Copyright © 2019 NR. All rights reserved.
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and benefits
afforded under P.R. China and international copyright and patent laws in its products, including but
not limited to software, firmware and documentation. NR Engineering Co., Ltd. is licensed to use
this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd,
including but not limited to copyright, rights in inventions, patents, know-how, trade secrets,
trademarks and trade names, service marks, design rights, database rights and rights in data, utility
models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards, but
no such assurance is given with respect to local codes and ordinances because they vary greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered sufficiently
for your purposes, please do not hesitate to contact us.
Preface
Preface
About This Document
This manual describes the configuration scheme in multiple application scenarios for PCS-9705S
Bay Control Unit, including how to connect the device to a computer and to configure functions,
such as control, protection, measurement and supervision in using of configuration tool.
To start using this manual for application configuration, user should know the basic operations of
the configuration tool PCS-Studio.
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for personal
safety, as well as to avoid material damage. Information is highlighted and illustrated as follows
according to the degree of danger:
Indicates an imminently hazardous situation that, if not avoided, will result
in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation that, if not avoided, may result
in minor or moderate injury or equipment damage.
Indicates that property damage can result if the measures specified are
not taken.
Important information about the product, please pay attention to avoid
undesired result.
Instructions and Warnings
The following hazard statements apply to this device.
Disconnect or de-energize all external connections BEFORE opening this
device. Contact with hazardous voltages and currents inside this device can
cause electrical shock resulting in injury or death.
PCS-9705S Bay Control Unit
Date: 16 January 2020
I
Preface
Contact with instrument terminals can cause electrical shock that can result
in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have ONLY qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
This device is shipped with default passwords. Default passwords should
be changed to private passwords at installation. Failure to change each
default password to a private password may allow unauthorized access. NR
shall not be responsible for any damage resulting from unauthorized access.
DO NOT look into the fibre (laser) ports/connectors.
DO NOT look into the end of an optical cable connected to an optical output.
DO NOT perform any procedures or adjustments that this instruction
manual does not describe.
During installation, maintenance, or testing of the optical ports, ONLY use
the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters,
are NOT user serviceable. Return units to NR for repair or replacement.
II
PCS-9705S Bay Control Unit
Date: 16 January 2020
Preface
Equipment components are SENSITIVE to electrostatic discharge (ESD).
Undetectable permanent damage can result if you do not use proper ESD
procedures. Ground yourself, your work surface, and this equipment
BEFORE removing any cover from this equipment. If your facility is not
equipped to work with these components, contact NR about returning this
device and related NR equipment for service.
Insufficiently rated insulation can deteriorate under abnormal operating
conditions and cause equipment damage. For external circuits, use wiring
of SUFFICIENTLY RATED insulation that will not break down under
abnormal operating conditions.
SEVERE power and ground problems can occur on the communications
ports of this equipment as a result of using non-standard cables. Please use
the wiring method recommended in the manual for communication terminals.
DO NOT connect power to the relay until you have completed these
procedures and receive instruction to apply power. Equipment damage can
result otherwise.
Use of controls or adjustments, or performance of procedures other than
those specified herein, may RESULT IN hazardous radiation exposure.
The firmware may be upgraded to add new features or enhance/modify
existing features, please MAKE SURE that the version of this manual is
compatible with the product in your hand.
Document Conventions
⚫
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The
Glossary also contains definitions of important terms.
⚫
Menu path is connected with the right arrow "→" and bold.
PCS-9705S Bay Control Unit
Date: 16 January 2020
III
Preface
For example: the access path of protection settings is: Main Menu→Settings→Protection
Settings.
⚫
Settings not in the table should be placed in brackets.
For example: the system setting [Opt_SysFreq]
⚫
Cross-references are presented in italics.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫
Binary input signals, binary output signals, analogues, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
For example: press the button "ENT".
Symbols
⚫
AND Gate
&
⚫
&
&
>=1
>=1
OR Gate
>=1
⚫
Comparator
⚫
Binary signal Input
BI
⚫
Signal input
SIG
⚫
xxx
Setting input
SET
IV
xxx
xxx
PCS-9705S Bay Control Unit
Date: 16 January 2020
Preface
⚫
Enable input
EN
⚫
xxx
Timer
Optional definite-time or inverse-time characteristic
Timer
t
t
⚫
Timer
Fixed delay pickup (10ms), fixed delay drop-off (2ms)
10ms
⚫
2ms
Timer
Settable delay pickup, fixed delay drop-off
[Tset1]
⚫
0ms
Timer
Fixed delay pickup, settable delay drop-off
0ms
⚫
[Tset2]
Timer
Settable delay pickup, settable delay drop-off
[Tset1]
⚫
[Tset2]
Generator
G
⚫
Transformer
PCS-9705S Bay Control Unit
Date: 16 January 2020
V
Preface
⚫
Reactor
⚫
Motor
M
⚫
Capacitor
C
⚫
Busbar
⚫
Circuit breaker
52
⚫
Current transformer
3CT
*
⚫
Voltage transformer
3VT
⚫
Disconnector
⚫
Earth
VI
PCS-9705S Bay Control Unit
Date: 16 January 2020
Preface
Three-phase Corresponding Relationship
Basic
A, B, C
L1, L2, L3
R, Y, B
AN, BN, CN
L1N, L2N, L3N
RN, YN, BN
ABC
L123
RYB
U (voltage)
V
U
Example
Ia, Ib, Ic, I0
IL1, IL2, IL3, IN
IR, IY, IB, IN
Ua, Ub, Uc
VL1, VL2, VL3
UR, UY, UB
Uab, Ubc, Uca
VL12, VL23, VL31
URY, UYB, UBR
U0, U1, U2
VN, V1, V2
UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please
consult the manufacturer or agent for warranty information.
Document Structure
This manual is a comprehensive work covering all aspects of device application and configuration.
Read the sections that pertain to your application to gain valuable information about configuring
the device. To concentrate on the target sections of this manual as your job needs and
responsibilities dictate. An overview of each manual section and section topics follows.
1 Functions and Applications
Introduction of device functions and typical application scenarios.
2 Configuration Tool
Introduction of the PCS-Studio configuration tool with the connection method.
3 Protective Functions
Protection functions configuration methods, including function activation method and specific
configuration method of each protection element.
4 Control Functions
Control function configuration methods, including switchgear control, direct control, synchronism
check, voltage selection and tap changer control.
PCS-9705S Bay Control Unit
Date: 16 January 2020
VII
Preface
5 Measurements
Measurement analogue input channels configuration methods which are specified for different
application scenarios
6 Supervision Functions
Supervision functions configuration functions, including circuit supervision of CT and VT, tripping
position supervision and counting.
7 Basic Functions
Basic functions configuration methods, including functions selection through MOT, diagram drawing
of LCD display, communication protocol selection and setting, user authority management,
configuration of binary inputs and outputs, programmable logic, etc.
Appendix A Glossary
List of abbreviations adopted in this manual.
Document Revision History
P/N: ZL_PCS-9705S_X_Application Manual_EN_Overseas General_X
Current Version: R1.00
Version
Release Date
Document
Firmware
R1.00
R1.12
VIII
17 January 2020
Description of change
Initial draft
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1 Functions and Applications
1
Table of Contents
1.1 Functions ......................................................................................................... 1-1
1.1.1 Basic Functions .................................................................................................................... 1-1
1.1.2 Control Functions ................................................................................................................. 1-1
1.1.3 Protection Functions ............................................................................................................. 1-1
1.1.4 Measurement and Metering ................................................................................................. 1-2
1.1.5 Synchrophasor Measurement .............................................................................................. 1-2
1.1.6 Monitoring ............................................................................................................................. 1-3
1.1.7 Communication..................................................................................................................... 1-3
1.1.8 User Interfaces ..................................................................................................................... 1-4
1.1.9 Additional functions .............................................................................................................. 1-4
1.2 Typical Application Scenarios ........................................................................ 1-5
1.2.1 Single Circuit Breaker (with Single Busbar, App1) ............................................................... 1-5
1.2.2 Single Circuit Breaker (with Double Busbars, App1) ........................................................... 1-7
1.2.3 Double Circuit Breakers (App2) ........................................................................................... 1-8
1.2.4 Multiple Busbars (App3) ....................................................................................................... 1-9
1.2.5 Bus Coupler (App3) ............................................................................................................ 1-10
1.2.6 Transformer Sides (App4) .................................................................................................. 1-11
1.2.7 Multiple Bays of One Busbar (App5) .................................................................................. 1-12
1.2.8 I/O Box (App7) .................................................................................................................... 1-13
PCS-9705S Bay Control Unit
Date: 16 January 2020
1-a
1 Functions and Applications
1
1-b
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1.1 Functions
1
1.1.1 Basic Functions
⚫
Multiple setting groups
⚫
Flexibly configurable binary inputs (max. 361)
⚫
Flexibly configurable binary outputs (max. 107)
⚫
Configuration of max.40 users and allow each user to own different password and access
authority
⚫
Function shortcuts key, which can be configured by software tool to execute express
operations.
⚫
Clock synchronization using IRIG-B, SNTP (Simple Network Time Protocol), PPS (Pulse-PerSecond) and PPM (Pulse-Per-Minute), IEEE1588
⚫
Auxiliary functions for simple tests and commissioning
1.1.2 Control Functions
⚫
Switchgear control
⚫
Double point status synthesis
⚫
Remote/Local control mode switch
⚫
Interlocking logic for control
⚫
Direct control
⚫
Closing synchronism check with voltage selection
⚫
Switchgear tripping counter
⚫
Tap position indication and control
1.1.3 Protection Functions
⚫
Breaker failure protection
➢
Phase-segregated re-trip and three-phase re-trip
➢
Optional current criterion (phase overcurrent element, zero-sequence overcurrent
element, negative-sequence overcurrent element)
➢
Optional circuit breaker position check logic
➢
Two time delay settings
PCS-9705S Bay Control Unit
Date: 16 January 2020
1-1
1 Functions and Applications
1
⚫
Transfer trip protection
➢
⚫
Three-phase or phase-segregated
Automatic reclosing
➢
One shot or multi-shot reclosing
➢
1-pole AR, 3-pole AR or 1/3-pole AR
➢
Optional trigger mode, by protection operating and external binary input
➢
Support of synchronism check logic and voltage check logic
1.1.4 Measurement and Metering
⚫
U, I, P, Q, Cos
⚫
Positive, negative and zero sequences
⚫
Max.15th harmonics
⚫
Energy metering (active and reactive energies for import and export)
⚫
Power Quality Supervision (PQS) with Total Harmonic Distortion (THD), deviation and
unbalance
⚫
DC analogue inputs (0~±20mA or 0~±10V)
⚫
DC analogue outputs (4~20mA, 0~10V, 0~5V or 0~20mA)
1.1.5 Synchrophasor Measurement
⚫
The integrated phasor Measurement Unit (PMU) function of synchrophasor measurement is
compatible with IEEE C37.118-2005, IEEE C37.118.1-2011, IEEE C37.118.2-2011 and IEEE
C37.118.1a-2014.
⚫
Supporting time synchronization by IRIG-B signal
⚫
Supporting P Class or M Class measurement (user selectable)
⚫
Measurement of three-phase and single-phase voltage and current
⚫
Measurement of positive/negative/zero-sequence voltage and current
⚫
Calculation of active power, reactive power, system frequency, and rate-of-change of
frequency (ROCOF)
⚫
Measurement of up to 32 binary status (user configurable)
⚫
Output of synchrophasor with timestamp, support of multiple protocols (TCP, TCP-UDP, UDP)
and multiple data rates (2f0, f0, f0/2) for maximum 4 clients (PDC)
1-2
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1.1.6 Monitoring
1
⚫
CT circuit failure Supervision (CTS)
⚫
VT circuit failure Supervision (VTS)
⚫
Self-diagnostic
⚫
Powerful faults recording (max. buffer for 10,000 sampled points at 4.8 or 9.6 kHz)
⚫
Event recorder including 1024 change-of-state events, 1024 supervision events, 256 control
logs and 1024 device logs
⚫
Disturbance recorder including 32 disturbance records with waveforms (format compatible with
COMTRADE)
⚫
Single line diagram representation in display
1.1.7 Communication
⚫
⚫
Support of various protocols
➢
Modbus
➢
DNP3.0
➢
IEC 60870-5-103
➢
IEC 61850 Ed1 & Ed2
➢
IEC 62439 Parallel Redundancy Protocol (PRP)
➢
IEC 62439 High-availability Seamless Ring (HSR) Redundancy Protocol
➢
IEEE 802.1w Rapid Spanning Tree Protocol (RSTP)
Support for digital substation
➢
Extendable quantity of communication interfaces
➢
Support of IEC 61850 MMS Server
➢
Support of IEC 61850-8-1 GOOSE
➢
Support of IEC 61850-9-2LE SMV
⚫
Up to four 10Base-T/100Base-TX copper Ethernet ports
⚫
Up to four 100Base-FX optical Ethernet ports
⚫
Two RS-485 serial ports for communication or printer
⚫
One RS-485/TTL serial port for clock synchronization
⚫
RJ45 debugging ports for both front and rear sides
PCS-9705S Bay Control Unit
Date: 16 January 2020
1-3
1 Functions and Applications
1
1.1.8 User Interfaces
⚫
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point
adjustment
⚫
Push buttons for open/close, switch for selection between local and remote control, and user's
login and logout authority management
⚫
4 Programmable operator pushbuttons with user-configurable labels
⚫
Up to 15/18 programmable target LEDs with user-configurable labels
⚫
1 RS-485 rear ports for printer
⚫
Language switchover: English+ selected language
⚫
Configuration tool: PCS-Studio
1.1.9 Additional functions
⚫
User programmable logic
⚫
System phase sequences rotation function (ABC or ACB)
⚫
Clock synchronization
➢
IRIG-B: IRIG-B via RS-485 differential level or TTL level
➢
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
➢
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
➢
IEEE1588: Clock message based on IEEE1588 via optical fibre interface
➢
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
➢
SNTP (BC): Broadcast SNTP mode via Ethernet network
➢
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus
protocol and DNP3.0 protocol
⚫
1-4
Cyber security
➢
NERC CIP
➢
IEC 62351
➢
IEC 62443
➢
IEEE 1686
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1.2 Typical Application Scenarios
No.
1
Scenario
App1
Single circuit breaker
App2
Double circuit breakers
App3
Busbars
App4
Transformer sides
App5
Bays
App7
I/O box
1.2.1 Single Circuit Breaker (with Single Busbar, App1)
In this scenario, the PCS-9705S is applied to a single circuit breaker with a single busbar. The
three-phase CT and VT are adopted for measurement and protection of the line CB. The singlephase VT is connected to the busbar for synchronism check. An optional single-phase CT may be
adopted for the residual current of line CB.
The circuit breaker and the relevant disconnector switches and earthing switches in this bay could
be controlled by the device. Breaker failure protection and auto-reclosing function are optional to
be adopted as the backup of line protection. Meanwhile, supervision functions of analog input
channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping
counter, etc. are equipped for the operating reliability and safety of the device. Moreover, phasor
measurement unit (PMU) function for synchrophasor measurement may be integrated.
PCS-9705S Bay Control Unit
Date: 16 January 2020
1-5
1 Functions and Applications
1
Busbar
1VT
52
25
79
3VTs
VTS
*
3CTs
CTS
*
50BF
PMU
1CT
FR
CSWI
1-6
XCBR
XSWI
CILO
84
PQS
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1.2.2 Single Circuit Breaker (with Double Busbars, App1)
In this scenario, the PCS-9705S is applied to a single circuit breaker with double busbars. The
three-phase CT and VT are adopted for measurement and protection of the line CB. Two singlephase VTs are connected to the two busbars respectively for synchronism check. An optional
single-phase CT may be adopted for the residual current of line CB.
The circuit breaker and the relevant disconnector switches and earthing switches in this bay could
be controlled by the device. Breaker failure protection and auto-reclosing function are optional to
be adopted as the backup of line protection. Meanwhile, supervision functions of analog input
channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping
counter, etc. are equipped for the operating reliability and safety of the device. Moreover, phasor
measurement unit (PMU) function for synchrophasor measurement may be integrated.
Busbar 1
Busbar 2
1VT
1VT
52
25
79
3VTs
VTS
*
3CTs
CTS
*
50BF
PMU
1CT
FR
CSWI
XCBR
PCS-9705S Bay Control Unit
Date: 16 January 2020
XSWI
CILO
84
PQS
1-7
1
1 Functions and Applications
1
1.2.3 Double Circuit Breakers (App2)
In this scenario, the PCS-9705S is applied to the tie CB and one bus CB in 3/2 CB arrangement.
Two three-phase CTs are adopted for measurement of the tie CB and one bus CB. A three-phase
VT is adopted between the tie CB and one bus CB for measurement of the outgoing line. Three
single-phase VTs are connected to the two busbars and the other outgoing line respectively for
synchronism check.
The three circuit breakers and the relevant disconnector switches and earthing switches in this
arrangement could be controlled by the device. Meanwhile, supervision functions of analog input
channels, binary input channels, CT secondary circuits, VT secondary circuits, switchgear tripping
counter, etc. are equipped for the operating reliability and safety of the device.
Busbar1
3CTs
*
1VT
Bus1
CB
52
25
3VTs
VTS
3CTs
Tie
CB
*
CTS
52
1VT
Bus2
CB
FR
52
CSWI
Busbar2
1-8
XCBR
XSWI
CILO
84
PQS
1VT
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1.2.4 Multiple Busbars (App3)
In this scenario, the PCS-9705S is applied to up to 4 busbars. A three-phase VT is adopted for
measurement of each busbar.
The relevant disconnector switches and earthing switches of busbars and outgoing lines could be
controlled by the device. Meanwhile, supervision functions of analog input channels, binary input
channels, VT secondary circuits, switchgear tripping counter, etc. are equipped for the operating
reliability and safety of the device.
...
Busbar 1
Busbar n
3VTs
3VTs
VTS
FR
CSWI
XSWI
CILO
84
PCS-9705S Bay Control Unit
Date: 16 January 2020
PQS
1-9
1
1 Functions and Applications
1
1.2.5 Bus Coupler (App3)
In this scenario, the PCS-9705S is applied to a bus coupler between two busbars. The three-phase
CT is adopted for measurement of the bus coupler. Two three-phase VTs are adopted for
measurement of the two busbars respectively.
The bus coupler and the relevant bus disconnector switches and earthing switches in this bay could
be controlled by the device. Meanwhile, supervision functions of analog input channels, binary input
channels, CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc. are
equipped for the operating reliability and safety of the device.
Busbar2
Busbar1
3CTs
*
52
3VTs
3VTs
CTS
1-10
VTS
25
FR
CSWI
XCBR
XSWI
CILO
PQS
PCS-9705S Bay Control Unit
Date: 16 January 2020
1 Functions and Applications
1.2.6 Transformer Sides (App4)
In this scenario, the PCS-9705S is applied to up to 4 sides of a transformer. A three phase CT is
adopted for measurement between the busbar and the transformer of each side. A three-phase VT
is adopted for measurement of each side.
The circuit breakers and relevant disconnector switches and earthing switches could be controlled
by the device. Meanwhile, supervision functions of analog input channels, binary input channels,
CT secondary circuits, VT secondary circuits, switchgear tripping counter, etc. are equipped for the
operating reliability and safety of the device.
HV Side
*
3CTs
52
3VTs
25
VTS
3VTs
52
CTS
CSWI
*
FR
XCBR
XSWI
CILO
84
PQS
3CTs
LV Side
PCS-9705S Bay Control Unit
Date: 16 January 2020
1-11
1