator C is 60.5

Hz, and

its speed droop is 2.6

percent.

(a)

If


a total load consisting of

7 MW

is

being supplied by this power system, what will

the

system
frequency be

and how will the power

be shared

among

the

three

generators?


(b)

Create a plot showing


the

power supplied by each generator as a

function

of

the

total

power

supplied to
all

loads

(you

may

use

MATLAB to create this plot).

At what load does one of the generators exceed
its ratings?


Which generator exceeds its ratings

first?


(c)

Is this

power sharing

in

(a)
acceptable? Why or why not?


(d)

What

actions could

an operator

take to

improve the real power

sharing among these generators?





S
OLUTION


(a)

Speed droop is

defined as


n

n

f

f




SD




nl

fl

100%
=





nl

fl
=

100%


fl

fl
n

f







so



f

=



f
nl
fl
SD

+

1

100


Thus,

the full-load frequencies of generators A, B, and

C are




f
fl,A




f
fl,B




f
nl,A


61 Hz

59.0 Hz

=

=

=

SD
A


3.4

1

1
+

+

100

100



f

nl,B


61.5 Hz

59.71 Hz

=

=

=


SD
B

3.0

1

1
+

+



f
fl,C



100

100



f

nl,C



60.5 Hz

58.97 Hz

=

=

=

SD
C

2.6

1

1
+

+

100

100

and the slopes

of


the power-frequency

curves are:

3 MW

1.5 MW
=

=

/Hz

S
PA


S
PB


S
PC



2
H
z




3
MW


1.676 MW
=

=

1.79 Hz

3 MW


1.961 MW
=

=

1.53 Hz





/Hz




/Hz











123

(a)

The total load

is 7 MW, so the system frequency is

(

)
=



(


)
+



(

)
+



LOAD
P

PA nl
s

A sys PB nl
f

f

s

B
f

sys
f


PC n
s

lC
f

sys
f



(

)
(

)

(
=



)
(

)
+




(


)
(

)
+




7 MW

1.5

61.0

sys
1.676

61.5

sys
1.961

60.5
f


f

sys
f




+



+



7

MW

91.5

1.
=


5.137

f

sys

=

306.2


f
sys

=

59.61 Hz

5

sys

103.07

1.676

sys

118.64

1.961

sys
f


f

f







The power supplied

by each generator

will

be

(

)

(

)
=




=



(



)

=

P

s

nl
A

P

A
A

f


sys
f



1.5 MW/Hz

61.0 Hz

59.61

Hz

2.09

MW

(

)

(

)
=



=


(




)

=

P

s

nlB
P BB
f


sys
f


1.676 MW/Hz

61.5 Hz

59.61 Hz

3.17

MW

(


)

(

)
=



=


(



)

=

P

s

nlC
P CC
f


sys

f


1.961 MW/Hz

60.5 Hz

59.61

Hz

1.74

MW


(b)

The

equation in part

(a)

can be re-written

slightly to express system frequency

as


a

function of load.

(

)
(

)

(

)
=



(

)
+


(

)


(


)
+




LOAD

1.5

61.0

sys

1.676

61.5
P

f

sys

1.961

60.5
f

sys

f


=



+



+



LOAD

91.5

1.5

sys

103.07

1.6
P

f


76

sys

118.64

1.96
f


=


5.137

sys

313.2
f

P

LOAD

1

sys
f







f
sys


=

313.2



L
P

OAD

5.137


A

MATLAB

program

that


uses this equation to determine the power sharing among the generators as a
function of load

is shown

below:


% M-file: prob5_9b.m

%

M-file to calculate and

plot the

power sharing

among

% three generators

as

a function of load.


% Define

values for this


generator

fnlA = 61.0;

% No-load freq of Gen

A
fnlB = 61.5;

% No-load freq of Gen

B
fnlC = 60.5;

% No-load freq of Gen

C
spA =

1.5;

% Slope of Gen A (MW/Hz)
spB =

1.676;

% Slope of Gen B (MW/Hz)
spC =


1.961;

% Slope of Gen C (MW/Hz)
Pload

= 0:0.05:10;

% Load in MW


% Calculate

the system frequency
fsys = (313.2 -

Pload) ./ 5.137;


% Calculate

the power

of

each generator

PA =

spA .* (


fnlA -

fsys);
PB =

spB .* (

fnlB -

fsys);
PC =

spC .* (

fnlC -

fsys);


% Plot the power sharing

versus load
plot(Pload,PA,'b-','LineWidth',2.0);


124

hold on;

plot(Pload,PB,'k ','LineWidth',2.0);

plot(Pload,PC,'r ','LineWidth',2.0);
plot([0 10],[3

3],'k','LineWidth',1.0);
plot([0 10],[0

0],'k:');

title

('\bfPower Sharing

Versus Total Load');

xlabel ('\bfTotal Load (MW)');

ylabel ('\bfGenerator

Power

(MW)');

legend('Generator A','Generator B','Generator C','Power

Limit');

grid on;

hold off;



The

resulting plot is

shown below:



This plot reveals

that there

are power sharing problems both for high loads and

for

low loads.

Generator

B is

the

first

to exceed its ratings as load

increases. Its rated power is reached


at a total load of 6.45 MW. On

the other hand, Generator

C gets into trouble as the total

load

is

reduced.

When the total

load

drops to

2.4

MW, the direction of power flow reverses in

Generator C.


(c)

The power sharing in


(a)

is not acceptable, because

Generator 2 has

exceeded its power limits.


(d)

To improve the

power

sharing among the three generators in

(a)

without affecting the operating
frequency

of

the

system,

the


operator

should

decrease

the

governor

setpoints

on

Generator

B

while
simultaneously

increasing them in Generators

A and C.


5-10.

A paper mill has


installed three steam generators (boilers)

to

provide

process

steam

and also to use

some

its
waste

products as an

energy source. Since there is extra

capacity,

the mill has installed

three 5-MW
turbine

generators to


take

advantage of

the

situation.

Each generator is a 4160-V 6250-kVA 0.85-PF-
lagging two-pole

Y-connected

synchronous

generator with a

synchronous reactance of 0.75

&
and

an
armature resistance of 0.04

&
. Generators 1 and 2 have a characteristic power-frequency

slope


s
P
of 2.5

MW/Hz,

and generators 2 and

3

have

a

slope of 3 MW/Hz.

(a)

If the no-load frequency of each of the three generators is adjusted to 61 Hz, how

much

power will

the
three machines

be supplying when

actual system frequency


is 60

Hz?





125

(b)

What

is

the

maximum

power

the

three generators can supply in

this condition without the ratings of one
of them


being

exceeded? At what

frequency

does this limit occur?

How much

power

does

each
generator

supply at that

point?


(c)

What

would have to

be done to get all three generators to supply their rated real and reactive powers


at an
overall operating frequency

of

60 Hz?


(d)

What would

the

internal

generated

voltages of the

three generators be under this

condition?




S
OLUTION



(a)

If the system frequency is 60 Hz and the no-load

frequencies

of

the

generators

are

61

Hz,

then

the
power supplied by the generators will be

(

)

(


)
=



=


(

)


=

1 1P
P

s

nl1
f


sys
f


2.5 MW/Hz


61 Hz

60 Hz

2.5 MW


(

)

(
=



=


)(

)


=

2

P


2
P

s

nl2
f


sys
f


2.5 MW/Hz

61

Hz

60 Hz

2.5 MW


(

)

(
=




=


)(

)


=

3

P

3
P

s

nl3
f


sys
f



3.0 MW/Hz

61 Hz

60

Hz

3.0 MW


Therefore the total power supplied

by the generators is

8

MW.


(b)

The maximum

power supplied by any

one generator is (6250 kVA)(0.85)

=


5.31

MW.

Generator

3

will be

the

first

machine to reach that

limit. Generator 3

will supply this power at a frequency

of

(

)
(

)
=



5.31 MW

3.0

MW/Hz

61

Hz

f

sys

f

sys

=

.5 9

Hz23


At this

point the power supplied by


Generators 1 and 2 is

=

=

(

)


(

)
=


(

)

=

1 2
P

P

1P
s


nl1
f


sys
f


2.5 MW/Hz

61 Hz

59.23 Hz

4.425 MW


The total power

supplied by

the

generators

at this condition is 14.16 MW.


(c)


To get each of the generators to supply 5.31 MW at

60

Hz,

the

no-load

frequencies

of

Generator

1
and

Generator

2

would have to be adjusted to 62.12 Hz, and the no-load frequency of Generator 3 would
have

to

be


adjusted

to

61.77

Hz.

The field currents of the three generators must then be adjusted to get
them

supplying

a power

factor

of

0.85 lagging. At that point, each generator will be supplying its rated
real and reactive power.


(d)

Under

the


conditions

of

part

(c)
, which

are

the rated conditions

of the

generators, the

internal
generated

voltage would

be given by


=

+

+


A

A
E

V


A
I

S

A
R

jX

I


The phase

voltage of the

generators is 4160 V /

3


=

2402 V, and since the generators are Y-connected,
their rated current is




S
I

I
=

=




62
=

50 kVA


867
=

A


3

3

(

)
4160

V

A

L

T
V


The power factor is

0.85 lagging,

so

I

A
867


31.
=



8


A
°

.

Therefore,


=

+

+

A
A
E

V


A

I

S A
R

jX

I


2402

0

(
0.04

)(

)


867

31.8

A

(
0.


)(

)
75

867

31.8

A

E

A

=



°

+

&






°

j
+

&





°



126

×