Tải bản đầy đủ (.pdf) (101 trang)

Acrobat AVCN n l dai hoc cong nghiep

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (5.88 MB, 101 trang )

CONTENTS

Contents................................................................................................................ 1
Preface .................................................................................................................. 2
Chapter 1: Classification of air conditioners........................................................ 3
Chapter 2: Components...................................................................................... 22
Chapter 3: Classification by expansion methods ............................................... 50
Chapter 4: Installation ........................................................................................ 66
Chapter 5: Troubleshooting................................................................................ 87
Chapter 6: Catagogues ..................................................................................... 102

1


Preface
This textbook is complied with the purpose of using for Technology of Heat,
Air conditioning and Refrigeration Students in Ho Chi Minh University of Industry
and for the junior and middle class service technicians.
Although the contents and expressions may be sometimes inadequate, the
minimum necessary knowledge and concepts for service technicians are edited to
make them understood easily. We hope you will use the textbook effectively.

Authors
Nguyen Tien Canh
Nguyen Thi Tam Thanh

2


Chapter 1: Classification of air conditioners
1.1 Air conditioning........................................................................................................4


1.2 What is comfortable air? ..........................................................................................5
1.3 Classification of air conditioners..............................................................................5
1.3.1 Classification by expansion methods...............................................................5
1.3.2 Classification by heat rejection methods .........................................................6
1.3.3 Classification by structures ..............................................................................8
1.3.4 Classification by locations of compressor .....................................................11
1.3.5 Classification by using positions ...................................................................12
1.3.6 Classification by installation methods of fan coil (indoor) units...................12
1.3.7 Table of classification of air conditioners......................................................13
1.3.8 Classification of central air conditioning systems .........................................14
1.3.9 Configuration of air conditioning system ......................................................20

Chapter 1: Classification of air conditioner

3


Chapter 1: Classification of air conditioners
1.1 Air conditioning
Air conditioning is defined as “the
process of treating air so as to control
simultaneously
its
temperature,
humidity, cleanness and distribution to
meet the requirements of the conditioned
space”.
As indicated in the definition, the
important actions involved in the
operation of an air conditioning system

are:
(1) Temperature control
Room temperature is controlled to the
predesigned dry bulb temperature by
cooling or heating room air.

(2) Humidity control
Room air is controlled to the predesigned
relative humidity by humidifying or
dehumidifying room air.

Fig. 1-1 Room air is cooled or heated

Fig. 1-2
Room air is humidified or dehumidified

Fig. 1-3 Room air is cleaned by
removing dust and dirt from it

(3)
Air filtering, cleaning and
purification
Room air is cleaned by removing dust
and dirt from the air.
Fig. 1-4 Controlled air is distributed
throughout a room.
(4) Air movement and circulation
Air which is controlled in temperature
and humidity and cleaned is distributed
throughout a room. As a result, room air

can be maintained evenly in temperature
and humidity conditions.
Chapter 1: Classification of air conditioner

4


Temperature, humidity, cleanness and distribution of air are called "Four elements of
air conditioning". By controlling these four elements, room air can be comfortably
maintained regardless of outdoor temperature. Should these four elements be replaced
with the works of the air conditioner, the room air is drawn in the air conditioner,
where dust and dirt are removed from the air by the air filter (cleanness of air) and is
sent to the evaporator, where temperature of the air is reduced by evaporation of the
refrigerant (temperature), and at the same time, humidity in the air is removed as
condensation (humidity). As a result, the air distributed from the air conditioner is cool
and crisp and can be distributed throughout the room by the evaporator fan
(distribution of air stream). Such works are repeated so as to perform air conditioning.
1.2 What is comfortable air?
The heat and coldness that the man feels
Fig. 1.5
depend not only on air temperature (dry bulb
temperature), but also on humidity and
distribution of air.
In addition, the general comfortable zone is
within the range shown with oblique lines in
Fig. 1-5, although comfort differs with the
distinction of sex, age and work.
In case of cooling, however, although room air
conditions are within the comfortable zone, the
room air is not always optimum. For example,

if temperature difference between indoor and
outdoor is nearly 10 0C because room air is controlled so as to be within this zone, one
feels coolness and heat strongly when he enters in and out of a room, which makes
him feel uncomfortable.
Such discomfort is called "cold shock". Consequently, it is important to control room
air temperature so as not to feel "cold shock" during cooling by adjusting the
thermostat. The optimum temperature difference between indoor and outdoor is from 3
to 6 0C in consideration with health and economy.
1.3 Classification of air conditioners
The main stream of air conditioners is packaged (unitary) air conditioners, but
they are gradually diversified in shapes and kinds owing to building utilities.
There are many kinds of classifications of air conditioner but the representative
classifications will be explained below.
1.3.1 Classification by expansion methods
Chapter 1: Classification of air conditioner

5


Expansion methods are largely classified in two types; i.e, direct expansion and
indirect expansion
The direct expansion method is that heat is directly exchanged between air to be
conditioned and the refrigerant, and the air conditioners adopt this method.
The indirect expansion method is that heat is exchanged indirectly between air to
be conditionned and the refrigerant by means of water or brine. The systems
combining the chillers or centrifugal water chillers with fan coil units adopt this
method.
Expansion method
Direct expansion
Indirect expansion

Fig. 1-6 Direct expansion

Fig. 1-7 Indirect expansion

1.3.2 Classification by heat rejection methods
Heat rejection methods are largely classified in two types; i.e. water cooled type by
means of water, and air cooled type by means of air.
(As the recent tendency, the air cooled type air conditioners which are free from
maintenance work increase)
Chapter 1: Classification of air conditioner

6


Air conditioners

Air cooled type
Water cooled type
Table 1-1: Features of air cooled and water cooled types
Items

Air cooled type

Water cooled type

1. Condensing
medium

- Out door air.


- Well water, city water.
- Cooling tower water.

2. Incidental works

- Power supply.
- Refrigerant piping (split type
only)

- Power supply, cooling water
piping.
- Pump for well water or water
circulating pump for cooling
tower.

3. Cooling capacity - Approx. 2100-2500kcal/h
per 0.75 kW

- Approx. 3000 kCal/h

4. Noise

- Comparatively high (outdoor unit) - Low

5. Check points

- Conditions of outdoor air intake
(chemicals, dust and dirt)
- Short-circuit of distributed air
Outdoor air temp.


Fig. 1-8 Water cooled type

Chapter 1: Classification of air conditioner

- Quantity and quality of cooling
water.
- Position of a cooling tower.

Fig. 1-9 Air cooled type

7


1.3.3 Classification by structure

Table 1-2: Features of Single packaged type and Split type
Items

Single packaged type

Split type

Structure

- One package type with all necessary
components incorporated.

Installation
work


- Piping work is required.
- Incorporation of all necessary
- Through holes must be made in the
components results in heavy weight
wall.
per unit.
- No piping work requires no skillful
piping worker, while the Roof top type
requires duct work.

Location of
installation

- In the case of indoor installation, a
large dead space is required due to the
floor installation.

- The indoor unit is light in weight
and requires a minimal floor space.
- The outdoor unit has a large
flexibility of the installation site.

Noise
Problem

- The indoor installation requirement
results in operation at a high noise
level including the compressor.
- By the central system, airflow sound

is only heard in the room. Therefore,
superb duct design enables low-noise
operation.

- Except for remote condenser type,
no compressor noises remain in the
room.
- On all types incorporating the
expansion valve (or capillary tube) in
indoor unit, refrigerant passing sound
is heard.

Chapter 1: Classification of air conditioner

- Indoor units and outdoor units are
manufactured independently.

8


Fig. 1-10 Window type

Fig.1-11 Roof top type (UAT)

Table 1-3: Features of Split-pair and Multi-system
Items

Pair System

Multi-system


Installation
Work

- Increasing the number of
applicable rooms increases the
number of outdoor units. As a
result, the number of through holes
in the distribution pipes increases.
- The work itself is easier than that
for multisystem, thus required no
skills of a high level.

- Even though there are a number of
applicable rooms, one outdoor unit can
cover. Therefore, the number of through
holes in the pipes can be minimized.
- The work itself becomes more
complicated than that for Pair System
due to additional work such as brazing.

Location of
Installation

- In the case of a system of multiple
outdoor units, larger space is
required.

- Less number of outdoor units achieves
less floor space required


Control

- It is hard to perform the
centralized control of a multiple of
pair systems.

- There are a number of models, which
enable the centralized control of a large
number of indoor units

Noise
problem

- The more outdoor units are
provided, the noise source is
dissipated.

- Since the noise source is concentrated
on one place, it is convenient to take
countermeasures such as the installation
of noise insulation wall.

Chapter 1: Classification of air conditioner

9


Table 1-4: Features of single packaged type and split type
Items


Single packaged type

Split type

Installation work
(thru hole)

A large hole is necessary for heat
radiation (for ducting or installation)

A small hole is necessary for
refrigerant piping.

Operation noise
(Indoor side)

Compared with the split type.
Operation noise of the window type
is comparatively large.

Compared with the single packaged
type, operation noise is small, but
take heed of noise of the outdoor unit.

Position of
installation

Since hot air is extracted, one side of Two refrigerant pipes and link wiring
connect two units.

a room should be faced outdoors.
(only window type)

Fig. 1-12 Split type (Pair system)

Chapter 1: Classification of air conditioner

Fig. 1-13 Split type (Multi-system)

10


1.3.4 Classification by locations of compressor
(In case of the split type air conditioners)
Indoor units

Outdoor units
Condensing unit
(comp. )

Split type air
conditioners

Fan coil unit

Remote condenser
type

Remote condenser
Indoor unit

(comp.)

Fig. 1-14 Split type

Fig. 1-15 Remote condenser type

Chapter 1: Classification of air conditioner

11


1.3.5 Classification by using positions
Air conditioners are largely classified in the residential use, commercial use and the
industrial use.
In general, residential air conditioners are referred to as room air conditioners and
commercial and industrial air conditioners as packaged air conditioners.
Residential use

Room air conditioners
Sky air series

Air conditioner
Commercial use and
industrial use

Packaged Air
conditioners
Air conditioner for
general purposes


1.3.6 Classification by installation methods of fan coil (indoor) units
Kinds

Rough sketch

Flour mounted type

Fan coil
(Indoor
unit)

The unit is installed on the
floor and is capable of
distributing the conditioned air
widely.

Wall mounted type

The unit is installed at the
middle of the wall. Since the
unit is of the thin type, the
room space can be used
effectively.

Ceiling suspended
type

The unit is suspended from the
ceiling and distributes the
conditioned air horizontally.

Namely, not only the floor
area, but also the wall face can
be used effectively.

Ceiling mounted
cassette type

The unit is installed in the
ceiling,
conditioned
air
distributes to the room by duct
and air terminal system.

Ceiling concealed
type

The unit is installed in the
ceiling, so room space can be
fully used and is good from the
interior designing point of
view.

Chapter 1: Classification of air conditioner

12


1.3.7 Table of classification of air conditioners


Chapter 1: Classification of air conditioner

13


1.3.8 Classification of central air conditioning systems
There are several classification methods available for the air conditioning systems.
This section describes the classification by decentralization degree and thermal
transfer medium of air conditioners.
a. Classification by decentralization degree of air conditioners
The decentralization degree methods are classified into centralized type (or central
type) and individual type, and also into the in-between types such as each floor type
and decentralized type.
™ Centralized type
The central type is that air conditioning is performed over several floors through largesized air conditioners and others, and used for air conditioning aimed at large area
such as buildings.
™ Each floor type
The each floor type is that air conditioning is performed by floor and used when each
floor has different intended use and time zone to be air-conditioned.
™ Decentralized type
The centralized type is that air conditioning is performed by partitioning a room into
several air-conditioning zones and installing air conditioners in each zone in
decentralized manner. This system is used to segment the indoor space.
™ Individual type
The individual type is that air conditioning is performed by installing individual air
conditioner for each room and used for small-sized air conditioning system such as
that for houses and stores.
* Lately, in terms of operation control, inspection/ maintenance, energy saving, and
others, the each floor type and the decentralized type have been increasingly
introduced, compared to the centralized type.

b. Classification by thermal transfer medium
™ Total air method
The total air method is that conditioned air from the air conditioner is fed to each room
through duct. Since heat is all transferred by means of air, this method is referred to as
total air method.
The total air method enables the intake of outdoor air, thus making it favorable in
order to upgrade the indoor air cleanliness factor. However, air has a low heat capacity
and requires larger ducts in size according to the airflow rate, thus resulting in
increased number of restrictions in installation.
™ Total water method

Chapter 1: Classification of air conditioner

14


The total water method is that heat transport up to the inside of room is all performed
by means of water. The fan coil unit type represents this method. It is a convenient
method to perform air conditioning, while being behind other methods in terms of
keeping the air cleanliness factor constant because indoor air is to be circulated for air
conditioning.
™ Water-air method
The water-air method is that indoor air-conditioning is performed in combination of
conditioned air from the air conditioner and chilled water from chiller or else. This
method performs air conditioning by means of both air and water, thus being referred
to as water-air method. The typical example is that the fan coil unit type supports the
perimeter area of room (perimeter zone) while the single duct type supports the central
area of the room (interior zone).
™ Refrigerant method
The refrigerant method is that indoor air-conditioning is performed through making

use of evaporation and condensation effect of fluorocarbon gas (Flon gas).
According to the innovation of air conditioning technology in recent years, this
method is widely used regardless of the sizes of buildings.
Compared to methods making use of water or air, this method will has advantages in
equipment costs, energy consumption, installation space, maintenance costs, and
others. The following figures show the examples of respective installations.
• Room air conditioner
The room air conditioner is an air conditioning system installed at home and the pair
type of room air conditioners, which indoor unit and outdoor unit are installed in a
pair, is currently the mainstream. Besides the pair type, the multitype, which enables
the installation of 2 to 3 indoor units in a system, is available.
• Package air conditioner for business use
Generally, as the air conditioning system used at any other place than home, the
package air conditioners are used in a variety of ways for diversified applications such
as stores, offices, plants, and buildings. Besides those for plant use, there is a wide
choice of variations available for indoor units.
Currently, the ceiling mounted cassette types come into common use, and the support
of optional accessories enables the incorporation with air cleaning and humidifying
functions.

Chapter 1: Classification of air conditioner

15


Fig. 1-15 Total air method (Example of typical installation)

Chapter 1: Classification of air conditioner

16



Fig. 1-16 Total water method (Example of typical installation)

Chapter 1: Classification of air conditioner

17


Fig. 1-17 Water-air method (Example of typical installation)

Chapter 1: Classification of air conditioner

18


Fig. 1-18 Refrigerant method (House, store, office, plant, building)

Chapter 1: Classification of air conditioner

19


1.3.9 Configuration of Air Conditioning System
Numbers of air conditioning systems, including the total air method, total water
method, and water-air method, consist of the following equipment.
a. Heat source unit
The heat source unit is used to produce chilled water, hot water or vapor required for
air conditioners. This unit consists of heat source units such as chiller (e.g. turbo
chiller and water chilling unit), absorption type chiller/ water heater, and boiler

together with various equipment required to operate the heat source units such as
pump, cooling tower, and oil tank.
b. Air conditioner
The air conditioner consists of cooling coil, heating coil, humidifier, air filter, and
others, which treats indoor heat loads to keep air clean.
The air conditioner sometimes takes in outdoor air (referred to as fresh air as well) and
mixes it in return air from rooms. This outdoor air replaces indoor air contaminated
due to breathing, odor, or smoking of people in the rooms.
c. Fan and duct
The fan serves as a power to transport air through transport path that is the duct.
Air treated with the air conditioner is transported through the duct and fed into the
room from the air outlet. Air, which has treated the indoor heat loads, is returned from
the air inlet back to the air conditioner through the duct.
d. Pump and piping
The pump serves as a power to transport the heating medium such as water through
transport path that is the piping.
Chilled water, hot water, or vapor, which is produced with the heat source unit, is
transported to the air conditioner through the piping, where the heat loads are treated.
After that, it is returned to the heat source unit. In order to discharge heat removed
through chiller or absorption type chiller to the outside, the pump transports cooling
water up to cooling tower through the piping.
e. Automatic control unit
On air conditioners, the chilled and hot water flow rates are adjusted and the discharge
temperature and relative humidity are controlled.
Furthermore, the airflow rate of the discharge air may be controlled. The intake
amount of outdoor air is controlled as well.
On heat source units, the chilled and hot water temperatures are kept constant and, at
the same time, the number of operating units and their capacities are controlled
according to the load capacities. On pumps, the number of units and the capacities are
controlled.

Chapter 1: Classification of air conditioner

20


Thus, the automatic control unit is a unit to operate the entire air conditioning system
so that it can keep the indoor temperature and relative humidity under the most
favorable conditions and economical running conditions.

Chapter 1: Classification of air conditioner

21


Chapter 2: Components
2.1 General decription ..................................................................................................24
2.2 Main components .................................................................................................. 27
2.2.1. Compressor................................................................................................... 27
(1) Classifications by compression methods .......................................................27
(2) Classifications of reciprocating compressors by structure .............................29
2.2.2 Condenser ....................................................................................................... 31
(1) Double tube type (Tube within a-tube type)...................................................32
(2) Shell and tube type .................................................. ......................................32
(3) Cross fin coil type.................................................... ......................................32
(4) Wind fin type ........................................................... ......................................33
2.2.3 Evaporator ...................................................................................................... 33
(1) Multiple tube within a tube type ................................................................... 33
(2) Dry expansion shell and tube type ............................................................... 33
(3) Flooded shell and tube type ...........................................................................34
(4) Plate type .....................................................................................................35

(5) Cross fin coil type ........................................................................................35
2.2.4 Metering devices ............................................................................................35
(1) Capillary tube ..................................... ...........................................................36
(2) Thermostatic expansion valves ..................................................................... 36
2.3 Control devices .......................................................................................................41
(1) Liquid receiver ...................................................................................................41
(2) Dryer filter .........................................................................................................42
(3) Accumulator .......................................................................................................42
(4) Injection capillary .............................................................................................. 43
(5) Low pressure control valve................................................................................ 43
(6) Pre-cooler........................................................................................................... 43
(7) Gas liquid heat exchanger...................................................................................44
(8) Muffler ............................................................................................................... 44
(9) Solenoid valve ................................................................................................... 44
(10) Check valve...................................................................................................... 45
(11) Four-way valve .................................................................................................45
(12) Bridge circuit ....................................................................................................47
2.4 Safety devices ................................................ ............................... ........................ 48
(1) High pressure switch (HPS)............................................................................... 48
(2) Low pressure switch (LPS).................................................................................48
Chapter 2: Components

22


(3) Oil pressure switch (OPS) ..................................................................................49
(4) Fusible plug ....................................................................................................... 49
(5) Safety valve (relief valve)...................................................................................50
(6) Pressure regulating valve....................................................................................50
(7) Stop valve ...........................................................................................................50


Chapter 2: Components

23


Chapter 2: Components
2.1 General description
The air conditioners consist of various parts and components. It is very important for
servicemen to understand the structure and functions of each part and component well
and to diagnose troubles with the air conditioners.
In this chapter, the parts and components used mainly in the room air conditioners and
packaged air conditioners in recent years are explained.
In order to support the reading exercise of piping diagram, this Chapter picks up a
product of simple design out of the SkyAir Series prevailing as air conditioners for
business use, thus explaining typical components. Referring to the actual single view
drawing on the following page of parts with the number corresponding to that shown
in the circuit diagram below, get at the outline image of the parts.
Fig. 2-1 R71KU

Components name
(1) Compressor
(2) High pressure switch
(3) Condenser (outdoor unit heat exchanger)
exchanger)
(4) Receiver
(5) Electronic expansion valve
(6) Filter (refrigerant)
(7) Capillary tube
Chapter 2: Components


(8) Filter (refrigerant)
9) Distributor
(10) Indoor unit fan (centrifugal)
(11) Evaporator (indoor unit heat
(12) Stop valve (service vale)
(13) Low pressure switch
(14) Outdoor fan (propeller)
(15) Filter (refrigerant)
24


Fig. 2-2 FVY71L

R71KU

Air conditioners have a variety of functional parts except for four components such as
compressor, condenser, expansion valve, and evaporator. It is certainly practical for
you to understand the structure and functions of the parts when you do many different
types of services.
Here, main components are schematically illustrated for better comprehension.
component or equipment. This figure effectively affects to let you comprehension. In
the succeeding pages, this schematic figure notice the location of the component in
relation to the other sometimes can be seen on the booth explaining each component’s
locations.
Chapter 2: Components

25



×