Copyright © 2020 NR. All rights reserved.
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface
About This Manual
The technical manual describes the protection, automation, control, and supervision functions of
PCS S series device for line distance protection, and contains operation principle descriptions,
and lists function blocks, logic diagrams, input and output signals, setting parameters and
technical data, sorted per function, as well as the hardware of the device. The manual can be used
as a technical reference during the engineering phase and during normal service. In addition, the
manual also includes a glossary that lists and defines technical terms used throughout the
manual.
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for
personal safety, as well as to avoid material damage. Information is highlighted and illustrated as
follows according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result
in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage.
Indicates that property damage can result if the measures specified are
not taken.
Important information about the device, product handling or a certain
section of the documentation which must be given particular attention.
Instructions and Warnings
The following hazard statements apply to this device.
Disconnect or de-energize all external connections BEFORE opening this
PCS-902S Line Distance Relay
Date: 2020-02-27
I
Preface
device. Contact with hazardous voltages and currents inside this device
can cause electrical shock resulting in injury or death.
Contact with instrument terminals can cause electrical shock that can result
in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
This device is shipped with default passwords. Default passwords should
be changed to private passwords at installation. Failure to change each
default password to a private password may allow unauthorized access.
NR shall not be responsible for any damage resulting from unauthorized
access.
DO NOT look into the fiber (laser) ports/connectors.
DO NOT look into the end of an optical cable connected to an optical
output.
DO NOT perform any procedures or adjustments that this instruction
manual does not describe.
During installation, maintenance, or testing of the optical ports, ONLY use
II
PCS-902S Line Distance Relay
Date: 2020-02-27
Preface
the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable. Return units to NR for repair or replacement.
Equipment components are SENSITIVE to electrostatic discharge (ESD).
Undetectable permanent damage can result if you do not use proper ESD
procedures. Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment. If your facility is not
equipped to work with these components, contact NR about returning this
device and related NR equipment for service.
Insufficiently rated insulation can deteriorate under abnormal operating
conditions and cause equipment damage. For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions.
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables. Please
use the wiring method recommended in the manual for communication
terminals.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage can
result otherwise.
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure.
The firmware may be upgraded to add new features or enhance/modify
PCS-902S Line Distance Relay
Date: 2020-02-27
III
Preface
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.
Document Conventions
⚫
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.
⚫
Menu path is connected with the arrow "→" and bold.
For example: the access path of protection settings is: MainMenu→Settings→Protection
Settings
⚫
Settings not in the table should be placed in brackets.
For example: the system setting [Opt_SysFreq]
⚫
Cross-references are presented in italics.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫
Binary input signals, binary output signals, analogues, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
For example: press the button "ENT".
Symbols
⚫
AND Gate
&
&
>=1
>=1
&
⚫
OR Gate
>=1
⚫
Comparator
⚫
Binary signal Input
BI
xxx
IV
PCS-902S Line Distance Relay
Date: 2020-02-27
Preface
⚫
Signal input
SIG
⚫
Setting input
SET
⚫
xxx
Enable input
EN
⚫
xxx
xxx
Timer
Optional definite-time or inverse-time characteristics
Timer
t
t
⚫
Timer
Fixed delay pickup (10ms), fixed delay dropout (2ms)
10ms
⚫
2ms
Timer
Settable delay pickup, fixed delay dropout
[Tset1]
⚫
0ms
Timer
Fixed delay pickup, settable delay dropout
0ms
⚫
[Tset2]
Timer
Settable delay pickup, settable delay dropout
[Tset1]
⚫
[Tset2]
Generator
G
PCS-902S Line Distance Relay
Date: 2020-02-27
V
Preface
⚫
Transformer
⚫
Reactor
⚫
Motor
M
⚫
Capacitor
⚫
Busbar
⚫
Circuit breaker
52
⚫
Current transformer
3CT
*
⚫
Voltage transformer
3VT
⚫
Disconnector
VI
PCS-902S Line Distance Relay
Date: 2020-02-27
Preface
⚫
Earth
Three-phase Corresponding Relationship
Basic
A, B, C
L1, L2, L3
R, Y, B
AN, BN, CN
L1N, L2N, L3N
RN,YN, BN
ABC
L123
RYB
U (voltage)
V
U
Example
Ia, Ib, Ic, I0
IL1, IL2, IL3, IN
IR, IY, IB, IN
Ua, Ub, Uc
VL1, VL2, VL3
UR, UY, UB
Uab, Ubc, Uca
VL12, VL23, VL31
URY, UYB, UBR
U0, U1, U2
VN, V1, V2
UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This manual is a comprehensive work covering the theories of protection, control, supervision,
measurement, etc. and the structure & technical datas of relevant hardwares. Read the sections
that pertain to your application to gain valuable information about using the device. To concentrate
on the target sections of this manual as your job needs and responsibilities dictate. An overview of
each manual section and section topics follows.
1 Introduction
Introduces features, summarizes functions and applications of the device.
2 Technical Data
Lists device specifications, type tests, and ratings.
3 Protection Functions
Describes the function of various protection elements, gives detailed specifics on protection
scheme logic, provides the relevant logic diagrams.
PCS-902S Line Distance Relay
Date: 2020-02-27
VII
Preface
4 Control Functions
Describes the logic for the control of up to 15 disconnectors and 2 circuit breakers, synchronism
check for manual closing and voltage selection logic for different application scenario.
5 Measurement
Provides information on viewing fundamental and rms metering quantities for voltages and
currents, as well as power and energy metering data.
6 Supervision
Describes self-supervision technique to help diagnose potential difficulties should these occur and
includes the list of status notification messages. Provides a troubleshooting chart for common
device operation problems.
7 System Functions
Describes how to perform fundamental operations such as clock synchronization, communicating
with the device, switching active setting group, checking relay status, reading event reports and
SER (Sequential Events Recorder) records.
8 Hardware
Describes the hardware of the PCS series device family and provides general information on the
product structure and the modules technical data.
9 Settings
Provides a list of all settings and their ranges, unit, steps, defaults. The organization of the settings
is similar to the settings organization in the device and in the configuration tool (PCS-Studio).
Appendix A Glossary
Describes the abbreviations adopted in this manual.
Document Revision History
PN: ZL_PCS-902S_X_Technical Manual_EN_Overseas General_X
Current version: R1.20
Corresponding Version
Release Date
Document
Software
R1.00
R1.00
R1.10
R1.12
2019-01-24
Description of change
⚫
Form the original manual
⚫
Add stub differential protection
⚫
Add switchgear position verification
⚫
Add the description about digital substation application
⚫
Add the description about digital interface
2019-11-25
VIII
PCS-902S Line Distance Relay
Date: 2020-02-27
Preface
⚫
Add technical data of GOOSE and SV
⚫
Add certifications of IEC 61850, DNP, PRP, HSR, IEEE
1588
⚫
Add alarm signals of GOOSE and SV
⚫
Delete switching setting group by input signals
⚫
Add NET-DSP plug-in module (NR6612B)
⚫
Add SV communication settings
⚫
Add label settings
⚫
Add GOOSE send links and receiving links
⚫
Add SV links
⚫
Add CPU plug-in module, NR6106AC and related
technical data of optical fiber channel (wave length
1550nm)
⚫
Add typical application of single circuit breaker (double
busbars)
⚫
Add out-of-step protection
⚫
Modify the logic of automatic reclosing and add the
related settings
⚫
Add
general
communication
[IP_SyslogServer01],
settings:
[IP_SyslogServer02],
[IP_SyslogServer03], [IP_SyslogServer04]
⚫
Add three-phase current element, three-phase voltage
element and single-phase current element
⚫
Modify the description about switching setting groups via
binary inputs
⚫
Modify the technical data of breaker failure protection
and broken conductor protection
⚫
Add the technical data of transfer trip
⚫
Add CPU plug-in module (NR6106AK)
PCS-902S Line Distance Relay
Date: 2020-02-27
IX
Preface
⚫
Modify the technical data of device′s power consumption
⚫
Modify the lower limit of the settings [VTS.t_DPU] and
[VTS.t_DDO]
⚫
Add synchrophasor measurement function
⚫
Modify the logic of distance protection
⚫
Modify the logic of VT circuit supervision
⚫
Modify I/O signals of switchgear control, synchronism
check and voltage selection
⚫
Add the description of base phase angle for angle value
in measurements
⚫
Modify the terms of "Energy Metering"
⚫
Modify the terms of "Energy Metering Settings"
⚫
Modify the technical data of binary input
⚫
Modify the description about switchgear trip counter
⚫
Modify the technical data of power supply
⚫
Delete the technical data of BNC connector
⚫
Modify
the
operating
time
delay
accuracy
of
negative-sequence overvoltage protection and residual
overvoltage protection
⚫
Modify the operating time delay accuracy and dropout
ratio of breaker failure protection
⚫
Modify the dropout ratio of broken conductor protection
⚫
Modify the setting range of the setting [85.U_UV_WI]
⚫
Modify the logics of breaker failure protection and pole
discrepancy protection
R1.11
R1.12
⚫
Modify the logic of enabling distance protection
⚫
Modify
2020-01-22
the
technical
data
of
synchrophasor
communication
⚫
Modify the technical data of protection class for front side
X
PCS-902S Line Distance Relay
Date: 2020-02-27
Preface
⚫
Modify the description about remote control mode
⚫
Update the terms of reclosing
⚫
Modify the technical data of dropout time accuracy of
negative-sequence overvoltage protection and residual
overvoltage protection
⚫
Modify the explanation of the settings [Prot.U1n],
[Prot.U2n],
2020-02-19
[UL2.Syn.U1n],
[UB1.Syn.U1n],
[UL2.Syn.U2n],
[UB2.Syn.U2n],
[Prot.Opt_CT_Measmt],
[UB1.Syn.U2n],
[UB2.Syn.U1n]
[CBx.25.Opt_ValidMode],
[Prot.CB1.Opt_CT_Measmt]
and [Prot.CB2.Opt_CT_Measmt]
⚫
Add the information about the settings [MMTR.U2n] and
[MMTR.I2n]
2020-02-27
⚫
Update current and voltage connection examples
⚫
Add output signal of transfer trip, "TT.BlkAR", and related
logic
⚫
Delete GOOSE communication settings
⚫
Modify the logic of earth fault protection
⚫
Modify the logic of negative-sequence overcurrent
protection
⚫
Add the description about CT circuit failure blocking
earth fault protection and negative-sequence overcurrent
R1.20
R1.20
2020-06-01
protection
⚫
Delete stage 5 and stage 6 of overfrequency protection,
underfrequency protection and frequency rate-of-change
protection
⚫
Modify the logics of AR
⚫
Modify the logic of reclosing numbers control
⚫
Modify the logics of switchgear control and DPS alarm
PCS-902S Line Distance Relay
Date: 2020-02-27
XI
Preface
⚫
Modify the logic of dead check
⚫
Modify the description and sequence chart of jitter
processing
⚫
Modify the technical standard of power supply
⚫
Update PMU
⚫
Add thermal overload protection
⚫
Modify the logic of sending permissive signal in current
differential protection
⚫
Add travelling-wave fault location function
⚫
Add
TWFL
module
(NR6111A),
CPU
module
(NR6106AQ) and IO module (NR6661A)
⚫
Modify the logics of pilot distance protection (POTT,
Blocking) and pilot directional earth-fault protection (PTT,
Blocking)
⚫
Add
the
settings:
[85.En_Op_Ctrl_Send],
[85.En_PilotOp_Ctrl_Send],
[85.En_52b_Ctrl_Send]
[85.En_52b_Echo] in "Pilot Scheme Settings"
⚫
Add the settings, [21L.PilotFwd.ZP.En_NegDir_Blk],
[21L.PilotFwd.ZG.En_NeuDir_Blk],
[21L.PilotFwd.ZG.En_NegDir_Blk]
in
"DistProt
Settings"
⚫
Revise CT requirement
XII
PCS-902S Line Distance Relay
Date: 2020-02-27
1 Introduction
1 Introduction
1
Table of Contents
1.1 Application ....................................................................................................... 1-1
1.2 Functions ......................................................................................................... 1-2
1.3 Highlights ........................................................................................................1-11
1.4 Features.......................................................................................................... 1-12
List of Figures
Figure 1.1-1 Typical application of single circuit breaker (single busbar) ............................ 1-1
Figure 1.1-2 Typical application of single circuit breaker (double busbars) ........................ 1-1
Figure 1.1-3 Typical application of double circuit breakers ................................................... 1-2
Figure 1.2-1 Functional overview of PCS-902S ........................................................................ 1-3
PCS-902S Line Distance Relay
Date: 2020-06-01
1-a
1 Introduction
1
1-b
PCS-902S Line Distance Relay
Date: 2020-06-01
1 Introduction
1.1 Application
PCS-902S protect overhead and underground lines, feeders and cables on all voltage levels with
highest possible selectivity. The availability of various protection and automation functions permits
its utilization in all domains of line protection. The devices contain all important auxiliary functions
that are necessary today for safe network operation. This includes control, measurement and
monitoring functions. The large number of communication interfaces and communication protocols
satisfies the requirements of communication-based selective protection and automation operation.
Its modular structure permits line protection devices always to be adapted flexibly to the individual
requirements.
52
52
PCS-902S
Optical fibre channel or PLC channel
PCS-902S
Communication channel via direct dedicated fibre, MUX or PLC
Figure 1.1-1 Typical application of single circuit breaker (single busbar)
52
52
PCS-902S
Optical fibre channel or PLC channel
PCS-902S
Communication channel via direct dedicated fibre, MUX or PLC
Figure 1.1-2 Typical application of single circuit breaker (double busbars)
PCS-902S is a high-speed transmission line distance relay featuring single-pole & three-pole
tripping and reclosing with synchronism check. The device features extensive metering & data
recording including high-resolution data capture and reporting. PCS-902S features expanded
control equation programming for easy and flexible implementation of custom protection and
control schemes.
A simple and robust hardware design features efficient digital signal processing. Combined with
extensive self-testing, these features provide device reliability and enhance relay availability.
PCS-902S can be configured to support single circuit breaker application or double circuit
breakers application by PCS-Studio. If the device is applied to double circuit breakers mode, all
PCS-902S Line Distance Relay
Date: 2020-06-01
1-1
1
1 Introduction
protection functions related to the number of circuit breaker will be affected.
Bus1
1
Single-phase
voltage
52
PCS-902S
Three-phase
voltage
Line 1
52
Line 2
Single-phase
voltage
52
Single-phase
voltage
Bus2
Figure 1.1-3 Typical application of double circuit breakers
The PCS-902S is widely adopted not only for conventional substations, but also for digital
substations. It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network
interfaces with high real-time performance. The process level network supports peer-to-peer (P2P)
mode and networking mode, including single network mode and dual network mode. The station
level network could also receive and send MMS messages (such as interlocking signals) or
process level GOOSE messages (such as circuit breakers or disconnectors positions and trip
signals).
1.2 Functions
The functional overview of the device is shown in Figure 1.2-1.
1-2
PCS-902S Line Distance Relay
Date: 2020-06-01
1 Introduction
Busbar
3VT
1
52
85
21
67P
67G
67Q
21D
50/51P
50/51G
50/51Q
32R
49
50DZ
46BC
62P D
50BF
37
PMU
59P
FR
59Q
*
3CT
78
FL
Data transmit/Rec eiv e
1VT
SOTF
59G
81O
27P
81U
81R
87STB (Only for one and a half breakers arrangement)
25
79
Line
Figure 1.2-1 Functional overview of PCS-902S
1
Protection functions
ANSI
Protection functions
Remark
⚫
Independent pilot zone (forward direction and reverse
direction, mho or quadrilateral characteristics)
⚫
PUTT, POTT, Blocking, Unblocking, Zone Extension
⚫
Current reversal logic
⚫
Weak infeed echo or echo&trip
⚫
Open breaker echo
⚫
Directional zero-sequence comparison element for
Pilot distance protection
85
Pilot
directional
pilot scheme
earth-fault
⚫
PTT, Blocking and Unblocking
⚫
Current reversal logic
⚫
Open breaker echo
⚫
Up to 6 zones
⚫
3 independent phase-to-ground distance elements for
protection
21L
Distance protection
PCS-902S Line Distance Relay
Date: 2020-06-01
1-3
1 Introduction
each zone
⚫
1
3 independent phase-to-phase distance elements for
each zone
⚫
Selectable
quadrilateral
characteristics
or
mho
characteristics
⚫
Independent impedance settings and time delays for
each zone
⚫
Zero-sequence
current
compensation
for
phase-to-ground distance element
⚫
Selectable forward direction, reverse direction or non
direction (except zone 1 that is fixed as forward
direction)
21D
78
67P
50/51P
DPFC distance protection
Out-of-step protection
⚫
Load encroachment for each zone
⚫
Power swing blocking and releasing for each zone
⚫
Faulty phase selection for each zone
⚫
Fixed forward direction
⚫
High-speed operation
⚫
Supplementary for zone 1 of distance protection
⚫
Easy to set and independent of system parameters
⚫
Up to 6 stages with independent logic
⚫
Voltage control element for each stage
⚫
Optional direction element for each stage, including
forward direction, reverse direction or non direction
Phase overcurrent protection
⚫
Optional definite-time characteristics and inverse-time
characteristics for each stage
67G
50/51G
⚫
Trip purpose or alarm purpose for each stage
⚫
Harmonic control element for each stage
⚫
Up to 6 stages with independent logic
⚫
Optional direction element for each stage, including
Earth fault protection
1-4
PCS-902S Line Distance Relay
Date: 2020-06-01
1 Introduction
forward direction, reverse direction or non direction
⚫
Optional definite-time characteristics and inverse-time
characteristics for each stage
⚫
Selectable trip purpose or alarm purpose for each
stage
67Q
50/51Q
Negative-sequence
⚫
Harmonic control element for each stage
⚫
Up to 2 stages with independent logic
⚫
Optional direction element for each stage, including
overcurrent
forward direction, reverse direction or non direction
protection
⚫
Optional definite-time characteristics and inverse-time
characteristics for each stage
SOTF
49
Switch onto fault
Thermal overload protection
⚫
Via distance measurement elements
⚫
Via dedicated earth fault element
⚫
Via phase overcurrent element
⚫
Up to 2 stages with independent logic
⚫
Selectable trip purpose or alarm purpose for each
stage
⚫
Up to 2 stages with independent logic
⚫
Optional definite-time characteristics and inverse-time
characteristics for each stage
59P
Phase overvoltage protection
⚫
Optional phase voltage or phase-to-phase voltage
⚫
Optional “1-out-of-3” logic or “3-out-of-3” logic
⚫
Selectable trip purpose or alarm purpose for each
stage
27P
⚫
Up to 2 stages with independent logic
⚫
Optional definite-time characteristics and inverse-time
Phase undervoltage protection
characteristics for each stage
⚫
Optional phase voltage or phase-to-phase voltage
⚫
Optional “1-out-of-3” logic or “3-out-of-3” logic
PCS-902S Line Distance Relay
Date: 2020-06-01
1-5
1
1 Introduction
1
⚫
Blocked by instantaneous VT circuit failure
⚫
Selectable trip purpose or alarm purpose for each
stage
⚫
Optional auxiliary criterion, including CB position check
and current check
59Q
59G
Negative-sequence
⚫
Up to 2 stages with independent logic
⚫
Selectable trip purpose or alarm purpose for each
overvoltage
protection
stage
Residual overvoltage protection
⚫
Up to 2 stages with independent logic
⚫
Selectable trip purpose or alarm purpose for each
stage
81O
81U
81R
32R
⚫
Up to 4 stages with independent logic
⚫
Voltage control element
⚫
Up to 4 stages with independent logic
⚫
Voltage control element
⚫
Up to 4 stages with independent logic
⚫
Voltage control element
⚫
Up to 2 stages with independent logic
⚫
Selectable trip purpose or alarm purpose for each
Overfrequency protection
Underfrequency protection
Rate
of
change
of
protection
Reverse power protection
frequency
stage
⚫
37
Optional auxiliary criterion, including CB position check
and current check
Undercurrent protection
⚫
Selectable trip purpose or alarm purpose for each
stage
50BF
⚫
Phase-segregated re-trip and three-phases re-trip
⚫
Optional current criterion (phase overcurrent element,
Breaker failure protection
zero-sequence
overcurrent
element,
negative-sequence overcurrent element)
⚫
Optional circuit breaker position check
1-6
PCS-902S Line Distance Relay
Date: 2020-06-01
1 Introduction
87STB
Stub differential protection
50DZ
Dead zone protection
⚫
Two time delays
⚫
Protect the T-zone in one-and-a-half breaker and ring
breaker arrangements
⚫
breaker
⚫
46BC
Clear the dead zone faults between CT and the circuit
Broken conductor protection
Adopt the ratio of negative-sequence current to
positive-sequence current (Ι2/Ι1) to detect the broken
conductor.
⚫
62PD
Initiated by three auxiliary contacts of phase-segregate
circuit breaker
Pole discrepancy protection
⚫
Optional auxiliary criterion (zero-sequence current
element or negative-sequence current element)
⚫
25
79
Synchrocheck
Auto-reclosing
Independent logic for auto-reclosing and manually
closing
⚫
One shot or multi-shot
⚫
1-pole AR, 3-pole AR or 1/3-pole AR
⚫
Optional trigger mode, including protection operating
and external binary input
PMU
⚫
Support synchro-check and voltage check
⚫
Compatible
Phasor measurement unit
with
IEEE
C37.118-2005,
IEEE
C37.118.1-2011, IEEE C37.118.2-2011 and IEEE
C37.118.1a-2014.
FL
Fault location
⚫
Single-ended impedance-based method
⚫
Zero-sequence mutual coupling compensation for
parallel lines
TWFL
⚫
Single-ended traveling-wave-based method
⚫
Double-ended traveling-wave-based method
Travelling-Wave fault location
PCS-902S Line Distance Relay
Date: 2020-06-01
1-7