Tải bản đầy đủ (.pdf) (43 trang)

PCS 902s x selection guide EN overseas general x r1 00

Bạn đang xem bản rút gọn của tài liệu. Xem và tải ngay bản đầy đủ của tài liệu tại đây (2.04 MB, 43 trang )



Copyright © 2019 NR. All rights reserved.
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know -how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.



Preface

Preface
About This Manual
The selection guide describes the application overview and the summary of protection, automation,


control and supervision functions of PCS-902S. Moreover, it provides the explanation about the
application option, the firmware option, the software option, the hardware option and etc., and can
be used to indicate how to order a PCS-902S based on expected configurations.

Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.

Document Structure
This guide is mainly for the overview of the application and the functions about PCS-902S, and it
provides the configuration of software and hardware information for ordering. An overview of each
manual section and section topics follows.

1 Functions and Application
Introduces the summary functions of this device, such as the protection, the automation, the
control and the supervision. Briefly introduces the typical application schemes of PCS-902S.

2 MOT Information
Introduces the meaning of the ordering code, and details all options about the application, the
firmware, the software, the hardware and etc. of PCS-902S.

Document Revision History
PN: ZL_PCS-902S_X_Selection Guide_EN_Overseas General_X
Current version: R1.00
Corresponding Version
Release Date
Document

Software


R1.00

R1.00

2019-01-31

Description of change



Form the original manual.

PCS-902S Line Distance Relay
Date: 2019-01-31

I


Preface

PCS-902S Line Distance Relay

II
Date: 2019-01-31


1 Functions and Applications

1 Functions and Applications


1

Table of Contents
1.1 Overview ........................................................................................................... 1-1
1.2 Protection Functions ....................................................................................... 1-2
1.3 Control Functions ............................................................................................ 1-5
1.4 Measurement Functions ................................................................................. 1-5
1.5 Supervision Functions .................................................................................... 1-5
1.6 Pilot Channel Scheme ..................................................................................... 1-5
1.7 Communication Functions ............................................................................. 1-6
1.8 User Interfaces ................................................................................................. 1-6
1.9 Additional Functions ....................................................................................... 1-6
1.10 Typical Applications ...................................................................................... 1-7

List of Figures
Figure 1.1-1 Functional overview of PCS-902S ........................................................................ 1-1
Figure 1.10-1 Typical application of single circuit breaker ..................................................... 1-8
Figure 1.10-2 Typical application of double circuit breakers ................................................. 1-8

PCS-902S Line Distance Relay
Date: 2019-01-31

1-a


1 Functions and Applications

1

PCS-902S Line Distance Relay


1-b
Date: 2019-01-31


1 Functions and Applications

1.1 Overview
PCS-902S protect overhead and underground lines, feeders and cables on all voltage levels with
highest selectivity possible. The large number of protective and automatic functions available
permits their utilization in all areas of line protection. The devices contain all important auxiliary
functions that are necessary today for safe network operation. This includes control, measurement
and monitoring functions. The large number of communication interfaces and communication
protocols satisfies the requirements of communication-based selective protection and of
automated operation. Their modular structure permits line protection devices always to be adapted
flexibly to the individual requirements.
The functional overview of the device is shown in Figure 1.1-1.
Busbar
3VT

52

85

21

67P

67G


67Q

21D

50/51P

50/51G

50/51Q

32R

50DZ

46BC

62PD

50BF

FR

59P

37

FL

59Q


SOTF

59G

81O

27P

81U

81R

*

3CT

Data transmit/Receive

1VT
25

79

Line

Figure 1.1-1 Functional overview of PCS-902S

PCS-902S is a high-speed transmission line distance relay featuring single-pole and three-pole
tripping and reclosing with synchronism check. The device features extensive metering and data
recording including high-resolution data capture and reporting. PCS-902S features expanded

control equation programming for easy and flexible implementation of custom protection and
control schemes.
A simple and robust hardware design features efficient digital signal processing. Combined with
extensive self-testing, these features provide device reliability and enhance relay availability.
PCS-902S can be configured to support single circuit breaker application or double circuit
breakers application by PCS-Studio. If the device is applied to double circuit breakers mode, all
PCS-902S Line Distance Relay
Date: 2019-01-31

1-1

1


1 Functions and Applications

protection functions related to the number of circuit breaker will be affected.

1

1.2 Protection Functions
ANSI

Protection functions

Remark


Independent pilot zone (forward direction and reverse
direction, mho or quadrilateral characteristics)


Pilot distance protection

85



PUTT, POTT, Blocking, Unblocking, Zone Extension



Current reversal logic



Weak infeed echo or echo&trip



Open breaker echo



Directional zero-sequence comparison element for
pilot scheme

Pilot

directional


earth-fault

protection



PTT, Blocking and Unblocking



Current reversal logic



Weak infeed echo or echo&trip



Open breaker echo



Up to 6 zones



3 independent phase-to-ground distance elements for
each zone




3 independent phase-to-phase distance elements for
each zone



Selectable

quadrilateral

characteristics

or

mho

characteristics

21

Distance protection

Independent impedance settings and time delays for
each zone



Zero-sequence

current


compensation

for

phase-to-ground distance element


Selectable forward direction, reverse direction or non
direction (except zone 1 that is fixed as forward
direction)

21D

67P
50/51P

DPFC distance protection

Phase overcurrent protection



Load encroachment for each zone



Power swing blocking and releasing for each zone




Faulty phase selection for each zone



Fixed forward direction



High-speed operation



Supplementary for zone 1 of distance protection



Up to 6 stages with independent logic



Voltage control element for each stage



Optional direction element for each stage, including
forward direction, reverse direction or non direction




Optional definite-time characteristics and inverse-time
characteristics for each stage

PCS-902S Line Distance Relay

1-2
Date: 2019-01-31


1 Functions and Applications


Trip purpose or alarm purpose for each stage



Harmonic control element for each stage



Up to 6 stages with independent logic



Optional direction element for each stage, including
forward direction, reverse direction or non direction

67G
50/51G




Earth fault protection

Optional definite-time characteristics and inverse-time
characteristics for each stage



Selectable trip purpose or alarm purpose for each
stage

67Q
50/51Q

Negative-sequence

overcurrent

protection



Harmonic control element for each stage



Up to 2 stages with independent logic




Optional direction element for each stage, including
forward direction, reverse direction or non direction



Optional definite-time characteristics and inverse-time
characteristics for each stage

SOTF

Switch onto fault



Via distance measurement elements



Via dedicated earth fault element



Via phase overcurrent element



Up to 2 stages with independent logic




Optional definite-time characteristics and inverse-time
characteristics for each stage

59P

Phase overvoltage protection



Optional phase voltage or phase-to-phase voltage



Optional “1-out-of-3” logic or “3-out-of-3” logic



Selectable trip purpose or alarm purpose for each
stage



Up to 2 stages with independent logic



Optional definite-time characteristics and inverse-time
characteristics for each stage


27P

Phase undervoltage protection



Optional phase voltage or phase-to-phase voltage



Optional “1-out-of-3” logic or “3-out-of-3” logic



Blocked by instantaneous VT circuit failure



Selectable trip purpose or alarm purpose for each
stage



Optional auxiliary criterion, including CB position check
and current check

59Q

59G


Negative-sequence

overvoltage

protection

Residual overvoltage protection



Up to 2 stages with independent logic



Selectable trip purpose or alarm purpose for each
stage



Up to 2 stages with independent logic



Selectable trip purpose or alarm purpose for each
stage

81O

Overfrequency protection


81U

Underfrequency protection



Up to 6 stages with independent logic



Voltage control element



Up to 6 stages with independent logic

PCS-902S Line Distance Relay
Date: 2019-01-31

1-3

1


1 Functions and Applications

81R

1


32R

Rate

of

change

of

frequency

protection
Reverse power protection



Voltage control element



Up to 6 stages with independent logic



Voltage control element



Up to 2 stages with independent logic




Selectable trip purpose or alarm purpose for each
stage


37

Undercurrent protection

Optional auxiliary criterion, including CB position check
and current check



Selectable trip purpose or alarm purpose for each
stage

50BF

50DZ



Phase-segregated re-trip and three-phases re-trip



Optional current criterion (phase overcurrent element,

zero-sequence

Breaker failure protection

Dead zone protection

Pole discrepancy protection

element,

negative-sequence overcurrent element)


Optional circuit breaker position check



Two time delays



Clear the dead zone faults between CT and the circuit
breaker


62PD

overcurrent

Initiated by three auxiliary contacts of phase-segregate

circuit breaker



Optional auxiliary criterion (zero-sequence current
element or negative-sequence current element)


46BC

Broken conductor protection

Adopt the ratio of negative-sequence current to
positive-sequence current (Ι2/Ι1) to detect the broken
conductor.

25

79

Synchrocheck

Auto-reclosing



Independent logic for auto-reclosing and manually
closing




One shot or multi-shot



1-pole AR, 3-pole AR or 1/3-pole AR



Optional trigger mode, including protection operating
and external binary input

FL

Fault location



Support synchro-check and voltage check



Single-end fault location



Double-end fault location




Zero-sequence mutual coupling compensation for
parallel lines

DPFC is the abbreviation of deviation of power frequency component.

PCS-902S Line Distance Relay

1-4
Date: 2019-01-31


1 Functions and Applications

1.3 Control Functions


Circuit breaker & disconnector control (Remote/local)



Synchronism check for remote and manual closing



Voltage switching

1

1.4 Measurement Functions



Energy metering (active and reactive energy are calculated in import respectively export
direction)



Power (Apparent/Real/Reactive)



Power Factor



Frequency



Event Recorder including 1024 disturbance records, 1024 binary events, 1024
supervision events, 256 control logs and 1024 device logs.



Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)

1.5 Supervision Functions


VT circuit supervision




CT circuit supervision



Trip/Close coil supervision



Self diagnostic



Pilot communication channel supervision



DC power supply supervision



Channel status statistic



System frequency supervision

1.6 Pilot Channel Scheme



Optional single- or dual- pilot channels (fiber optic)



Support G.703 and C37.94

PCS-902S Line Distance Relay
Date: 2019-01-31

1-5


1 Functions and Applications

1.7 Communication Functions

1



Up to four 10Base-T/100Base-TX copper Ethernet ports using IEC 61850, DNP3.0 or
IEC 60870-5-103 over TCP/IP



Up to four 100Base-FX optical Ethernet ports using IEC 61850, DNP3.0 or IEC
60870-5-103 over TCP/IP




Two RS-485 serial ports using IEC 60870-5-103 or Modbus



One RS-485 serial port for clock synchronization



Support GOOSE communication module using IEC 61850-8-1 GOOSE



Full compatibility between IEC 61850 Editions 1 and 2



Redundancy protocols PRP, HSR and RSTP



One front RJ-45 port and one rear RJ-45 port for debugging

1.8 User Interfaces


Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment




Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management



4 Programmable operator pushbuttons with user-configurable labels



Up to 18 programmable target LEDs with user-configurable labels



1 RS-485 rear ports for printer



Language switchover—English+ selected language



Configuration tool—PCS-Studio

1.9 Additional Functions


User programmable logic




Fault location



Fault phase selection



Parallel line compensation for fault location



Switching system phase sequences function (ABC or ACB)



Clock synchronization

PCS-902S Line Distance Relay

1-6
Date: 2019-01-31


1 Functions and Applications






IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface



PPS: Pulse per second (PPS) via RS-485 differential level or binary input



PPM: Pulse per minute (PPM) via RS-485 differential level or binary input



IEEE1588: Clock message based on IEEE1588 via optical fibre interface



SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network



SNTP (BC): Broadcast SNTP mode via Ethernet network



Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol,
Modbus protocol and DNP3.0 protocol

1


Cyber security



NERC CIP



IEC 62351



IEC 62443



IEEE 1686

1.10 Typical Applications
There are several typical applications for different application situation.


2-terminal transmission line

PCS-902S Line Distance Relay
Date: 2019-01-31

1-7



1 Functions and Applications
Busbar

1VT

52

1

3VT

85

21

67P

67G

67Q

21D

50/51P

50/51G

50/51Q


32R

50DZ

46BC

62PD

50BF

FR

59P

37

FL

59Q

SOTF

59G

81O

27P

81U


81R

*

3CT

Data transmit/Receive

79

52

25

Figure 1.10-1 Typical application of single circuit breaker

52

1VT

52

*

3CT

3VT
52

52


*

3CT

1VT

52

52

1VT

85

21

67P

67G

67Q

21D

50/51P

50/51G

50/51Q


32R

50DZ

46BC

62PD

Data transmit/Receive

50BF

FR

59P

37

FL

59Q

SOTF

59G

81O

27P


81U

81R

25

79

Figure 1.10-2 Typical application of double circuit breakers

PCS-902S Line Distance Relay

1-8
Date: 2019-01-31


2 MOT Information

2 MOT Information
Table of Contents
2.1 Ordering Code.................................................................................................. 2-1
2.2 Selection Information ...................................................................................... 2-2
2.2.1 Device Type .......................................................................................................................... 2-2
2.2.2 Application Scenario (U Field) .............................................................................................. 2-2
2.2.3 Firmware Type (A Field) ....................................................................................................... 2-3
2.2.4 Firmware Version (R Field) .................................................................................................. 2-3
2.2.5 Software Functions (S Field) ................................................................................................ 2-3
2.2.6 Chassis Structure and Installation (C Field)......................................................................... 2-5
2.2.7 Power Supply Plug-in Module (PWR Field) ....................................................................... 2-16

2.2.8 Plug-in Module Configuration (H Field) .............................................................................. 2-17
2.2.9 MOT Version ....................................................................................................................... 2-23

PCS-902S Line Distance Relay
Date: 2019-01-31

2-a

2
2


2 MOT Information

2

PCS-902S Line Distance Relay

2-b
Date: 2019-01-31


2 MOT Information

2.1 Ordering Code
PCS S series device can select the hardware configuration and software functions of the device
through the auxiliary tool “PCS-Torch”, and a corresponding MOT (Market Ordering Table) serial
code will be generated.
The MOT serial code consists of 9 parts, including:



Device type: indicates the device type



U field: indicates application scenario



A field: indicates firmware type, which can be standard version or regional version



R field: indicates firmware version



S field: indicates software functions



C field: indicates chassis structure and installation



PWR field: indicates the voltage level of power supply plug-in module



H field: indicates plug-in module configuration




MOT version: indicates MOT version

The display format is shown as below:
Device type

U field
A field

R field
S field

C field
PWR field
H field
MOT version

Click the button "Default", all options will be chosen as default value directly. Click the button
PCS-902S Line Distance Relay
Date: 2019-01-31

2-1

2
2


2 MOT Information


"Import", an existing MOT file (*.xls) can be directly imported into the corresponding device type of
PCS-Torch.
After selecting the specific function, click the button “Complete” to display the currently selected
configuration information, is shown as below:

2

Click the button "Copy", MOT (Market Ordering Table) serial code based on selected information
will be copy to the clipboard. Click the button "Export", MOT and hardware configuration can be
exported as a file (*.xls).

2.2 Selection Information
A MOT serial code consists of several bits, and the specific meaning of each bit is as below.

2.2.1 Device Type
For a specific device, the device type is fixed, such as PCS-902S, so it is not need to be chosen.

2.2.2 Application Scenario (U Field)
The corresponding application scenarios are selected according to the actual protected objects by
the device. Only one kind of application is available, so it is chosen as "2 terminal line" fixedly.

PCS-902S Line Distance Relay

2-2
Date: 2019-01-31


2 MOT Information


2.2.3 Firmware Type (A Field)
The firmware type is used to select between the standard version program and the regional
version program. Only the standard version program is available, so it is chosen as "Standard"
fixedly.

2
2
2.2.4 Firmware Version (R Field)
The firmware version is used to select required program version. If there is no special version
requirement, the latest version can be chosen, i.e., “Latest version”. Otherwise, the specified
version can be chosen.

2.2.5 Software Functions (S Field)
The software functions are determined by four parts: "Software", "Language", "Protocol" and
"Sampling mode".
1.

Software

The option is used to select the required protection functions, which is used in conjunction with the
application scenario option.

Different options correspond with different combinations of protection functions, which can be
viewed through the button "Software Functions" in PCS-Torch.

PCS-902S Line Distance Relay
Date: 2019-01-31

2-3



2 MOT Information

2

2.

Language

The option is used to select other supported language. "Chinese" is supported fixedly. "English"
or "English + Spanish" is available.

3.

Protocol

The option is used to select the supported protocol for communication with SCADA system. There
are four kinds protocols, including IEC103, DNP3.0, Modbus and IEC61850.
"Basic (IEC 60870-5-103 + DNP3.0 + Modbus)": includes IEC 60870-5-103, DNP3.0 and Modbus
"Basic + IEC 61850 (Editions 1.0 or Edition 2.0)": includes IEC 60870-5-103, DNP3.0, Modbus
and IEC 61850, and full compatibility between IEC 61850 Editions 1.0 and 2.0.

PCS-902S Line Distance Relay

2-4
Date: 2019-01-31


2 MOT Information


4.

Sampling Mode

The option is used to select sampling mode, and conventional sampling mode or digital sampling
mode is available.

"Conventional instrument transformer": conventional sampling mode
"Non-conventional instrument transformer": digital sampling mode based on IEC 61850-9-2LE

If "Non-conventional instrument transformer" is chosen, the item "12 ×
100Base-FX (LC-Connector)" in "Slot02" of H field is activated.

2.2.6 Chassis Structure and Installation (C Field)
The chassis structure and installation are determined by five parts: "Case Size", "Installation
Mode", "Front Side Protection Class", "Tri-proof" and "I/O Terminal".
1.

Case Size

The option is used to select the case size. The device supports two kinds of case sizes.
"6U 1/2 19": 6U height, 1/2 width, 19-inch chassis
"6U 1/1 19": 6U height, Full width, 19-inch chassis



Choose "6U 1/2 19"

The device can support five kinds of installation modes.


PCS-902S Line Distance Relay
Date: 2019-01-31

2-5

2
2


2 MOT Information

2

The device can be equipped with 18 configurable LEDs, 1 CPU module, 1 AI module, 3 I/O
modules ("Slot4"~"Slot6") and 1 PWR module.

PCS-902S Line Distance Relay

2-6
Date: 2019-01-31


2 MOT Information

2
2



Choose "6U 1/1 19"


The device only can support two kinds of installation modes. ("Flush" and "Rack")

The device can be equipped with 18 configurable LEDs, 1 CPU module, 1 AI module, 10 I/O
modules ("Slot5"~"Slot14") and 1 PWR module. "Slot4" will be always fixed as "Not required"
and "Slot7"~"Slot14" in the H field are activated.

PCS-902S Line Distance Relay
Date: 2019-01-31

2-7


×